Chapter IIIHealth and Sanitation General Building Requirements
Means of access.— (a) Every person who erects a detached building shall provide as means of access to such building a clear way not less than 3.5 m. in width for buildings up to 3 storeys and 5 m. in width for buildings beyond three storeys from a street to the entrance door of such buildings; such pathways shall be maintained free from any obstruction and shall not at any time cause or permit any portion of any building below a height of 2.3 m. to overhang or to project over or into such passage.
(b) He shall indicate upon the site plan, required to be furnished by him under Bye-law 5, of the whole area of such means of access by a distinguishing colour and description.
(c) He shall not at any time erect or cause or permit to be erected or re-erected, any building which in any way encroaches upon or diminishes the area so set apart for this purpose.
(d) The space so set apart shall be separately distinguished from any house-gully, lane or open space required to be provided under any other bye-law made under these rules.
(e) Every such means of access shall be paved, drained and lighted. Provision of man -hole covers or any other fittings laid in such means of access shall be flushed with the finished surface level so as not to obstruct safe travel over the same.
(f) A person who undertakes construction works on a building shall not reduce the access to any building previously existing below the minimum width as required under clause (a).
(g) No building shall be erected so as to deprive any other building of the means of access as provided in this bye-law.
(h) The means of access under these bye-laws shall not be deemed to be suitable and sufficient until it has been approved by the Planning Authority who shall have power to prescribe the width of clear way which the Planning Authority shall communicate its decision after consulting the Town and Country Planning Department.
Safeguard against reduction of open space- No construction work on a building shall be allowed if such work operates to reduce an open space of any other adjoining building belonging to the same owner to an extent less than what is prescribed by any of the bye-laws in force at the time of the proposed work or to reduce further such open space if it is already less than that prescribed.
Projections.— (1) No projections of any sort whatsoever except sunshades extending more than 23 cm. below the height of 4.3 m. shall project over the road or over any drain or over any portion outside the boundaries of the site provided that the projection arising out of the vertical part of the rain water spouts projecting at the road level or the water pipe may be permitted in accordance with the drainage plan.
(2) Projection of sunshades over windows or ventilators when permitted by the Planning Authority shall fulfill the following conditions, namely: -
(a) No sunshade shall be permitted over the road or over any drain or over any portion outside the boundaries of the site below a height of 2.8 m. from the road level.
(b) Sunshades provided above a height of 2.8m. from the ground level shall be permitted to project up to a maximum width of 60 cm. if the road over which it projects exceeds 9.0m. in width; and
(c) No sunshade shall be permitted to project on roads less than 9.0 m. in width or on roads having no footpaths/platforms.
(3) Every setback provided either in the side or rear shall be kept free from any erection thereon and shall be open to sky and no cornice, roof or sunshade more than 0.75 m. shall overhang or project over the said setback so as to reduce the width to less than minimum required. In case of front setback a clear distance of 1.0 m./1.5 m. open to sky shall be left from the boundary line of the plot towards the front of the building depending on the front setback insisted for the buildings and no projection whatsoever should extend beyond the above limit.
[ PART-I
(4) Balconies in the existing developed areas may be permitted to project over the road or over any drain or over any portion outside the boundaries of the site to a maximum of 1.0 m. if the road over which they project exceeds 9.0 m. in width and no balcony shall be permitted on roads less 9.0 m. in width or on roads having no footpaths.
(5) (i) The distance between the existing electric lines or telegraph lines and any portion of the structure should be governed by the current rules of the Electricity Department or Telegraphs Department respectively, and its amendments from time to time and shall not be less than the minimum distances mentioned below:
Sl. No.
Description
Vertically (in m.)
Horizontally (in m.)
(a)
Low and Medium voltage lines and service lines
2.5
1.2
(b)
High voltage lines up to and including 11 K.V.A.
3.7
1.2
(c)
High voltage lines above 11 K.V.A. and up to and including 33 K.V.A.
3.7
2.0
(d)
Extra high voltage line beyond 33 K.V.A.
3.7 (plus 0.3 m. for every additional 33 K.V.A. and part thereof)
2.0 (plus 0.3 m. for every additional 33 K.V.A. and part thereof)
(ii) In case of Electrical lines maintained by the Power Grid Corporation, Government of India, the clearances stipulated by the said corporation shall be followed.
Height Limitations.— (1) Height Limitation: The height and number of storeys shall be related to F.A.R. and the provisions of open space within the plot.—
The maximum height shall be limited according to the width of the street as follows:
(a) The maximum height of building shall not exceed 1.5 times the width of road abutting plus the height may be exceeded to the extent of 1m. for every 30 cm. by which the building is setback from the street.
(b) If a building abuts on two or more streets of different widths, the building shall be deemed to face upon the street that has the greater width and the height of the building shall be regulated by the width of that street and may be continued to this height to a depth of 24.0 m. along the narrower street subject to conformity of provisions of open space within the plot.
(c) For buildings in vicinity of aerodromes, the maximum height of such buildings shall be decided in consultation with the Civil Aviation Authorities and provisions of clause (3) below shall apply.
