a. A staircase shall not be arranged round a lift shaft.
b. The staircase shall be ventilated to the atmosphere at each landing and a vent at the top; the vent openings shall be of 0.5 sq.m in the external wall and the top. If the staircase cannot be ventilated, because of location or other reasons, a positive pressure 50 Pa shall be maintained inside. The mechanism for pressurizing the staircase shall operate automatically with the fire alarm. The roof of the shaft shall be 1 m above the surrounding roof. Glazing or glass bricks if used in staircase, shall have fire resistance rating of minimum 2 hour.
c. The minimum width of staircase shall be as table given below:
| Sl No. | Types of Building | Minimum Width (in meter) |
|---|---|---|
| 1 | Residential Buildings (dwellings) | 1.20 |
| 3 | Residential hotel buildings | 1.50 |
| 4 | Assembly buildings like auditorium, Banquet Hall, theatres and cinemas | 2.00 |
| 5 | Educational buildings | 2.00 |
| 6 | Institutional Buildings training centers, | 2.00 |
| 7 | Medical/Nursing Home/Polyclinic Building | 2.00 |
| 8 | All other buildings commercials and semi commercial | 1.50 |
d. The minimum width of treads without nosing shall be 0.25m for staircase for residential buildings. In the case of other buildings, the minimum tread shall be 0.30m. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 0.19m in the case of residential buildings and 0.15m in the case of other buildings and shall be limited to 15 risers per flight.
e. Handrails shall be provided with a minimum height of 0.9m from the center of the tread.
f. The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2m.
g. g. Access to main staircase shall be gained through adequate fire resistance rating (clause 11.7.1 of Chapter 11) Automatic closing doors placed in the enclosing walls of the staircases. It shall be a swing type door opening in the direction of the escape.
h. No living space, store or other fire risk shall open directly into the staircase or staircases. External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a draught lobby.
i. The exit sign with arrow indicating the way to the escape route shall be provided at a height of 0.5m from the floor level on the wall and shall be illuminated by electric light connected to corridor
Chapter 5
Provision of High Rise Development
circuits. All exit way marking signs should be flushed with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment’s. Further all landings of floor shall have floor indication boards indicating the number of floor. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5x 0.5m and it shall be prominently on the wall facing the staircase.
j. In case of single staircase, it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. However, the second staircase may lead to basement levels provided the same is separated at ground level by either a ventilated lobby with discharge points at two different ends or through enclosures with fire resistance rating door (clause 11.7.1 of Chapter 11) or through a fire protected corridor.