a. Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
Chapter 5
Provision of High Rise Development
b. No exit doorway shall be less than 1m in width. Doorways shall be not less than 2 m in height. Doorways for bathrooms, water closet, stores etc. shall be not less than 0.75m wide.
c. Exit doorways shall open outwards, that is, away from the room but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 0.9m, overhead or sliding doors shall not be installed.
d. Exit door shall not open immediately upon a flight or stairs, a landing equal to at least the width of the door shall be provided in the stairway at each doorway, level of landing shall be the same as that of the floor which it serves.
e. Exit doorways shall be openable from the side which they serve without the use of a key.
f. Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
5.4.2 Revolving Doors
Revolving door shall not be provided as a means of fire exit.
5.4.3Stairways
a. A staircase shall not be arranged round a lift shaft.
b. The staircase shall be ventilated to the atmosphere at each landing and a vent at the top; the vent openings shall be of 0.5 sq.m in the external wall and the top. If the staircase cannot be ventilated, because of location or other reasons, a positive pressure 50 Pa shall be maintained inside. The mechanism for pressurizing the staircase shall operate automatically with the fire alarm. The roof of the shaft shall be 1 m above the surrounding roof. Glazing or glass bricks if used in staircase, shall have fire resistance rating of minimum 2 hour.
c. The minimum width of staircase shall be as table given below:
Table 5.1Minimum width of Staircase for different types of Buildings
Sl No.
Types of Building
Minimum Width (in meter)
1
Residential Buildings (dwellings)
1.20
3
Residential hotel buildings
1.50
4
Assembly buildings like auditorium, Banquet Hall, theatres and cinemas
2.00
5
Educational buildings
2.00
6
Institutional Buildings training centers,
2.00
7
Medical/Nursing Home/Polyclinic Building
2.00
8
All other buildings commercials and semi commercial
1.50
d. The minimum width of treads without nosing shall be 0.25m for staircase for residential buildings. In the case of other buildings, the minimum tread shall be 0.30m. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 0.19m in the case of residential buildings and 0.15m in the case of other buildings and shall be limited to 15 risers per flight.
e. Handrails shall be provided with a minimum height of 0.9m from the center of the tread.
f. The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2m.
g. g. Access to main staircase shall be gained through adequate fire resistance rating (clause 11.7.1 of Chapter 11) Automatic closing doors placed in the enclosing walls of the staircases. It shall be a swing type door opening in the direction of the escape.
h. No living space, store or other fire risk shall open directly into the staircase or staircases. External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a draught lobby.
i. The exit sign with arrow indicating the way to the escape route shall be provided at a height of 0.5m from the floor level on the wall and shall be illuminated by electric light connected to corridor
Chapter 5
Provision of High Rise Development
circuits. All exit way marking signs should be flushed with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment’s. Further all landings of floor shall have floor indication boards indicating the number of floor. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5x 0.5m and it shall be prominently on the wall facing the staircase.
j. In case of single staircase, it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. However, the second staircase may lead to basement levels provided the same is separated at ground level by either a ventilated lobby with discharge points at two different ends or through enclosures with fire resistance rating door (clause 11.7.1 of Chapter 11) or through a fire protected corridor.
Chapter 5Provisions for High Rise Development
5.1 High Rise
Buildings higher than 15 meters of height without stilts and above 17.4m of height with stilts shall be considered as high rise building.
Note: These provisions shall be in addition to the Chapter 3 for plan sanction procedure, general building requirements (low/high) given in Chapter 4 of this document and structural safety given in Chapter 6.
5.1.1 Plot Area
Plots to be used for high rise development should be located in an approved Layout plan, Comprehensive plans or sub division plans as prepared and approved by competent authorities/ as per policy of the Government of India / State Governments.
