19.1 Applicability
The following structural and seismic safety regulations shall apply to all buildings.
19.2 Structural Stability and Maintenance of Existing Buildings
-
The Owner/ developer/ occupants and registered appointed Person on Record shall have the assessment of structural safety of an existing building/structure damaged/undamaged carried out at stipulated periodical intervals through expert(s) chosen from a panel of experts identified by the Competent Authority. The intervals for maintenance and inspection shall be as per Schedule 12.
-
The owner/developer/occupant on advice of such expert(s) shall carry out such repair/restoration and strengthening/retrofitting of the building found necessary so as to comply with the safety standards laid down in the national building code and the Indian standards as specified.
-
In case, the owner/developer/occupant does not carry out such action, the Competent Authority or any agency authorized by the Competent Authority may carry out such action at the cost of owner/developer/occupant.
-
The Competent Authority shall specify the period within which such compliance is to be carried out.
-
The Competent Authority may also direct the owner/developer/occupant, whether the building could be occupied or not during the period of compliance.
19.3 Additions and Alterations to Existing Buildings
An alteration or addition to an existing building that is not structurally independent shall be designed and constructed such that the entire structure conforms to the structural and seismic safety requirements for new buildings, unless the following three conditions are complied with:
-
The alteration or addition complies with the requirements for new buildings.
-
The alteration or addition does not increase the seismic forces in any structural element of the existing building by more than 5% unless the capacity of the element subject to the increased force is still in compliance with the requirements for new buildings.
-
The alteration or addition does not decrease the seismic resistance of any structural element of the existing building unless the reduced resistance is equal to, or greater than, that required for new buildings.
19.4 Change of Use of Buildings or Part of a Building
When a change of use results in a structure being reclassified to a Higher Importance Factor (I) as defined in the IS: 1893‐2002 "Criteria for Earthquake Resistant Design of Structures (Fifth Revision)”, the building shall conform to seismic requirements for a new building with the Higher Importance Factor.
19.5 Structural Safety Provisions During Construction
-
The quality of all materials and workmanship shall conform to accepted standards and Indian Standard Specifications and Codes as included in Part V: Building Materials and Part VII Constructional Practices and Safety, National Building Code of India.
-
All borrow pits dug in the course of construction and repair of buildings, embankments, etc. shall be deep and connected with each other in the formation of a drain directed towards the lowest level and properly stepped for discharge into a river, stream, channel or drain, and no person shall create any isolated borrow pit which is likely to cause accumulation of water that may breed mosquitoes.
-
Alternative materials, method of design and construction and tests:‐ The provisions of the regulations are not intended to prevent the use of any material or method of design of construction not specifically prescribed in them provided any such alternative has been approved. Nothing of the provisions of these regulations is intended to prevent the adoption or architectural planning and layout conceived as an integrated development scheme. the competent authority may approve any such alternative if it conforms to the provisions of the relevant parts of the national building code, regarding material, design and construction, and the material, method, or work offered is, for the purpose intended, at least equivalent to that prescribed in these regulations in quality, strength, compatibility, effectiveness, fire and water resistance, durability and safety.
-
All buildings shall be constructed on quality control requirements.
-
In case of buildings under construction based on approved development permission, structural safety requirements shall have to be observed. However, due to such structural work of strengthening/retrofitting in the event of natural disaster if certain setbacks and margin get reduced, special permission may be granted by the Competent Authority on case to case basis.
19.6 Structural Safety Tests for Special Buildings
Whenever as per an opinion of panel experts there is insufficient evidence of compliance with the provisions of the regulations or evidence that any material or method of design or construction does not conform to the requirements of the regulations, in order to substantiate claims for alternative materials, design or methods of construction, the competent authority may require tests, sufficiently in advance, as proof of compliance. These tests shall be made by an approved agency at the expense of the owner as follows :
-
Test Methods: test methods shall be as specified by the regulations for the materials or design or construction in question. if there are no appropriate test methods specified in the regulations, the competent authority shall determine the test procedure. for methods or tests for building materials, reference shall be made to the relevant Indian standards as given in the national building code of India published by the bureau of Indian standards.
-
Test result to be preserved: copies of the result of all such tests shall be retained by the Competent Authority for not less than two years after the acceptance of the alternative material.
(a) the testing of the materials as per Indian standards shall be carried out by laboratories approved by the competent authority on this behalf.
(b) the laboratory/agency shall work out in consultation with the construction agency a testing programme of materials such as cement, steel and quality of concrete including its mixing, laying and strength at site as well as in the laboratory.
(c) This should cover various stages of construction from foundation to completion as per regulation. the laboratory shall maintain a duly authenticated report in a bound register, copy of which will be submitted to the construction agency, which will in turn forward the testing report to the competent authority.
19.7 Design for Structural and Seismic Safety
19.7.1 Design Standards
The structural design of foundations, elements of masonry, timber, plain concrete, reinforced concrete, pre‐stressed concrete and structural steel shall conform to:
-
The provisions of the National Building Code of India, Part VI ‐ Structural Design (Section – 1 Loads, Section – 2 Foundation, Section – 3 Wood, Section – 4 Masonry, Section – 5 Concrete and Section – 6 Steel), and,
-
The following Indian Standards:
(a) Structural Safety:
-
IS: 456: 2000 “Code of Practice for Plain and Reinforced Concrete”
-
IS: 800: 1984 “Code of Practice for General Construction in Steel”
-
IS 875 (Part 2): 1987 “Design loads (other than earthquake) for buildings and structures” Part 2 Imposed Loads
-
IS 875 (Part 3): 1987 “Design loads (other than earthquake) for buildings and structures” Part 3 Wind Loads
-
IS: 883: 1966 “Code of Practice for Design of Structural Timber in Building”
-
IS: 1904: 1987 “Code of Practice for Structural Safety of Buildings: Foundation”
-
IS1905: 1987 “Code of Practice for Structural Safety of Buildings: Masonry Walls”
(b) Seismic Safety:
-
IS: 1893‐2002 "Criteria for Earthquake Resistant Design of Structures (Fifth Revision)"
-
IS:13920‐1993 "Ductile Detailing of Reinforced Concrete Structures subjected to Seismic Forces ‐ Code of Practice"
-
IS:4326‐1993 "Earthquake Resistant Design and Construction of Buildings ‐ Code of Practice (Second Revision)"
-
IS:13828‐1993 "Improving Earthquake Resistance of Low Strength Masonry Buildings ‐ Guidelines"
-
IS:13827‐1993 "Improving Earthquake Resistance of Earthen Buildings ‐ Guidelines"
-
IS:13935‐1993 "Repair and Seismic Strengthening of Buildings ‐ Guidelines"
-
"Guidelines for Improving Earthquake Resistance of Buildings", by Expert Group, Government of India, Ministry of Urban Affairs & Employment, published by Building Materials and Technology Promotion Council, 1998.
-
In pursuance of the above, a certificate as indicated in Form 2D shall be submitted along with building plans/ drawings and other building information schedule annexed thereto.
(a) Cyclone/ Wind Storms:
-
IS 875 (3): 1987 "Code of Practice for Design Loads (other than Earthquake) for Buildings and Structures, Part 3, Wind Loads"
-
“Guidelines (based on IS 875 (3): 1987) for Improving the Cyclonic Resistance of Low‐rise Houses and Other Building”, by Expert Group, Government of India, Ministry of Urban Affairs & Employment, published by Building Materials and Technology Promotion Council, 1998.
19.8 Structural Safety of Display Structures
Every display structure such as billboard shall be designed to ensure safety and be installed in compliance of National Building Code.