(2) Height Exceptions.—
Roof Structures.— The following appurtenant structures shall not be included in the height of the building unless the aggregate area of such structures, including pent-houses, exceeds one-third of the area of the roof of building upon which they are erected:
(a) Roof tanks and their supports (with support height not exceeding 1.0 m.);
(b) Ventilating, air-conditioning, lift rooms and similar service equipment;
(c) Stair cover (MUMTY) not exceeding 3.0m. in height; and
(d) Chimneys, parapet walls and architectural features not exceeding 1.2m. in height.
(3) Restrictions in the Vicinity of Aerodromes.— For buildings in the vicinity of aerodromes, the maximum height of such building shall be decided in consultation with the Civil Aviation Authorities. This shall be regulated by the rules for giving no objection certificate for construction of buildings in the vicinity of aerodromes of Directorate General of Civil Aviation. However, the latest rules of Directorate General of Civil Aviation shall be followed in all cases of buildings coming up in the vicinity of an aerodrome.
PART-I
223
(a) For the purpose of restrictions in the vicinity of Aerodromes, new buildings, structures which rise to 30.0 m. or more in height and are to be located within 20 km. of the aerodrome reference point, shall be constructed only if no objection certificate has been obtained from the Directorate General of Civil Aviation.
(b) In the case of building to be erected in the vicinity of Defence aerodromes, the maximum height of such building shall be decided by the Defence Authority.
(c) This will apply specially to new constructions, overhead high voltage/medium voltage lines, telephones/telegraph lines, factories, chimneys, wire/T.V. antennas.
(d) No new chimneys or smoke producing factories shall be constructed within a radius of 8 km. from the aerodrome reference point (A.R.P.).
(e) Overhead high voltage/medium voltage lines or telephone/telegraph lines shall not be permitted in the approach/take-off climb areas within 3000.0 m. of the inner edge of these areas.
(f) A 3.0 m. margin shall be allowed in new constructions for wireless/T.V. antennas, cooling towers and mumties.
30. Minimum ceiling height of rooms:
General
(i) Plinth.—The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm. from the surrounding ground level.
(ii) Interior Courtyards and Covered Parking.— Every interior courtyard shall be raised at least 150 mm. above the determining ground level and shall be satisfactorily drained.
(iii) Habitable rooms: Every habitable room in any building shall be in every part at least 2.80 m. in height from the surface of the floor to the underside of the roof slab or ceiling, provided that in the case of slope roof, the minimum height shall not be less than 2.2 m. This is applicable to residential, business and mercantile buildings. For office, educational and industrial buildings, the following minimum requirements shall apply:
(a) Office, Educational buildings.... Ceiling height 3.6 m. for all regions.
(b) Industrial buildings.... Ceiling height 3.6 m. except when air-conditioned, where it shall be not be less than 3.0 m. (Factory Act, 1948 and Rules therein shall govern such heights, where applicable).
(iv) Kitchen: The ceiling height of the kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.8 m. except for the portion to accommodate floor trap of the upper floor.
(v) Ledge or Tand/Loft.—The minimum head room of ledge or tand / loft shall be 2.2 m. The maximum height of loft shall be 1.5 m.
(vi) Mezzanine floor: It shall have minimum ceiling height of 2.2m.
(vii) Store room.—The height of storeroom shall not be less than 2.2 m.
(viii) Garage.—The height of the garage shall not be less than 2.4 m.
(ix) Basement.—Every basement shall be in every part at least 2.4 m. in height from the floor to the underside of the roof slab or ceiling. The minimum height of ceiling of any basement shall be 0.9 m. and the maximum 1.2 m. above the average surrounding ground level.
(x) Stilt floor.—The minimum height of the stilt floor shall not be less than 2.4 m.
(xi) Staircase headroom.— The minimum headroom in a passage under the landing of a staircase shall be 2.2 m. The minimum clear headroom in any staircase shall be 2.2 m.
(xii) Low income and EWS housing: The minimum height of rooms / spaces shall be as follows: - Note: (no basement shall be allowed)
[ PART-I
(a) Habitable room...2.60 m.
(b) Kitchen...2.6 m.
(c) Bath/W.C...2.1 m.
(d) Corridor ...2.1 m.
(e) Staircase head room... 2.10 m.
(f) In the case of sloped roof, the average height of the roof for habitable rooms shall be 2.60 m. and the minimum height at eaves shall be 2.00 m.
(xiii) Parapet: Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0m. and not more than 1.2m. in height from the finished floor level.
(xiv) Boundary Wall/Compound Wall: The maximum height of the compound wall shall be 1.5 m. above the centerline of the front street. Compound wall up to 2.4 m. height may be permitted if the top 0.9 m. is of open type.
Minimum size of habitable rooms.—No habitable room shall have a floor area of less than 9.3 sq.m. except in the case of hostels attached to recognised educational institutions. The minimum size of habitable room for the residence of a single person may be 8.0 sq.m. The minimum width of a habitable room shall be 2.5 m. Where there are two rooms, one of these shall not be less than 9.3 sq.m. and the other not less than 7.5 sq.m. with a minimum width of 2.1 m.