5.1.2 Means of access
a. A building shall abut on a street or streets or upon spaces directly connected from the street by a hard surface approach road, width of approach road is not less than 9 meters,
b. If there are any bends or curves on the approach road, a sufficient width shall be provided at the curve to enable the fire appliances to turn, the turning circle being at least of 9.0 m radius. Where entry to the plot is through a slip road the gate width shall not be less than 6 m for entry of the firefighting appliance.
c. The approach road to the building and open spaces on its all sides up to 6 m width and the layout for the same shall be done in consultation with Director Fire Services, Fire Service and the same shall be reinforced to ensure safety of the fire equipment and capable of taking the weight of Fire engine, weighing up to 45 tonnes) The said open space shall be kept free of obstructions and shall be motorable.
d. Main entrances to the premises shall be of adequate width to allow easy access to the fire engine and in no case it shall measure less than 6 m. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for movement of fire service vehicles. If archway is provided over the main entrance the height of the archway shall not be at a height less than 5m.
e. For multistoried group housing schemes on one plot, the approach road to the site shall be minimum 9.00 m in width.
5.2 Peripheral Open Spaces including set backs
There shall be a space of 5 meters in front and 3 meters in three sides of the building.
5.3 Parking Spaces
a. The parking spaces shall be provided as per the provisions of Master Plan or Zonal plan as prevalent. The location of parking spaces shall be well ventilated.
b. In case of high-rise buildings parking will be permitted at any / all of the following:
i. Basements
ii. Stilts
72
iii. Podium
c. Stacked/ Multi-level/ Automated parking is also permitted.
5.4.4Lifts
General requirements of lifts shall be as follows:
a. All the floors shall be accessible for 24 hours by the lifts. The lifts provided in the buildings shall not be considered as a means of escape in case of emergency. In a dual line arrangement (lifts opposite to each other) the lobby may be between 1.5 times to 2.5 times the depth of one car. For in-line (single line) arrangements the lobby may be typically half of the above recommendations.
b. Grounding switch, at ground floor level, to enable the fire service to ground the lift shall also be provided.
c. The lift machine room shall be separate and no other machinery shall be installed therein.
d. Walls of lift enclosures and lift lobby shall have fire rating of 2 hours; (Refer Section 11.7.1 of Chapter 11); lifts shall have a vent at the top of area not less than 0.2 sq.m
e. Lift car door shall have a fire resistance rating of 1 hour.
f. Lift lobby doors in lift enclosures shall have fire resistance as per Section 11.7.1 of Chapter 11.
g. Collapsible gates shall not be permitted for lifts and shall have solid doors with fire resistance of at least 1 hour.
h. If the lift shaft and lobby is in the core of the building, a positive pressure between 25 and 30 Pa shall be maintained in the lobby and a positive pressure of 50 Pa shall be maintained in the lift shaft. The mechanism for pressurization shall act automatically with the fire alarm; it shall be possible to operate this mechanically also.
i. Lifts if communicating with the basement, the lift lobby of the basements shall be pressurized as suggested in clause 11.9.1(g) and 11.9.1(h) with self-closing door with fire resistance rating (Refer Section 11.7.1 of Chapter 11). Telephone or other communication facilities shall be provided in lift cars and to be connected to fire control room for the building.
j. Exit from the lift lobby, if located in the core of the building, shall be through a self-closing fire door of half an hour fire resistance.
k. Suitable arrangements such as providing slope in the floor of lift lobby shall be made to prevent water used during firefighting, etc., at any landing from entering the lift shafts.
l. A sign shall be posted and maintained on every floor at or near the lift indicating that in case of fire, occupants shall use the stairs unless instructed otherwise. The sign shall also contain a plan for each floor showing the locations of the stairways. Alternate source of power supply shall be provided for all the lifts through a manually operated changeover switch.
m. For Pressurization Specifications of various building components refer NBC Chapter 4 Fire and Life Safety Clause 4.10 Pressurization of Staircases (Protected Escape Routes)
5.4.5Basements
a. Basement shall be permitted within the setback lines subject to clearance from local bodies/departments concerned, Competent Authority/Municipal Corporation and Fire Department. Where there are no setbacks, basement should be permitted after leaving 2 m and
Chapter 5
Provision of High Rise Development
where there is setback, it should be after leaving required 6 m from plot boundary (as per provisions of development control norms of Master Plan).
b. Each basement shall be separately ventilated. Vents with cross-sectional area (aggregate) not less than 2.5 percent of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills or breakable stall board lights or pavement lights or by way of shafts. Alternatively, a system of air inlets shall be provided at basement floor level and smoke outlets at basement ceiling level. Inlets and extracts may be terminated at ground level with stall board or pavement lights as before, but ducts to convey fresh air to the basement floor level have to be laid. Stall board and pavement lights should be in positions easily accessible to the fire brigade and clearly marked ‘SMOKE OUTLET’ or ‘AIR INLET’ with an indication of area served at or near the opening.
c. The staircase of basements shall be of enclosed type having fire resistance rating (Refer Section 11.7.1 of Chapter 11). The staircase shall be situated at the periphery of the basement to be entered at ground level only, from outside open air. The staircase shall communicate with basement through a lobby with self-closing doors with fire resistance rating as per relevant NBC code mentioned above.
d. For travel distance Table 5.2 given below shall be followed. If travel distance exceeds that given in the table below, additional staircases shall be provided.
