(i) Plinth.—The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm. from the surrounding ground level.
(ii) Interior Courtyards and Covered Parking.— Every interior courtyard shall be raised at least 150 mm. above the determining ground level and shall be satisfactorily drained.
(iii) Habitable rooms: Every habitable room in any building shall be in every part at least 2.80 m. in height from the surface of the floor to the underside of the roof slab or ceiling, provided that in the case of slope roof, the minimum height shall not be less than 2.2 m. This is applicable to residential, business and mercantile buildings. For office, educational and industrial buildings, the following minimum requirements shall apply:
(a) Office, Educational buildings.... Ceiling height 3.6 m. for all regions.
(b) Industrial buildings.... Ceiling height 3.6 m. except when air-conditioned, where it shall be not be less than 3.0 m. (Factory Act, 1948 and Rules therein shall govern such heights, where applicable).
(iv) Kitchen: The ceiling height of the kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.8 m. except for the portion to accommodate floor trap of the upper floor.
(v) Ledge or Tand/Loft.—The minimum head room of ledge or tand / loft shall be 2.2 m. The maximum height of loft shall be 1.5 m.
(vi) Mezzanine floor: It shall have minimum ceiling height of 2.2m.
(vii) Store room.—The height of storeroom shall not be less than 2.2 m.
(viii) Garage.—The height of the garage shall not be less than 2.4 m.
(ix) Basement.—Every basement shall be in every part at least 2.4 m. in height from the floor to the underside of the roof slab or ceiling. The minimum height of ceiling of any basement shall be 0.9 m. and the maximum 1.2 m. above the average surrounding ground level.
(x) Stilt floor.—The minimum height of the stilt floor shall not be less than 2.4 m.
(xi) Staircase headroom.— The minimum headroom in a passage under the landing of a staircase shall be 2.2 m. The minimum clear headroom in any staircase shall be 2.2 m.
(xii) Low income and EWS housing: The minimum height of rooms / spaces shall be as follows: - Note: (no basement shall be allowed)
[ PART-I
(a) Habitable room...2.60 m.
(b) Kitchen...2.6 m.
(c) Bath/W.C...2.1 m.
(d) Corridor ...2.1 m.
(e) Staircase head room... 2.10 m.
(f) In the case of sloped roof, the average height of the roof for habitable rooms shall be 2.60 m. and the minimum height at eaves shall be 2.00 m.
(xiii) Parapet: Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0m. and not more than 1.2m. in height from the finished floor level.
(xiv) Boundary Wall/Compound Wall: The maximum height of the compound wall shall be 1.5 m. above the centerline of the front street. Compound wall up to 2.4 m. height may be permitted if the top 0.9 m. is of open type.
- Minimum size of habitable rooms.—No habitable room shall have a floor area of less than 9.3 sq.m. except in the case of hostels attached to recognised educational institutions. The minimum size of habitable room for the residence of a single person may be 8.0 sq.m. The minimum width of a habitable room shall be 2.5 m. Where there are two rooms, one of these shall not be less than 9.3 sq.m. and the other not less than 7.5 sq.m. with a minimum width of 2.1 m.
For Low Income Housing & E.W.S. the minimum size of habitable room shall be as follows :
(i) In the case of one roomed house, the size of multi-purpose room, including space for cooking, shall be not less than 12.5 sq.m. with a minimum width of 2.50 m.
(ii) In the case of two-roomed house, the size of 1st room shall not be less than 9.0 sq.m. with minimum width of 2.5 m. and 2nd shall not be not less than 6.50 sq.m. with a minimum width of 2.10 m., provided the total area of both the rooms is not less than 15.5 sq.m. In the case of incremental housing the bigger room shall always be the first room.
- Minimum size of Bathrooms and water closets.— (1) Every bathroom or water closet shall:-
(a) be so situated that at least one of its walls open to external air, and in case of bathroom it shall have a window or a ventilator open to external air of a superficial area of not less than 10% of the floor area;
(b) (i) have a floor area in case of bathrooms inclusive of water closet of not less than 2.8 sq.m. for which the smallest side shall not be less than 1.20 m.;
(ii) in case of a bathroom exclusive of a water closet, the floor area shall not be less than 1.80 sq.m. and the smallest side not less than 1.2 m.