For Low Income Housing & E.W.S. the minimum size of habitable room shall be as follows :
(i) In the case of one roomed house, the size of multi-purpose room, including space for cooking, shall be not less than 12.5 sq.m. with a minimum width of 2.50 m.
(ii) In the case of two-roomed house, the size of 1st room shall not be less than 9.0 sq.m. with minimum width of 2.5 m. and 2nd shall not be not less than 6.50 sq.m. with a minimum width of 2.10 m., provided the total area of both the rooms is not less than 15.5 sq.m. In the case of incremental housing the bigger room shall always be the first room.
Minimum size of Bathrooms and water closets.— (1) Every bathroom or water closet shall:-
(a) be so situated that at least one of its walls open to external air, and in case of bathroom it shall have a window or a ventilator open to external air of a superficial area of not less than 10% of the floor area;
(b) (i) have a floor area in case of bathrooms inclusive of water closet of not less than 2.8 sq.m. for which the smallest side shall not be less than 1.20 m.;
(ii) in case of a bathroom exclusive of a water closet, the floor area shall not be less than 1.80 sq.m. and the smallest side not less than 1.2 m.
(c) have a height of not less than 2.5m;
(d) not be directly over or under any other room other than another bathroom or water closet, washing place, terrace unless it has a water tight floor;
(e) have the platform or seat either plastered with cement or is made of some water tight non-absorbent material;
(f) be enclosed by walls or partitions of brick or stone. The surface of every such wall or partition shall be finished with a smooth impervious surface such as cement plaster 12 mm. thick of glazed tiles or polished marble or any other suitable material to a height of 1.5 m. above the floor of such room;
(g) have an impermeable floor made of smooth hard material having a suitable fall to a soil pipe with an adequate trap connection and have a floor level of such a height so as to ensure suitable grade towards the sewage drain.
PART-I
225
(2) No room containing a water closet shall be used for any purpose other than a lavatory and no such room shall open directly into any kitchen or cooking space. Every room containing a water closet shall have a door completely closing the entrance to such a room.
(3) A water closet alone shall have--
(a) a floor area of not less than 1.15 sq.m. of which the smallest side shall not be less than 1 m.;
(b) a window or a ventilator of superficial area of not less than 10% of the floor area;
(c) an impermeable floor made of smooth hard material having slope of 0.5 per cent. towards the back of latrine;
(d) an impermeable dado 1.0 m. high;
(e) roof height not less than 2.5m.
(4) (a) Every building meant for habitation shall be provided with water closet. The Planning Authority shall determine in each case whether the premises shall be served by a water closet connected to a sewer or a septic tank provided that if a sewer is within 30.0 m. of the site it shall be connected to the sewer, provided further that until the sewer begins to function, the water closet shall be connected to a septic tank provided for this purpose, subject to the condition that it shall be connected to the sewer as and when required by the Planning Authority.
(b) The Planning Authority may refuse to permit the construction of any latrine or urinal at a particular place if in its opinion such latrine or urinal would be a nuisance in the neighbourhood or would be objectionable to the occupants of neighbourhood building.
Note: For temporary structures including huts meant for habitation the Planning Authority shall determine in each case whether the provision of latrine is obligatory or not.
(5) Minimum size of bath and W.C. for low-income housing:
(i) The size of independent W.C. shall be 0.90 sq.m. with minimum width of 0.90m.
(ii) The size of combined bath and W.C. shall be 1.80 sq.m. with minimum width of 1.0 m.; and
(iii) The size of independent bath shall be 1.20 sq.m. with minimum width of 1.0m.
Minimum size of Kitchen.— (1) The area of a kitchen where separate dining area is provided, shall be not less than 5.0 sq.m. with a minimum width of 1.8 m. Where there is a separate store, the area of the kitchen may be reduced to 4.5 sq.m. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 sq.m. with a minimum width of 2.1 m.
(2) Every room to be used as kitchen shall have -
(a) a height of not less than 2.80m;
(b) a window or a ventilator of superficial area of not less than 10% of the floor area;
(c) an impermeable floor and an impermeable dado or any other water proof material to a minimum of one metre high.
(d) The minimum size of kitchen for low-income housing - The size of cooking alcove serving as cooking space shall not be less than 2.40 sq.m. with a minimum width of 1.20 m. The size of individual kitchen provided in a two-roomed house shall not be less than 3.30 sq.m. with a minimum width of 1.50 m.
Minimum size of Lofts.—A loft in a habitable room shall not cover more than 25% of the area of floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
Minimum size of Mezzanine floor.— Size - The minimum size of mezzanine floor if it is used as a living portion shall not be less than 9.3 sq.m., the aggregate area of which shall in no case exceed one-third of the plinth area of the building. A mezzanine floor may be permitted over a room or a compartment provided that:
(1) it conforms to the standards of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.3 sq.m. or more;
[ PART-I
(2) it is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
(3) such mezzanine floor is not subdivided into smaller compartments;
(4) such mezzanine floor or any part of it shall not be used as a kitchen; and
(5) in no case a mezzanine floor shall be closed so as to make it liable to be converted into unventilated compartments.
