The following exemption to open space shall be permitted.
4.30.1 Projections into Open Spaces
a) Every interior or exterior open space shall be kept, free from any erection thereon and shall be open to the sky. Nothing except cornice, chajja or weather shade (not more than 0.75 m. wide) shall overhang or project over the said open spaces so as to reduce the width to less than the minimum required.
Note: Such projections shall not be allowed at a height less than 2.20 m. from the corresponding finished floor level
b) A canopy or canopies each not exceeding 4.50 m. in length and 2.40 m. in width in the form of cantilever or cantilevers, over the main entrance/entrances, providing a minimum clear height of 2.30 m. below the canopy.
In single storeyed residential building, only one such canopy shall be permitted for each individual detached block. In more than one storeyed residential building, two canopies shall be permitted over ground floor/higher floor entrances.
Chapter 4
In buildings of other occupancies, the permissibility of canopy, canopies shall be as decided by the Authority on its merits.
c) In case of residential building only, a balcony or balconies at roof level of a width of 1.20 m. overhanging in set-backs within one’s own land. The courtyards provided the minimum area required shall not be reduced by more than 30% of such open spaces.
d) The projections (cantilever) of cupboards and shelves shall be permitted and are exempted from covered area calculations in case of residential buildings only. Such projection shall be upto 0.75 m. depth provided.
i) That no cupboard shall project in the side set back on the ground floor.
ii) That outer length of cupboard overhanging in the set-backs shall not exceed 2.0 m. per habitable room. In addition to this, cupboard under the above and windows can be provided.
Note: Cupboard means a space used for storage of household goods/clothes, having shelves/partitions not more than 1.5 m. apart.
iii) Only one pergola on each floor shall be permitted in a residential building if constructed in the exterior open spaces or terrace.
Such pergola shall not exceed 3.50 sq m. in area on which 40% shall be void & shall have a clear height 2.20 m.
4.30.1.1 In addition to above, the following shall not be included in covered area for FAR calculations.
a) Machine room for lift on top floor as required for the lift machine installation (see Appendix ‘Ll’ and ‘L2’).
Note: The shaft provided for lift shall be taken for covered area calculations only on one floor.
b) Rockery, well and well structures, plant nursery, water pool, swimming pool (if uncovered), platform round a tree, tank, fountain, bench, chabutara with open top and / or unenclosed sides by walls, open ramps, compound wall, gate, slide swing door, uncovered staircase (uncovered and unclosed on three sides except for a 0.90 m. high railing/wall, overhead water tank on top of building/open shafts.
c) A mumty over staircase on top floor.
d) Culvert on Municipal drains.
4.30.2 Height Limit
The Height and number of storeys shall be related to provisions of FAR as given in Chapter-3 and the provisions of open spaces given in Building Bye-Laws and the following:
a) The maximum height of building shall not exceed 1.5 times the width of road abutting plus the front open spaces.
b) If a building abuts on two or more streets of different width, the building shall be deemed to face upon the street that has the greater width and the height of the building shall be regulated by the width of that street. Height shall however, not exceed the maximum height of 15 meters.
c) For buildings in the vicinity of the aerodromes the maximum height of such buildings shall be in accordance with regulations of “critical” and “non-critical” zones as identified by the AAI in its Colour-Coded Zoning Maps (CCZM). The application for Building plan approval shall be processed by the Authority as per the CCZM for ‘non-critical’ areas.
Note: The location of slaughter house/butcher house and other areas for activities like depositing of garbage dumps which would attract high flying birds like eagles/hawks etc. shall not be permitted within a radius of 10 km. from aerodrome reference point.
Chapter 4
4.30.3 Height Exemptions
The following appurtenant structures shall not be included in the height of building covered under Building Bye-Laws 4.9.7.
a. Roof tanks and their supports not exceeding 1.0 m. in height,
b. Ventilating, air conditioning and lift rooms and similar service equipments, stair covered with Mumpty not exceeding 3.00 m. in height.
c. Chimneys and parapet wall and architectural features not exceeding 1.50 m. in height, unless the aggregate area of such structures exceeds 1/3 of the roof area of the building on which they are erected.
d. All such appurtenant structures shall be camouflaged to achieve streamlined aesthetics.