43.3.1 The unit of exit width used to measure capacity of any exit shall be 50cm. A clear width of 25cm. shall be counted as an additional half unit. Clear width less than 25cm. shall not be counted for exit width.
43.3.2 The occupancies per unit exit which shall be as given in Table-20.
a4 = (1)/(2)a3 + + an
| Sl. | Type of Occupancy | Number of occupants per unit exit | |
| Stair Case | Door | ||
| (1) | (2) | (3) | (4) |
| 1 | Residential | 25 | 75 |
| 2 | Educational | 25 | 75 |
| 3 | Institutional | 25 | 75 |
| 4 | Assembly | 60 | 90 |
| 5 | Business | 50 | 75 |
| 6 | Mercantile | 50 | 75 |
| 7 | Industrial | 50 | 75 |
| 8 | Storage | 50 | 75 |
| 9 | Hazardous | 25 | 10 |
Explanation:
(A) Lifts and escalators shall not be considered as an exit.
(B) Travel distance means the distance from any point in the floor area to any exit measured along the path or egress except that when the floor areas are sub-divided into rooms, used singly or of rooms and served by suite corridors and passage, the travel distance may be measured from the corridor entrance of such rooms or suites to the nearest staircase or verandah having access to the street.
(C) For the dormitory portions of homes for the aged, orphanages, mental hospitals, etc. these multipliers will be doubled.
(D) The plinth or covered area shall include, in addition to the main assembly rooms or space, any occupied connecting room or space in the same storey or in the storey above or below where entrance is common to such rooms and space and they are available for use by the occupants of the assembly place.
(E) No deductions shall be made in the gross area of the corridors, closets or other sub-divisions; all space serving the particular assembly occupancy shall be reckoned.