Basement.— (1) The basement shall not be used for residential purposes.
(2) The basement to be constructed within the building envelop and subject to maximum coverage on floor 1 (entrance floor) may be put to only the following uses:
(a) Storage of household or other goods of ordinary non-combustible materials;
(b) Strong rooms, bank cellars etc;
(c) Air-conditioning equipment and other machineries equipments used for services and utilities of the building and
(d) Parking spaces.
(3) The basement shall have the following requirements:
(a) No basement shall be permitted on an individual plot unless it has a clear set back of 2m. from the boundary line of the plot or the required setbacks whichever is more.
(b) Every basement shall be in every part at least 2.4 m. in height from the floor to the underside of the roof slab or ceiling;
(c) Adequate ventilation shall be provided for the basement. The ventilation requirements shall be the same as required by the particular occupancy according to bye-laws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems etc.
(d) The minimum height of the ceiling of any basement shall be 0.9 m. and the maximum, 1.2 m. above the average surrounding ground level.
(e) Adequate arrangements shall be made such that surface drainage does not enter the basement.
(f) The walls and floors of the basement shall be water-tight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
(g) The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors. Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of clause (d) above.
The slope of a ramp shall not exceed 1 in 10. In certain cases steeper slopes may be permitted but in no case greater than 1 in 8. For all slopes exceeding 1 in 10 and wherever the use is such as to involve danger of slipping, the ramp shall be surfaced with approved non-slipping material.
(h) Basement in an individual plot touching the adjacent property shall not be allowed and in all cases the owners shall have to indemnify the Planning Authority against any damage caused by her/him/them to the adjacent property as per the Annexure-VI.
Minimum size of Other requirements.—(1) Store room : The size of store room when provided in a residential building shall not be less than 3.00 sq.m.
(2) Garage: The size of garage shall be as below:
(i) Private Garage : 3.0 m. x 6.0 m. minimum and
(ii) Public Garage : Based on the number of vehicles parked.
PART-I]
227
(3) Petty shops: The minimum width of a petty shop shall be 2.50 m. and the floor area shall not be less than 7.5 sq.m.
Other building requirements.—(1) Minimum width of staircase shall be as follows:
(a) Residential buildings (dwellings) .. 1.0 m.
Note: For row housing with two storeys, the minimum width shall be . . 0.75 m.
(b) Residential hotel building . . 1.5 m.
(c) Assembly buildings like auditoria, theaters and cinemas. . . 2.0 m.
(d) Educational buildings .. 1.5 m.
(e) Institutional buildings . . 2.0 m.
(f) All other buildings . . 1.5 m.
(2) The minimum width of corridors shall be as follows:
Sl.No.
Building use or type
Minimum width of corridor
01
Residential buildings
1.0 m.
02
Assembly buildings such as Auditoriums, Kalyanamandapam, Cinema theatre, Religious Buildings, Temples, Mosques or Churches and other buildings of Public Assembly of Conference.
2.0 m.
03
Institutional buildings such as(a) Government Offices(b) Hospitals and Nursing Homes(c) Educational Buildings such as schools, Colleges, Research Institutions,(d) Commercial buildings such as private offices, Nursing Homes, Lodges, etc.,(e) All other buildings
2.0 m.2.4 m.2.0 m.2.0 m.1.5 m.
(3) The minimum width of balcony in any residential building shall not be less than 1.0 m. and 1.5 m. for other than residential uses.
(4) The following criteria shall be adopted for low income housing in urban area for internal individual staircase:
(a) Minimum width of stair
(i) Two storeyed-straight . . 0.60 m.
(ii) Two storeyed - winding . . 0.75 m.
(iii) Three or more storeyed-straight .. 0.75 m.
(iv) Three or more storeyed-winding .. 0.90 m.
(b) Riser . . 0.20 m. (maximum)
(c) Tread
(i) Two storeyed .. 0.23 m. (minimum)
[ PART-I
(5) Details of staircase, ramps, exit, doors, lift and fire escapes :
All stairs shall comply with the following requirements:
(a) Head room: All stairs ways shall have at least 2.20 m. of clear head room, measured perpendicularly from the nosing.
(b) Tread and risers: Treads and risers shall be so proportioned that the sum of two risers and a tread width is not be less than 53 cm. and not more than 63 cm. No riser shall be more than 20 cm. and no tread width less than 23 cm. There shall be no variation in the widths of treads or the heights of risers in any one flight of stairs. No stairway should ordinarily be permitted cutting across any window. The surface material of stairs treads and landings shall be as such as not to involve undue danger of slipping. Number of risers shall be limited to 12 per flight.
(c) Landing: No stairway shall have a height of more than 1.75 m. between landings nor less than two risers between consecutive landings, the landing shall have a dimension, not less than the width of stairs, measured in the direction of the run.
(d) Rails: Stair shall have walls or well-secured balustrades or guards on both sides. Handrails shall be placed not less than 75 cm. and not more than 1.0m. above the nosing of the treads.