(c) have a height of not less than 2.5m;
(d) not be directly over or under any other room other than another bathroom or water closet, washing place, terrace unless it has a water tight floor;
(e) have the platform or seat either plastered with cement or is made of some water tight non-absorbent material;
(f) be enclosed by walls or partitions of brick or stone. The surface of every such wall or partition shall be finished with a smooth impervious surface such as cement plaster 12 mm. thick of glazed tiles or polished marble or any other suitable material to a height of 1.5 m. above the floor of such room;
(g) have an impermeable floor made of smooth hard material having a suitable fall to a soil pipe with an adequate trap connection and have a floor level of such a height so as to ensure suitable grade towards the sewage drain.
PART-I
225
(2) No room containing a water closet shall be used for any purpose other than a lavatory and no such room shall open directly into any kitchen or cooking space. Every room containing a water closet shall have a door completely closing the entrance to such a room.
(3) A water closet alone shall have--
(a) a floor area of not less than 1.15 sq.m. of which the smallest side shall not be less than 1 m.;
(b) a window or a ventilator of superficial area of not less than 10% of the floor area;
(c) an impermeable floor made of smooth hard material having slope of 0.5 per cent. towards the back of latrine;
(d) an impermeable dado 1.0 m. high;
(e) roof height not less than 2.5m.
(4) (a) Every building meant for habitation shall be provided with water closet. The Planning Authority shall determine in each case whether the premises shall be served by a water closet connected to a sewer or a septic tank provided that if a sewer is within 30.0 m. of the site it shall be connected to the sewer, provided further that until the sewer begins to function, the water closet shall be connected to a septic tank provided for this purpose, subject to the condition that it shall be connected to the sewer as and when required by the Planning Authority.
(b) The Planning Authority may refuse to permit the construction of any latrine or urinal at a particular place if in its opinion such latrine or urinal would be a nuisance in the neighbourhood or would be objectionable to the occupants of neighbourhood building.
Note: For temporary structures including huts meant for habitation the Planning Authority shall determine in each case whether the provision of latrine is obligatory or not.
(5) Minimum size of bath and W.C. for low-income housing:
(i) The size of independent W.C. shall be 0.90 sq.m. with minimum width of 0.90m.
(ii) The size of combined bath and W.C. shall be 1.80 sq.m. with minimum width of 1.0 m.; and
(iii) The size of independent bath shall be 1.20 sq.m. with minimum width of 1.0m.
- Minimum size of Kitchen.— (1) The area of a kitchen where separate dining area is provided, shall be not less than 5.0 sq.m. with a minimum width of 1.8 m. Where there is a separate store, the area of the kitchen may be reduced to 4.5 sq.m. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 sq.m. with a minimum width of 2.1 m.
(2) Every room to be used as kitchen shall have -
(a) a height of not less than 2.80m;
(b) a window or a ventilator of superficial area of not less than 10% of the floor area;
(c) an impermeable floor and an impermeable dado or any other water proof material to a minimum of one metre high.
(d) The minimum size of kitchen for low-income housing - The size of cooking alcove serving as cooking space shall not be less than 2.40 sq.m. with a minimum width of 1.20 m. The size of individual kitchen provided in a two-roomed house shall not be less than 3.30 sq.m. with a minimum width of 1.50 m.
-
Minimum size of Lofts.—A loft in a habitable room shall not cover more than 25% of the area of floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
-
Minimum size of Mezzanine floor.— Size - The minimum size of mezzanine floor if it is used as a living portion shall not be less than 9.3 sq.m., the aggregate area of which shall in no case exceed one-third of the plinth area of the building. A mezzanine floor may be permitted over a room or a compartment provided that:
(1) it conforms to the standards of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.3 sq.m. or more;
[ PART-I
(2) it is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
(3) such mezzanine floor is not subdivided into smaller compartments;
(4) such mezzanine floor or any part of it shall not be used as a kitchen; and
(5) in no case a mezzanine floor shall be closed so as to make it liable to be converted into unventilated compartments.
- Basement.— (1) The basement shall not be used for residential purposes.
