Revolving doors shall not be provided as a means of fire exit.
3 Stairways.
(a) A staircase shall not be arranged round a lift shaft.
(b) The staircase shall be ventilated to the atmosphere at each landing and a vent at the top, the vent openings shall be of 0.5 sqm. in the external wall and the top. If the staircase cannot be ventilated, because of location or other reasons, a positive pressure 50 pa shall be maintained inside. The mechanism for pressurizing the staircase shall operate automatically with the fire alarm. The roof of the shaft shall be 1m above the surrounding roof, glazing or glass bricks if used in staircase shall have fire resistance rating of minimum 2 hour.
(c) The minimum width of staircase shall be as given below:
| Type of building | width |
|---|---|
| Residential building(dwellings) | 1.0 m |
| Residential hotel buildings | 1.5 m |
| Assembly buildings like auditorium, theatre, cinemas. | 2.0 m |
| Educational buildings up to 30m in height | 1.5 m |
| Institutional buildings like hospitals | 2.0 m |
| All other buildings | 1.5 m |
(d) The minimum width of treads without nosing shall be 0.25 m for staircase for residential building. In case of other buildings, the minimum tread shall be 0.3 m. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 0.19 m in the case of residential building and 0.15 m in the case of other buildings and shall be limited to 15 risers per flight.
(e) Handrails shall be provided with a minimum height of 0.9 m from the centre of the tread
(f) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
(g) Access to main staircase shall be gained through adequate resistance rating. Automatic closing door placed in the enclosing walls of the staircases. It shall be swing type door opening in the direction of the escape.
(h) No living space, store or other for risk shall open directly to the open space, store or other fire risk shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a drought lobby.
(i) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a drought lobby.
(j) The exit sign with arrow indicating the way to the escape route shall be provided at a height of 0.5 m from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way making signs shall be flushed with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further all landing of floors shall have floor indication boards indicating the number of floors. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 mx0.5 m and it shall be prominently on the wall facing the staircase.
(k) In case of single staircase, it shall terminate at the ground floor and access to the basement shall be by a separate staircase. However, the second staircase may lead to basement levels provided the same is separated at ground level by either a ventilated lobby with discharge points at two different ends or through enclosures with fire resistance rating door or through a fire protected corridor.
4. Lifts
General requirements of the lifts
(a) All the floors shall be accessible for 24 hours by the lift.
(b) Grounding switch at ground floor level to enable the fire service to ground the lift shall also be provided.
(c) The lift machine room shall be separate and no other machinery shall be installed therein.
(d) Walls of lift enclosures and lift lobby shall have fire rating of 2 hour. Lifts shall have vent at the top of area not less than 0.2 sq. m
(e) Lift car door shall have a fire resistance rating of 1 hour.
(f) Lift lobby doors in lift enclosures shall have fire resistance as per section11.7.1 of chapter 11.
(g) Collapsible gates shall not be permitted for lifts and shall have solid doors with fire resistance of at least 1 hr.
(h) If the lift shaft and lobby is in the core of the building a positive pressure between 25 and 30 pa shall be maintained in the lobby and appositive pressure of 50 pa shall be maintained in the lift shaft. The mechanism for pressurization shall act automatically with a fire alarm. It shall be possible to operate this mechanically also.
(i) Lifts communicating with the basement, the lift lobby of the basements shall be pressurized as suggested in Clause 11.9.1 (g) and 11.9.1 (h) with self-closing door with fire resistance rating (refer section 11.7.1 of chapter 11). Telephone or other communication facilities shall be provided in lift cars and to be connected to fire control room for the building
(j) Exit from the lift lobby, if located in the core of the building shall be through a self-closing fire door of half an hour fire resistance.
(k) Suitable arrangements such as providing slope in the floor of lift lobby shall be made to prevent water used during firefighting etc. at any landing from entering the lift shafts.
(l) A sign shall be posted and maintained on every floor at or near the lift indicating that in case of fire, occupants shall use the stairs unless instructed otherwise. The sign shall also contain a plan for each floor showing the
location of stairways. Alternate source of power supply shall be provided for all the lifts through a manually operated change over switch.
(m) For pressurization specifications for various building components refer chapter 4 of NBC and lift safety clause 4.10.
5. Basements
(a) Basements shall be permitted within the setback lines subject to clearance from the local bodies/departments concerned, Municipal Corporation and Fire Departments. Where there are no setbacks, it should be after leaving required 6 m from plot boundary (as per development control rules of Master Plan)
(b) Each basement shall be separately ventilated. Vents with cross sectional area not less than 2.5 percent of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills or breakable stall board lights or pavement lights or by way of shafts. Alternatively, a system of air inlets shall be provided at basement floor level and smoke outlets at basement ceiling level, inlets and extracts may be terminated at ground level with stall board or pavement lights as before, but ducts to convey fresh air to the basement floor level have to be laid. Stall board and pavement lights should be in positions easily accessible to the fire brigade and clearly marked ‘SMOKE OUTLET’ or ‘AIR INLET’ with an indication of area served or near the opening.