(e) Space under stairs: The space beneath any stairway built in whole or in part of combustible materials except handrails shall be left entirely open. The minimum head room in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
(f) Ventilation for staircases: Every staircase shall be lighted and ventilated to the satisfaction of the Planning Authority from any open space. There shall be provided, a window or windows or ventilator or ventilators for an aggregate area of at least 1.5 sq.m. in each floor in such of the wall of the staircase room as abuts 1.75 m. open space to light and ventilators such staircase. The above provision can be disposed with when an open well for light and ventilation within the space enclosed by the stairway and its landing is proposed to be provided the least horizontal dimensions of which are equal to twice the width of the staircase provided that there shall be in the roof directly over such staircase well, a ventilating skylight provided with fixed or movable louvers. The glazed roof of the skylight shall not be less than 3.75 sq.m. in area. No lift or any other fixture shall be erected in such staircase well meant for ventilation.
(g) Passage giving access to staircase: Every passage in a building in the ground floor shall in no part be less than the width of the staircase of such building to which it gives access. Provided that if only one such passage gives access to more than one staircase, its minimum width shall be equal to the width of such staircase plus one half of the total width of the remaining staircases.
(h) Ramps: Ramps if provided as a substitute for stairways shall be laid with a slope not exceeding 1 in 10 and such ramp shall comply with all requirements of a stairway and shall be surfaced with approved non-slippery materials.
(i) Corridor, verandahs and passageways: The clear width of any corridor, verandah or passageway in any building shall be not less than the details mentioned in section 38(2) above.
(j) Fire escape staircase:
(1) Fire escape staircase shall be provided for every building of, -
(i) Residential occupancies exceeding three storeys above ground level;
(ii) Occupancies other than residential exceeding two storeys above ground level;
PART-I
229
(2) The width of fire escape staircase shall be not less than 75 cm. The width of fire escape stair tread shall be not less than 15 cm. The height of the fire escape stair riser shall not exceed 19 cm. and the number of risers shall not exceed 16 per flight of stairs.
(3) The height of handrail of a fire escape staircase shall not be less than 100cm.
(4) Fire escape stairs shall be constructed only in the exterior of the building and shall be connected directly to the ground.
(5) Fire escape stairs shall have a straight flight.
(6) Entrance to fire escape staircase shall be separated and removed from internal staircase.
(k) Travel distance to emergency staircase.—(i) Every building meant for human occupancy shall be provided with emergency exit sufficient to permit safe escape of occupants in case of fire or whenever other emergency occurs.
(ii) Emergency exits shall be located in such a way that the travel distance on each floor shall not exceed 30 m. for every occupant.
(1) Fire Protection requirements.— All requirements in respect of fire protection shall be as in Part-IV, Fire Protection in National Building Code of India, 2005 and amendment No.3 under Fire Protection Annexure-II.
(m) Number of exits:
(i) For residential building/flat, one stairway shall be provided for every 12 dwelling units and part thereof.
(ii) All buildings used as educational, assembly, institutional, industrial, storage and hazardous occupancies, mixed occupancies, having area more than 500 sq.m. on each floor shall have a minimum of two staircases. They shall be enclosed type; at least one of them shall be on external walls of buildings shall open directly to the exterior, interior open space or to an open place of safety.
(n) Doorways:
(i) Every exit doorway shall open into an enclosed stairway or a horizontal exit or a corridor or passageway providing continuous and protected means of egress.
(ii) No exit doorway shall be less than 75 cm. in the case of residential and 1.2 m. in the case of all other occupancies.
(o) Arrangement of Exits:
(i) Exits shall be so located that the travel distance on the floor shall not exceed the distance given in the Table below:
(ii) The travel distance to an exit from the dead end of a corridor shall not exceed half the distance specified in the Table below except in assembly and institutional occupancies in which case it shall not exceed 6 m.
(iii) Whenever more than one exit is required for any room space or floor of a building, exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in separate directions from any point in the area served.
[ PART-I
(p) Travel distance for occupancy and Type of Construction
Sl.No.
Group of Occupancy
Maximum Travel Distance (m.)
(i)
Residential
30.00
(ii)
Educational
30.00
(iii)
Institutional
30.00
(iv)
Assembly
30.00
(v)
Business
30.00
(vi)
Mercantile
30.00
(vii)
Industrial
45.00
(viii)
Storage
30.00
(ix)
Hazardous
22.50
Note: (i) For fully sprinklered building, the travel distance may be increased by 50 per cent. of the values specified.
(ii) Ramps shall be protected with automatic sprinkler system and shall be counted as one of the means of escape.
(q) Spiral stair fire escape:
(i) The use of spiral staircase shall be limited to low occupant load and buildings up to 9 m. in height unless they are connected to platforms such as balconies and terraces to allow easy exit.
(ii) A spiral staircase shall be not less than 150 cm. in diameter and shall be designed to give adequate head room.
(r) Lift:
(1) Every building exceeding 3 storeys (excluding sunken floors) in the case of hospitals/medical occupancy and 4 storeys (excluding sunken floors) in the case of other occupancies have plinth area more than 2500 sq.m. shall be provided with one lift for every 2500 sq.m. or part thereof exceeding first 2500 sq.m., in addition to the required number of staircases.