(2) The basement to be constructed within the building envelop and subject to maximum coverage on floor 1 (entrance floor) may be put to only the following uses:
(a) Storage of household or other goods of ordinary non-combustible materials;
(b) Strong rooms, bank cellars etc;
(c) Air-conditioning equipment and other machineries equipments used for services and utilities of the building and
(d) Parking spaces.
(3) The basement shall have the following requirements:
(a) No basement shall be permitted on an individual plot unless it has a clear set back of 2m. from the boundary line of the plot or the required setbacks whichever is more.
(b) Every basement shall be in every part at least 2.4 m. in height from the floor to the underside of the roof slab or ceiling;
(c) Adequate ventilation shall be provided for the basement. The ventilation requirements shall be the same as required by the particular occupancy according to bye-laws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems etc.
(d) The minimum height of the ceiling of any basement shall be 0.9 m. and the maximum, 1.2 m. above the average surrounding ground level.
(e) Adequate arrangements shall be made such that surface drainage does not enter the basement.
(f) The walls and floors of the basement shall be water-tight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
(g) The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors. Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of clause (d) above.
The slope of a ramp shall not exceed 1 in 10. In certain cases steeper slopes may be permitted but in no case greater than 1 in 8. For all slopes exceeding 1 in 10 and wherever the use is such as to involve danger of slipping, the ramp shall be surfaced with approved non-slipping material.
(h) Basement in an individual plot touching the adjacent property shall not be allowed and in all cases the owners shall have to indemnify the Planning Authority against any damage caused by her/him/them to the adjacent property as per the Annexure-VI.
- Minimum size of Other requirements.—(1) Store room : The size of store room when provided in a residential building shall not be less than 3.00 sq.m.
(2) Garage: The size of garage shall be as below:
(i) Private Garage : 3.0 m. x 6.0 m. minimum and
(ii) Public Garage : Based on the number of vehicles parked.
PART-I]
227
(3) Petty shops: The minimum width of a petty shop shall be 2.50 m. and the floor area shall not be less than 7.5 sq.m.
- Other building requirements.—(1) Minimum width of staircase shall be as follows:
(a) Residential buildings (dwellings) .. 1.0 m.
Note: For row housing with two storeys, the minimum width shall be . . 0.75 m.
(b) Residential hotel building . . 1.5 m.
(c) Assembly buildings like auditoria, theaters and cinemas. . . 2.0 m.
(d) Educational buildings .. 1.5 m.
(e) Institutional buildings . . 2.0 m.
(f) All other buildings . . 1.5 m.
(2) The minimum width of corridors shall be as follows:
| Sl.No. | Building use or type | Minimum width of corridor |
|---|---|---|
| 01 | Residential buildings | 1.0 m. |
| 02 | Assembly buildings such as Auditoriums, Kalyanamandapam, Cinema theatre, Religious Buildings, Temples, Mosques or Churches and other buildings of Public Assembly of Conference. | 2.0 m. |
| 03 | Institutional buildings such as(a) Government Offices(b) Hospitals and Nursing Homes(c) Educational Buildings such as schools, Colleges, Research Institutions,(d) Commercial buildings such as private offices, Nursing Homes, Lodges, etc.,(e) All other buildings | 2.0 m.2.4 m.2.0 m.2.0 m.1.5 m. |
(3) The minimum width of balcony in any residential building shall not be less than 1.0 m. and 1.5 m. for other than residential uses.
(4) The following criteria shall be adopted for low income housing in urban area for internal individual staircase:
(a) Minimum width of stair
(i) Two storeyed-straight . . 0.60 m.
(ii) Two storeyed - winding . . 0.75 m.
(iii) Three or more storeyed-straight .. 0.75 m.
(iv) Three or more storeyed-winding .. 0.90 m.
(b) Riser . . 0.20 m. (maximum)
(c) Tread (i) Two storeyed .. 0.23 m. (minimum)
[ PART-I
(5) Details of staircase, ramps, exit, doors, lift and fire escapes :
All stairs shall comply with the following requirements:
(a) Head room: All stairs ways shall have at least 2.20 m. of clear head room, measured perpendicularly from the nosing.
