4.25.7.1 Ramps
a. The ramp to basement and parking floors shall not be less than 7.2m wide for two-way traffic and 4 m wide for one-way traffic, provided with Gradient of 1:10 for cars and 1:15 for heavy vehicles. At curved portions of the ramp or for circular ramps the slope should not be more than 1:12.
b. Ramps may also be provided in the setbacks which can be sloped considering unhindered movement of fire engine and in no case the gradient shall be less than 1:10
c. All structural design/safety aspects as per latest BIS Codes & NBC, 2005 shall be complied along with consideration of weight of Fire Engine & its maneuverings.
d. The minimum width of the ramps in hospitals shall be 2.4 m for stretcher and not for vehicular movement.
e. In this case Handrails shall be provided on both sides of the ramp.
f. Ramps shall lead directly to outside open space at ground level or courtyards or safe place
Ramps with Gradients
a. Where ramps with gradients are necessary or desired, they shall conform to the following requirements.
b. A ramp when provided should not have a slope greater than 1 in 20 or maximum of 1 in 12 for short distance up to 9000 mm.
c. A ramp shall have handrails on at least one side, and preferably two sides, that are 900 mm high, measured from the surface of the ramp, that are smooth, and that extend 300 mm beyond the top and bottom of the ramp. Where major traffic is predominantly children, the handrails should be placed 760 mm high.
Notes
Where handrails are specified to be of heights other than 80 cm, it is recommended that two sets of handrails be installed to serve all people. Where major traffic is predominantly children, particularly physically disabled children, extra care should be exercised in the placement of handrails, in accordance with the nature of the facility and the age group or groups being serviced.
ii. Care should be taken that the extension of the handrails is not in itself a hazard. Extension up to 300 mm may be made on the side of a continuing wall.
iii. A ramp shall have a surface that is non-slip surface and if length is 3500 mm, the minimum width shall be 1500 mm. greatly assists the challenged persons with semi-ambulatory and ambulatory disabilities. Non-slip surfaces are provided by many finishes and materials. The surfaces of the concrete ramps can be made nonskid by brooming the surface or by finishing with an indenting roller.
iv. A ramp shall have a level platform at the top which is at least 1800 mm long, if a door swings out onto the platform or toward the ramp. This platform shall extend at least 300 mm beyond each side of the doorway.
v. Each ramp shall have at least 1800 mm of straight clearance at the bottom.
vi. Ramps shall have level platforms at 10 m to 12 m intervals for purposes of rest and safety, and shall have platforms minimum 1.5 m length wherever they turn.
vii. For visually impaired people, ramps may be colour contrasted with landing.
viii. To minimize rise to wheelchair users, ramps should be equipped with herbs approximately 50 mm high at exposed sides.
Department of Town Planning & ULBs, Govt. of Arunachal Pradesh|| Arunachal Pradesh Building Byelaws 2019
Chapter 4
4.25.7.1 Doorways
a. Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
b. No exit doorways shall be less than 1m in width except assembly and institutional buildings where Doorway shall not be less than 2 m.
c. Exit doorways shall open outwards, that is away from the room but shall not obstruct the travel along any exit. No door when opened shall reduce the required width of stairway or landing to less than 0.90 m Overhead or sliding door shall not be installed.
In the case of buildings where there is a central corridor, the doors of rooms shall open inwardsto permit smooth flow of traffic in the corridor
d. Exit door shall not open immediately upon a flight of stairs. A landing equal to at least, the width of the door shall be provided in the stairway at each doorway. Level of landings shall be the same as that of the floor, which it serves.
e. Exit doorways shall be open able from the side, which they serve without the use of a key.
f. Revolving doors shall not to be provided as means of fire exit.
g. Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.