(2) The planning, design and installation etc. of lifts and escalators shall be in accordance with Part-VIII, Building services, Section 5, installation of lift and Escalators in the National Building Code of India, 2005;
(3) Whenever more than one lift is required, at least one lift shall be a higher capacity lift that can carry a stretcher.
(s) Circulation area:
(a) The circulation area of any floor including staircase, shall not exceed—
(i) 2.0 sq.m./unit where 4 dwelling units are grouped around the staircase; and
(ii) 4.0 sq.m. / unit where 2 dwelling units are grouped.
(7) Energy Conservation Building:
Any building designed for energy efficiency under the budget building definition should be in accordance with the Energy Conservation Building Code, 2007 notified by the Central/State Government.
The code is applicable to buildings or building complexes that have a connected load of 100 K.W. or greater or a contract demand of 120 K.V.A. or greater. Generally buildings or building complexes having conditioned area of 1000 sq.m or more will fall under this category.
PART-I
231
39. Lighting and ventilation of rooms and open spaces area:
I. Lighting and Ventilation of rooms: (a). All habitable rooms shall have for the admission of light and air, one or more apertures, such as window, glazed door and fan lights, opening directly to the external air or into a open verandah not more than 2.40 m. in width. In case light and ventilation to habitable space area are through an internal courtyard, the minimum dimensions of such courtyard shall not be less than 3.0 m. x 3.0 m. for buildings up to 12.50 m. in height. For buildings with higher heights, the minimum dimensions of the internal courtyard shall be as given in clause 39 (2).
(b) where the lighting and ventilation requirements are not met through day lighting and natural ventilation, the same shall be ensured through artificial lighting and mechanical ventilation as given in Part-VIII Buildings Services Section-1 Lighting and Ventilation of National Building Code of India, 2005 published by the Bureau of Indian Standards. The latest version of the National Building Code of India shall be taken into account as the time of enforcement of the Building Bye-Law. Notwithstanding the above, the minimum aggregate area of openings of habitable rooms and kitchens excluding doors shall be not less than 1/10 of the floor area. No portion of a room shall be assumed to be lighted if it is more than 7.50 m. from the opening assumed for lighting that portion.
(c) For ventilating the spaces for water closets and bathrooms, if not opening on the front, side, rear and interior open spaces, shall open on the ventilation shaft, the size, of which shall not be less than the values given below:
Size of Ventilation Shaft:
Height of Building in m.
Size of ventilation shaft in sq m.
Minimum width of shaft in m.
Up to 10
1.2
0.9
12
2.8
1.2
18
4.0
1.5
24
5.4
1.8
30
8.0
2.4
Above 30
9.0
3.0
Note : (1) For buildings above 30.0 m., mechanical ventilation system shall be installed besides the provision of minimum ventilation shaft.
(2) For fully air-conditioned residential buildings for lodging purposes, the ventilation shaft need not be insisted upon, provided the air-conditioning system works in an uninterrupted manner, also provided there is an alternative source of power supply.
Open spaces area.— Every room that is intended for human habitation shall abut on an interior or exterior open space or on to a verandah open to such interior or exterior open space. The open spaces to be left around the building including setbacks, covered area, total built up area, limitations through F.A.R. shall be as per Master Plan/Zonal Plan requirements. The relevant provisions related to open spaces, areas and height limitations are given in Zoning Regulations.
Drainage and Sanitation:
Sites containing deposited refuse: No building shall be constructed on any site on any part of which there is deposited refuse, excreta or other offensive matter to which the Health Authority having jurisdiction objects until such refuse has been prepared or left in a manner suitable for building purposes to the satisfaction of the Planning Authority:
Provided that where it is intended to found the building on piles or on reinforced concrete pillars, the Planning Authority may approve the erection of such a building after the refuse has been appropriately treated by chemical or some other manner to the satisfaction of the Planning Authority to a depth of not less than 0.6 m. or by a layer of cement concrete of not less than 15 cm. thick.
Sites liable to floods: No building shall be erected on a site liable to flood or on a slope forming an angle of more than 45 degrees with the horizontal or soil unsuitable for percolation or in sandy beds, unless it is proved by the owner to the satisfaction of the Planning Authority that erection of such a building will not be dangerous or injurious to health or will not involve danger from flooding or erosion or cause undue expenditure of public funds in the provision of roads, sewers, sanitation, water supply or other public service.
Site containing pits, quarries, etc.: No building shall be erected on a site, which comprises or includes a pit, quarry or other excavation or any part thereof unless such site has been prepared or left in a manner and condition suitable for building purposes to the satisfaction of the Planning Authority.
Lowest storage on sites subject to flooding: In water logged or low lying areas subject to flooding and where a building has been specifically permitted under Bye-law 41 the Planning Authority may require the floor of the lowest storey of such building to be raised above the maximum flood level of the adjoining ground or to such other level as the Planning Authority may specify.
