PER CAPITA WATER REQUIREMENT FOR VARIOUS OCCUPANCIES / USES
| Sl.No. | Type of Occupancy | Consumption per head per day (in litres) |
| (1). | Residential | |
| a) In living units | 135 | |
| b) Hotels with lodging accommodation (per bed) | 180 | |
| (2) | Educational | |
| a) Day schools | 45 | |
| b) Boarding schools | 135 | |
| (3) | Institutional (Medical Hospitals) | |
| a) No. of beds not exceeding 100 | 340 | |
| b) No. of beds exceeding 100 | 450 | |
| c) Medical quarters and hostels | 135 | |
| (4) | Assembly – Cinema theatres, auditoria etc. (per seat accommodation) | 15 |
| (5) | Government or semi public business | 45 |
| (6) | Mercantile (Commercial) | |
| a) Restaurants (per seat) | 70 | |
| b) Other business building | 45 | |
| (7) | Industrial | |
| a) Factories where bath-rooms are to be provided | 45 | |
| b) Factories where bath-rooms are not to be provided | 30 | |
| (8) | Storage (including warehouses) | 30 |
| (9) | Hazardous | 30 |
| (10) | Intermediate Stations (excluding mail and express stops) | 45(25)* |
| (11) | Junction Station | 70(45)* |
| (12) | Terminal Stations | 45 |
| (13) | International and Domestic Airports | 70 |
* The values in parenthesis are for such stations, where bathing facilities are not provided.
Note: The number of persons for Sl.No.10 to 13 shall be determined by the average number of passenger handled by the station daily with due consideration given to the staff and workers likely to use the facilities.
[ PART-I]