Table 5.2Travel Distance for Occupancy and Type of Construction
Sl. No
Group of Occupancy
Maximum Travel Distance Construction
Type 1 &2
Type 3 & 4
i.
Residential(A)
30.0
22.5
ii.
Educational(B)
30.0
22.5
iii.
Institutional
30.0
22.5
iv
Assembly(D)
30.0
30.0
v
Business(E)
30.0
30.0
vi
Mercantile(F)
30.0
30.0
vii
Industrial(G)
45.0
Construction type 3 and 4 not permitted.
viii
Storage(H)
30.0
Construction type 3 and 4 not permitted.
ix
Hazardous(J)
22.5
Construction type 3 and 4 not permitted.
Notes:
Notes
For fully sprinkled building, the travel distance may be increased by 50% of the values specified above
Ramps shall be counted as one of the means of escape wherever permitted in National Building Code 2005.
e. In multi-story basements, intake ducts may serve all basement levels, but each basement level and basement compartment shall have separate smoke outlet duct or ducts. Ducts so provided shall have the same fire resistance rating as the compartment itself. Fire rating may be taken as the required smoke extraction time for smoke extraction ducts.
f. Mechanical extractors for smoke venting system from lower basement levels shall also be provided. The system shall be of such design as to operate on actuation of heat / smoke sensitive detectors or sprinklers, if installed, and shall have a considerably superior performance compared to the standard units. It shall also have an arrangement to start it manually.
Chapter 5
Provision of High Rise Development
g. Mechanical extractors shall have an internal locking arrangement, so that extractors shall continue to operate and supply fans for HVAC shall stop automatically with the actuation of fire detectors.
h. Mechanical extractors shall be designated to permit 30 air changes per hour in case of fire or distress call. However, for normal operation, air changes schedule shall be as given in Part 8, Building Services, Section 3, Air-conditioning, Heating and Mechanical Ventilation of National Building Code, 2005.
i. Mechanical extractors shall have an alternative source of supply.
j. Ventilating ducts shall be integrated with the structure and made out of brick masonry or reinforced cement concrete and when this duct crosses the transformer area or electrical switchboard, fire dampers shall be provided.
k. Use of basements for kitchens working on gas fuel shall not be permitted, unless air conditioned. The basement shall not be permitted below the ward block of a hospital/nursing home unless it is fully sprinkled. Building services such as electrical sub- stations, boiler rooms in basements shall comply with the provisions of the Indian Electricity Act / Rules. Boiler room shall be provided at the first basement along the periphery wall with fire resistance rating (Refer Section 11.7.1 of Chapter 11) or shall be separated with the blast wall.
l. If cutouts are provided from basements to the upper floors or to the atmospheres, all sides cutout openings in the basements shall be protected by sprinkler head at close spacing so as to form a water curtain in the event of a fire.
m. It is essential to make provisions for drainage of any such water on all floors to prevent or minimize water damage of the contents. The drain pipes should be provided on the external wall for drainage of water from all floors. On large area floors, several such pipes may be necessary which should be spaced 30 m apart. Care shall be taken to ensure that the construction of the drain pipe does not allow spread fire / smoke from floor to floor.
5.4.6 Compartmentation
The building shall be suitably compartmentalized so that fire/smoke remains confined to the area where fire incident has occurred and does not spread to the remaining part of the building.
Compartmentation and Pressurization method shall be adopted (as per clause 4.10 of Part 4 of NBC, 2005) to protect escape routes against ingress of smoke, or toxic gases into the escape routes will be prevented. Pressurization shall be adopted for high rise buildings and building having mixed occupancy/multiplexes having covered area more than 500 m2.