Damp sites: Wherever the dampness of a site or the nature of the soil renders such precautions necessary, the ground surface of the site between the walls of any building erected thereon shall be covered with a layer of sound cement concrete not less than 15 c.m. thick or with asphalt paving on a layer of closed packed broken stone hard cake not less than 15 cm. thick or be otherwise rendered damp proof to the satisfaction of the Planning Authority.
(a) Interior Open Space for Light and Ventilation.— The whole or part of one side of one or more rooms intended for human habitation and not abutting on either the front, rear or side open spaces shall abut on an interior open space whose minimum width in all directions shall be 3.0 m. in case of buildings not more than 12.50 m. in height and subject to the provision of increasing the same with increasing height @ of 0.3 m. per every metre height or part thereof beyond 12.50 m. However, in case of buildings already constructed with 3.0 m., the open space for new construction on upper floor, the open space on this basis should be ensured and would remain as mandatory open space.
Note: Where only a kitchen is abutting an interior open space, the minimum width as specified can be reduced by 0.55 m. correspondingly.
[ PART-I
(b) Exterior open spaces around the building:
(i) The setbacks of the respective building shall be as per Master Plan, detailed Layout Plan, general Development Plan.
(ii) For buildings identified in Building Bye-Laws 7 (ii) of chapter II, the provision of exterior open spaces around the buildings shall be as given in the following Table.
Sl.No
Height of the Building Up to (m.)
Exterior open spaces to be left out on all sides in m.(front rear and sides in each plot)
1
10
Setbacks as prescribed in respective zones
2
15
3
18
4
21
5
24
6
27
7
30
(iii) In case of multi-storeyed buildings the exterior open space around a building shall be of hard surface capable of taking load of fire engine weighing up to 45 tonnes.
Joint Open Air Space: Every interior or exterior or air space, unless the latter is a street, shall be maintained for the benefit of such building exclusively and shall be entirely within the owner's own premises.
(a) If such interior or exterior open air space is intended to be used for the benefit of more than one building belonging to the same owner; then the width of such open air space shall be the one specified for the tallest building as specified in building bye-law (1) and (2) of 39 Chapter (III) abutting on such open air space.
Structures in setback spaces.—(1) Unless or otherwise specifically provided for elsewhere in these regulations, no structure shall be constructed within the minimum prescribed setback spaces except the following:
In cases of non-multistoreyed buildings (including ordinary buildings)
Unsupported sunshade, wardrobes, balconies and other projections from the main walls, so long as such structures do not fall within the minimum required setback spaces, more than what is prescribed below:
(i)
Sun shades
0.60 m.
(ii)
Non-continuous wardrobes or built-in cupboards in the upper floors above ground floor
0.60 m.
(iii)
Open non-continuous balconies (above ground floor)
1.20 m.
(iv)
Open service verandah to kitchen (above ground floor)
1.20 m.
(v)
Architectural projections above ground floor
1.00 m.
(vi)
Staircase open landing projections (not affecting driveway)
1.00 m.
(vii)
Cantilevered portico so long as it does not fall within 1.5 m. from the street alignment or boundary of the site which ever is closer
For the items (iii) to (vi) above, there shall be a minimum clearance of 0.5 m. for an ordinary building and 1.50 m. for a special building / group development and for any other non-multistoreyed building, from the property boundary (or street alignment, whichever is closer) Provided further that if non-continuous projecting structures stated above in the setbacks exceed 50% of the site / length of the building, then they shall be taken as forming part of the main building, and shall not be allowed in the minimum prescribed setback spaces.
Motor room of area not exceeding 2 sq.m. each and height not exceeding 1.8 m., without affecting parking and driveway requirements.
In case of ordinary building, open single flight or spiral staircase or open double flight staircase so long as such structure does not fall within 0.50 m. from the side boundary or 1.0 m. from the rear or front boundary of the site or street alignment.
PART-I
233
A compound wall of height not exceeding 2.0 m.
Watchman booth not exceeding 2.5 m. x 2.5 m. in size at each gate and height not exceeding 3.0 m.
Gate pillars without or with arches with a min. headroom clearance of 5.50m. available at least to a width of 3.5m.
Meter Rooms for meter boxes / electrical panels along the boundary wall or external walls of the building with the projections not exceeding 0.60 m. from the abutting walls and the open Transformer without affecting parking and drive way, subject to the safety measures stipulated by Electricity Department.
Explanation:—Any wardrobe or staircase projection stated above is countable for coverage and F.A.R. computation.
In order to minimise traffic conflicts on to the abutting roads, the number of vehicular entry / exits to site shall be kept minimum and it shall not exceed 2 numbers (i.e. one entry / one exit); provided that an additional gate for every 50.0m. frontage may be allowed in large sites where its frontage exceeds 50.0m.
Damp proofing of basements: When any habitable room is located in a basement, the floor and exterior walls of such basement shall be constructed or treated as to render the basement water tight and damp proof. In addition, when buildings with basements enclosing habitable rooms are located on a site where ground water conditions exist or are likely to occur such as might produce any hydrostatic head against the basement walls or floors, the floors shall be constructed on porous brick fills and all walls shall be backfilled with porous material within 30 cm. of ground level and above that with relatively impermeable soil, and an adequate drainage system shall be laid which will collect the water from the bottom of all porous backfills and conduct it away from the building.
