4.4.1 The unit of exit width, used to measure the capacity of any exit, shall be 500 mm. A clear width of 250 mm shall be counted as an additional half unit. Clear widths less than 250 mm shall not be counted for exit width.
NOTE — The total occupants from a particular floor must evacuate within 2½ minutes for Type 1 construction, 1½ minutes for Type 2 construction and 1 minute for Type 3 construction. Size of the exit door/exitway shall be calculated accordingly keeping in view the travel distance as per Table 22.
4.4.2 Occupants per unit exit width shall be in accordance with Table 21.
4.4.3 Horizontal Exit Allowance
When horizontal exit is provided in buildings of mercantile, storage, industrial, business and assembly occupancies, the capacity per storey per unit width of exit of stairways in Table 21 may be increased by 50 percent and in buildings of institutional occupancy it may be increased by 100 percent.
| Sl No. | Group of Occupancy | Occupant Load, Floor Area in m²/Person |
|---|---|---|
| (1) | (2) | (3) |
| i) | Residential (A) | 12.5 |
| ii) | Educational (B) | 4 |
| iii) | Institutional (C) | 15 (see Note 1) |
| iv) | Assembly (D) | |
| a) With fixed or loose seats and dance floors | 0.6 (see Note 2) | |
| b) Without seating facilities including dining rooms | 1.5 (see Note 2) | |
| v) | Mercantile (F) | |
| a) Street floor and sales basement | 3 | |
| b) Upper sale floors | 6 | |
| vi) | Business and industrial (E&G) | 10 |
| vii) | Storage (H) | 30 |
| viii) | Hazardous (J) | 10 |
1 Occupant load in dormitory portions of homes for the aged, orphanages, insane asylums, etc, where sleeping accommodation is provided, shall be calculated at not less than 7.5 m2 gross floor area/person.
2 The gross floor area shall include, in addition to the main assembly room or space, any occupied connecting room or space in the same storey or in the storeys above or below, where entrance is common to such rooms and spaces and they are available for use by the occupants of the assembly place. No deductions shall be made in the gross area for corridors, closets or other sub-divisions; the area shall include all space serving the particular assembly occupancy.
| Sl No. | Group of Occupancy | Number of Occupants | ||
| Stairways | Ramps | Doors | ||
| (1) | (2) | (3) | (4) | (5) |
| i) | Residential (A) | 25 | 50 | 75 |
| ii) | Educational (B) | 25 | 50 | 75 |
| iii) | Institutional (C) | 25 | 50 | 75 |
| iv) | Assembly (D) | 40 | 50 | 60 |
| v) | Business (E) | 50 | 60 | 75 |
| vi) | Mercantile (F) | 50 | 60 | 75 |
| vii) | Industrial (G) | 50 | 60 | 75 |
| viii) | Storage (H) | 50 | 60 | 75 |
| ix) | Hazardous (J) | 25 | 30 | 40 |