(b) Tread and risers: Treads and risers shall be so proportioned that the sum of two risers and a tread width is not be less than 53 cm. and not more than 63 cm. No riser shall be more than 20 cm. and no tread width less than 23 cm. There shall be no variation in the widths of treads or the heights of risers in any one flight of stairs. No stairway should ordinarily be permitted cutting across any window. The surface material of stairs treads and landings shall be as such as not to involve undue danger of slipping. Number of risers shall be limited to 12 per flight.
(c) Landing: No stairway shall have a height of more than 1.75 m. between landings nor less than two risers between consecutive landings, the landing shall have a dimension, not less than the width of stairs, measured in the direction of the run.
(d) Rails: Stair shall have walls or well-secured balustrades or guards on both sides. Handrails shall be placed not less than 75 cm. and not more than 1.0m. above the nosing of the treads.
(e) Space under stairs: The space beneath any stairway built in whole or in part of combustible materials except handrails shall be left entirely open. The minimum head room in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
(f) Ventilation for staircases: Every staircase shall be lighted and ventilated to the satisfaction of the Planning Authority from any open space. There shall be provided, a window or windows or ventilator or ventilators for an aggregate area of at least 1.5 sq.m. in each floor in such of the wall of the staircase room as abuts 1.75 m. open space to light and ventilators such staircase. The above provision can be disposed with when an open well for light and ventilation within the space enclosed by the stairway and its landing is proposed to be provided the least horizontal dimensions of which are equal to twice the width of the staircase provided that there shall be in the roof directly over such staircase well, a ventilating skylight provided with fixed or movable louvers. The glazed roof of the skylight shall not be less than 3.75 sq.m. in area. No lift or any other fixture shall be erected in such staircase well meant for ventilation.
(g) Passage giving access to staircase: Every passage in a building in the ground floor shall in no part be less than the width of the staircase of such building to which it gives access. Provided that if only one such passage gives access to more than one staircase, its minimum width shall be equal to the width of such staircase plus one half of the total width of the remaining staircases.
(h) Ramps: Ramps if provided as a substitute for stairways shall be laid with a slope not exceeding 1 in 10 and such ramp shall comply with all requirements of a stairway and shall be surfaced with approved non-slippery materials.
(i) Corridor, verandahs and passageways: The clear width of any corridor, verandah or passageway in any building shall be not less than the details mentioned in section 38(2) above.
(j) Fire escape staircase:
(1) Fire escape staircase shall be provided for every building of, -
(i) Residential occupancies exceeding three storeys above ground level;
(ii) Occupancies other than residential exceeding two storeys above ground level;
PART-I
229
(2) The width of fire escape staircase shall be not less than 75 cm. The width of fire escape stair tread shall be not less than 15 cm. The height of the fire escape stair riser shall not exceed 19 cm. and the number of risers shall not exceed 16 per flight of stairs.
(3) The height of handrail of a fire escape staircase shall not be less than 100cm.
(4) Fire escape stairs shall be constructed only in the exterior of the building and shall be connected directly to the ground.
(5) Fire escape stairs shall have a straight flight.
(6) Entrance to fire escape staircase shall be separated and removed from internal staircase.
(k) Travel distance to emergency staircase.—(i) Every building meant for human occupancy shall be provided with emergency exit sufficient to permit safe escape of occupants in case of fire or whenever other emergency occurs.
(ii) Emergency exits shall be located in such a way that the travel distance on each floor shall not exceed 30 m. for every occupant.
(1) Fire Protection requirements.— All requirements in respect of fire protection shall be as in Part-IV, Fire Protection in National Building Code of India, 2005 and amendment No.3 under Fire Protection Annexure-II.
(m) Number of exits:
(i) For residential building/flat, one stairway shall be provided for every 12 dwelling units and part thereof.
(ii) All buildings used as educational, assembly, institutional, industrial, storage and hazardous occupancies, mixed occupancies, having area more than 500 sq.m. on each floor shall have a minimum of two staircases. They shall be enclosed type; at least one of them shall be on external walls of buildings shall open directly to the exterior, interior open space or to an open place of safety.
(n) Doorways:
(i) Every exit doorway shall open into an enclosed stairway or a horizontal exit or a corridor or passageway providing continuous and protected means of egress.
(ii) No exit doorway shall be less than 75 cm. in the case of residential and 1.2 m. in the case of all other occupancies.