Drainage of sub-soil: Whenever in the opinion of the Planning Authority the site of a building so requires, the sub-soil shall be drained effectively by means of sub-soil drains or by other means to the satisfaction of such Authority.
[ PART-I
Surface water drains:
(i) Any land, passage or other area within the cartilage of a building shall, if the Planning Authority so requires, be effectively drained by surface water drains or other means to its satisfaction.
(ii) The written approval of the Public Works Department shall be obtained for connecting any subsoil or surface water drain to a sewer.
Drainage below ground floor level: In every building, any basement cellar or other space below the ground floor shall be directly drained or drained by a sump provided with a suitable pump.
Drainage of roofs.—(a) The roof of a building shall be so constructed or framed as to permit effectual drainage of the rain water therefrom by means of a sufficient number of rain water pipes of adequate size so arranged, joined and fixed as to ensure that the rain water is carried away from the building without causing dampness in any part of the walls or foundations of the building or those of an adjacent building;
(b) The Planning Authority may require rain water pipes to be connected to a drain or sewer to a covered channel formed beneath the public footpath to connect the rain water pipe to the rainwater harvesting system or to the road gutter or in any other approved manner;
(c) Rain water pipes shall be affixed to the outside of the external walls of the building or in recess or chases cut or formed in such external walls or in such other manner as may be approved by the Planning Authority.
(d) Regulations for conservation of rainwater shall be as prescribed in the G.O. Ms. No. 6/2010- Hg., Dated 19-3-2010 of the Housing Secretariat, Puducherry and appended in Annexure-VII.
Defective work.— The Planning Authority shall have power to condemn any work, workmanship or materials executed by any person which in its opinion is unsatisfactory or is likely to constitute danger to public safety or health. Any work, workmanship or materials so condemned shall be remedied, amended or made good or shall be removed in whole or in part and replaced by new work, workmanship or materials as the Planning Authority may require.
Water supply and sanitary installations.— The percapita water requirement for various occupancies are detailed in Annexure-VIII. The requirements regarding sanitary installations of the buildings shall conform to those prescribed in the National Building Code of India. The requirements of sanitary installations for various occupancies are detailed in Annexure-IX.
Latrines with an opening on public roads.— It is prohibited to have latrines opening on to public roads.
Disposal of sewage.—Until arrangements are made for the removal of waste by an appropriate water borne system it will be obligatory for every application for a new construction or major additions or alteration to be accompanied by plans for properly designed septic tanks within the curtilage of the plot. In case of existing buildings in the built up area where water borne system of drainage is available, it shall be obligatory for the owner to provide flush out and connect this sewage to the main underground sewage within such period as may be specified by the competent authority of the Government.
Construction of horse stables, cattle yards and factories of washable corrosive products.— No construction of horse stables, cattle yards and factories of washable corrosive products prejudicial to health can take place in less than 100.0 m. of any existing drinking well / source of water.
Construction of wells.—(1) No drinking water well can be opened without the prior consent of the Planning Authority and Ground Water Authority.
(2) Wells intended to supply water for human consumption or domestic purposes shall comply with the following requirements:
(i) the wells shall not be less than 15.0m. from any ash pit, refuse pit, earth closet or privy;
(ii) not less than 18.0 m. from any cesspit soakway or borehole latrine and shall be located on a site upward from the earth closet or privy ;
PART-I
235
Note: The distances mentioned above shall be reduced to 14.0 m. if one anaerobic filter is provided and to 10.0 m. if two anaerobic filters are provided between the drinking water well and the cesspit / ash pit etc.
(iii) the well shall be so situated that contamination by the movement of sub-soil or other water closet is unlikely;
(iv) the well shall be of a minimum internal diameter of not less than 1.0m.
(v) the well shall be not under a tree or otherwise it should have a canopy over it, so that leaves and twigs may not fall into the well and rot.
(3) The wall of the head of the well shall be raised above the level of the adjoining ground to form a parapet or kerb and to prevent surface water from flowing into a well and shall be surrounded with a paving constructed of impervious material which shall extend for a distance of not less than 1.8 m. in every direction from the parapet from the kerb forming the well head and the upper surface of such a paving shall be sloped away from the well.
(4) The interior surface of the lining walls of the well shall be rendered impervious for a depth of not less than 1.8 m. measured from the level of the ground immediately adjoining the well head.
(5) A well from which water is drawn by means of a bucket or other similar apparatus shall be provided with the following:
(i) a mosquito-proof type of cover to be approved by the Planning Authority / Local Authority;
(ii) a stand for the bucket, raised not less than 15cm. above the level of the surrounding paving.
Lime kilns/Brick kilns: Industries of similar nature should not be permitted within a habitable distance of 100.0 m. from habitable area or public road and quarrying shall not take place in areas other than the one marked as "Mining Zone". Proper licence for this purpose shall be obtained from the Competent Authority.