43.5.5 Ramps
43.5.5.1 Minimum gradient for the ramps going down to the basement only for parking purposes of maximum of 2.4m. depth should be 1:7 and for depth more than 2.4m. it should be 1:10
43.5.5.2 For all slopes the ramp shall be surfaced with approved non slipping materials.
43.5.5.3 Parking may be provided along the run of Ramp if the slope is not steeper than 1:20 and the Ramp will be treated as driveway.
43.5.5.4 Ramps may be permitted in the rear setback for the for the buildings whose width area in rear side is more or equal to 30m. after leaving requisite setback and the length of the ramp should not exceed more than 50% of such width and also an open an open space of 1.5m. should be left for drainage etc. between the ramp & boundary wall provided the side setback is not less than 4.5m.
43.5.5.5 Ramps may also be permitted in the front setback after leaving 4.5m. from the front boundary. (excluding road widening strip if applicable)
43.5.5.6 Ramps may also be permitted in the side back after leaving 4.5m. from the boundary.
43.5.5.7 Ramps for Hospital: In the case of Hospitals, the slope of ramp shall not be greater than 1:20.
44. Interior open space
44.1 At least one side of all the rooms intended for human habitation, if such room does not abut on the front or the rear or the side setbacks, shall abut on an interior open space whose minimum dimension shall be 3 meters X 3 meters in cases of buildings up to a height of 12 meters. In cases where the height of the building is more than 12 meters, the width of the interior open space shall be increased at the rate of one meter for every additional 3 (three) meters height. This provision shall be applicable to all categories of buildings, like residential, group housing, commercial, institutional, administrative, assembly etc.
assemely etc.
simmo. (5cm)
44.2 For ventilating the spaces for water closets and bathrooms ventilation shafts shall be provided with size as provided under clause - 8.2.5(b), Group 1, Part-3 of National Building Code of India as bye laws for ventilation shaft.
45 Height exemption of a building
Any exemption to height shall not be taken in account in case of AAI approval. The following appurtenant structures shall not be included in the height of the building.
45.1 Roof tanks and their supports (with support height not exceeding 3 m.)
45.2 Ventilating, air conditioning, lift rooms and similar service equipment.
45.3 Stair cover (Mumty) or architectural features not exceeding 3.0m. in height.
46. Exemption in Open space
46.1 Every open space provided either in the interior or exterior in respect of any building shall be kept free from any erection thereon and shall be open to the sky and no cornice, roof, or weather shade of more than 0.75 m. in width shall overhang or project over such open space.
46.2 A portico of up to 2.5 m, width and 4.6 m. length with a minimum height of 2.1 m. from the plinth level may be permitted within the side setback and leaving minimum 4.5m. from side boundary for buildings 15.0 m. and above in height. A garage is permissible at the rear end of side open space provided no openings are located on the side and rear boundary. Access to the top of the portico/garage should not affect the privacy of the neighboring plot.
46.3 The portico provided as above should not rest on the boundary wall and should be open to provide through access to the rear. In case the Portico is not a cantilevered one and supported by pillars, the area shall be included in the FAR.
46.4 No projected balcony shall be allowed, on setback less than 2.0m. Projected balcony shall be allowed with a width of 0.9 meters where the setback is between 2.0 meters to 2.5 meters. For setback more than 2.5 meters projected balcony shall be allowed with a width of 1.2 meters. Projected balcony shall only be allowed on the second floor and above floors. It may be allowed on first floor subject to condition that it shall not obstruct the clear vehicular and pedestrian movement around the building including movement of fire tender. 50% of the area on the projected balcony shall be taken into account for calculation of floor area. No balcony should be provided with fixed grill as it works as fire refuse areas.

Fig. 31.
X
47. Mezzanine
47.1 Mezzanine floor may be permitted above any floor in all types of buildings up to an extent of one-third of the actual covered area of that floor. All Mezzanine floors shall be counted toward FAR calculation.
The mezzanine floor shall have a minimum clear height of 2.10 m The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5 Sq meter. The aggregate area of such mezzanine floor in a building shall in no case exceed one-third the plinth area of the building.
48. Basement/Cellar
48.1 Basements/cellars shall not be permitted in low lying area and without adequate drainage facilities to ensure drainage from the basement. Basement shall not be allowed in flood prone areas.
48.2 Construction of basements/cellars may be allowed by the Authority in accordance with the provisions contained in the development plan applicable to the concerned area.
48.3 The basements/cellars shall only be put to the following uses:
48.3.1 Storage of household or other non-combustible material
48.3.2 Strong room, bank cellars library;
48.3.3 Installation of air-conditioning equipments and other machines used for service and utilities of building;
48.3.4 Parking.
48.4 Individual residential and small commercial buildings, plot size up to 750sqm. may have one basement. However maximum two floor basements/cellars may be permitted to be constructed for plot size above 750sqm. leaving the prescribed set back/open space applicable to the building. Further, in case of apartment/group housing/commercial/buildings and basements may be allowed to be constructed under the entire plot area leaving minimum of 3m. space from the boundary in front, sides and rear of the premises subject to the following;
48.4.1 In all such cases the owners have to indemnify the Authority against any damage caused by her/him/them to the adjacent property (Form-XIII (A)).
48.4.2 The portion of the basement projecting out of the building line in the setback area shall flush with the ground or of a plinth not exceeding 0.9 m height, approachable with a ramp of 1:10 gradient from the road level and the roof of such the basement in the open spaces areas, if intended to be used as
Lear 37.
vehicular passage, should be designed to be able to take the load of fire engines/vehicles of 45 tones
The basements shall be used exclusively for parking/services/storage or as permitted in 41.9 and 48.3
48.6 The basement shall fulfill the following requirements:
48.6.1 Every basement shall be in every part at least 2.4m. in height from the floor to the soffit of the roof slab or ceiling; and minimum of 2.1m below the soffit of beams.
48.6.2 Adequate ventilation shall be provided for the basement. The standard of ventilation shall be the same as required by the particular occupancy according to bye laws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans (one exhaust fan for 50sqm. of basement area), air conditioning system etc;
48.6.3 The minimum height of the ceiling of upper basement shall be 0.90m. and the maximum, 1.5 m. above the average surrounding ground level;
48.6.4 Adequate arrangement shall be made, so that surface drainage does not enter the basement;
48.6.5 The walls and floors of the basement shall be water-tight and be so designed that the effect of the surrounding soil and moisture, if any, are taken in to account in design and adequate damp proofing treatment is given;