(c) The staircase of basement shall be of enclosed type having fire resistance rating. The staircase shall be situated at the periphery of the basement to be entered at ground level only from outside open air. The staircase shall communicate with basement through a lobby with self-closing doors with fire resistance rating as per relevant NBC code mentioned above.
(d) For travel distance Table given below shall be followed. If travel distance exceeds that given in the table below, additional staircases may be provided.
| No | Group of occupancy | Maximum travel distance construction | |
| Type 1 & 2 | Type 3&4 | ||
| i | Residential (A) | 30.0 | 22.5 |
| ii. | Educational (B) | 30.0 | 22.5 |
| ii. | Institutional | 30.0 | 22.5 |
| iv. | Assembly(D) | 30.0 | 30.0 |
| v. | Business(E) | 30.0 | 30.0 |
| vi. | Mercantile((F) | 30.0 | 30.0 |
| vii. | Industrial(G) | 45.0 | Construction Type 3 &4 not permitted |
| viii. | Storage(H) | 30.0 | Construction Type 3 &4 not permitted |
| ix. | Hazardous(J) | 22.5 | Construction Type 3 &4 not permitted |
6. Compartmentation
The building should be suitably compartmentalized so that fire /smoke remains confined to the area where fire incident has occurred and does not spread to the remaining part of the building. Compartmentalization and pressurization method shall be adopted as per clause 4.10 of Para 4 of NBC 2005.
7. Ramps
(a) The ramps to basement and parking floors shall be not less than 7.2 m wide for two-way traffic and 4 m wide for one way traffic provided with gradient 1:10 for cars and 1:15 for heavy vehicles. At curved portions of the ramp or for circular ramps the slope should not be more than 1:12.
(b) Ramps may also be provided in setback area which can be sloped considering unhindered movement of fire engine and in no case the gradient shall be less than 1:10.
(c) All structural safety and design aspects as per latest BIS Code and NBC, 2005 shall be complied along with consideration of weight of fire engine and in no case the gradient shall be less than 1;10
(d) The minimum width of ramps in hospitals shall be 2.4 m for stretcher and not for vehicular movement.
(e) In this case Handrails shall be provided on both sides of the ramp.
(f) Ramps shall lead directly to outside open space at ground level or courtyards or safe place.
8. Corridors
(a) Exit corridors and passageways shall be of width not less than the aggregate required width of exit doorways leading from them in the direction of travel to the exterior.
(b) The minimum width of a corridor in a residential building shall be 1.0.m for single loaded and 1.8 m for double loaded and in all other buildings shall be 1.5 m.
(c) Where stairways discharge through corridors and passageways, the height of corridors and passageways shall be not less than 2.4
(d) All means of exit including staircases lifts lobbies and corridors shall be ventilated.
9. Glass facades/service ducts/Shafts/Refuge area/vents
(a) An opening to the glass facade of min width 1.5 m and height 1.5 m shall be provided at every floor at a level of 1.2 m from the flooring facing compulsory open space as well as on road side.
(b) Mechanism of opening. The openable glass panel shall be either left or right shall have manual opening mechanism from inside as well as outside. Such openable panels shall be marked conspicuously so as to easily identify the openable panel from outside.
(c) Fire seal to be provided at every floor level between the external glazing and building structure.
(d) The glazing used for the facade shall be of toughened (tempered) safety glass as per I.S.2553
(e) To avoid Fire propagation vertically from one floor to another floor, a continuous glass must be separated internally by a smoker fire seal which is of non-combustible material having a fire resistance rating of not less than 2 hours.
(f) Service ducts and shafts shall be enclosed by walls and doors with fire resistance rating. All such ducts and shafts shall be properly sealed and stopped fire ingress at all floor levels.
(g) A vent opening at the top of the service shall be provided having an area between one fourth and one half of the area of the shaft.
(h) The openable vent of minimum 2.5% of the floor area shall be provided. The open able vent can be pop out type or bottom hinged provided with fusible link opening mechanism and shall also be integrated with automatic smoke detection system.
-
Alternate vertical glass panels of the facade shall be open able type with the mechanism mentioned above in order to ventilate the smoke.
-
Refuge areas covered with the glass facade shall have all the panels fully open able (either left or right hinged (both from inside as well as outside).
Glass quality practice of use of glass in buildings shall have to be in conformity with the BIS Codes.