17.3.1 Ventilation of Rooms
- Every habitable and usable room shall be equipped for adequate ventilation by provision of windows and/or ventilators that open directly into an open space or semi‐open space such as
courtyard or verandah. The size of such an open space shall be minimum one‐tenth of the floor area of the room.
-
The aggregate of all openings including doors, windows and ventilators in a room shall be minimum one‐seventh of the floor area of the room.
-
Any deficiency shall be compensated by use of mechanical system such as blowers, exhaust fans or air conditioning system according to the standards in Part VIII Building Services, Section‐I Lighting and Ventilation, National Building Code and to the satisfaction of the Competent Authority.
17.3.2 Ventilation of Basement
Every basement shall be ventilated adequately for its respective use. Any deficiency shall be compensated by use of mechanical system such as blowers, exhaust fans or air conditioning system according to the standards in Part VIII Building Services, Section‐I Lighting and Ventilation, National Building Code, and to the satisfaction of the Competent Authority.
17.3.3 Ventilation of Atrium
Any atrium covered from top shall be provided with provision of light and ventilation.
17.3.4 Ventilation of Bathrooms and Water Closets
-
Every bathroom and water closet shall be ventilated adequately.
-
At least one of the walls of a water closet or bathroom or sanitary block shall have an opening of minimum 0.25 sq.m. for each unit of W.C. or bathroom. Such opening shall open into an open to sky space with minimum dimension of 0.90 m X 0.90 m.
-
Any deficiency shall be compensated by use of mechanical system such as blowers, exhaust fans or air conditioning system according to the standards in Part VIII Building Services, Section‐I Lighting and Ventilation, National Building Code, and to the satisfaction of the Competent Authority.
17.3.5 Ventilation of Staircase for Detached Dwelling Unit, Semi-detached Dwelling Unit, ROW House, Tenement
-
For ventilation by windows: Every staircase shall be ventilated adequately from an open air space with a minimum area of 1 sq.m. The aggregate area of all windows provided shall be at least 1.20 sq.m. at each stair landing or floor in the enclosing wall of the staircase which abuts on such 1 sq.m. open air space.
-
For mechanical ventilation: Any deficiency shall be compensated by use of mechanical system such as blowers, exhaust fans or air conditioning system according to the standards in Part VIII Building Services, Section‐I Lighting and Ventilation, National Building Code, and to the satisfaction of the Competent Authority.
17.3.6 Ventilation of Industrial Buildings
-
Every usable room shall be equipped for adequate ventilation by provision of windows, ventilators, skylights or artificial means.
-
For natural ventilation, every room in such building shall be lit and ventilated by adequate number of windows, ventilators and sky lights exclusive of doors having clear opening not less than 1/7th of the floor area abutting on open air space of width not less than 1/3rd of the height of the part of the building abutting such open space.
-
Any deficiency shall be compensated by use of mechanical system such as blowers, exhaust fans or air conditioning system according to the standards in Part VIII Building Services, Section‐I Lighting and Ventilation, National Building Code, and to the satisfaction of the Competent Authority.
17.3.7 Ventilation of Special Buildings
-
Every auditorium, halls and other special buildings shall be naturally lit and ventilated by doors, ventilators and windows abutting on an interior or exterior open air space which shall not be less than 1/5th of the total floor area.
-
Any deficiency shall be compensated by use of mechanical system such as exhaust fans or air‐conditioning system according to the standards in Part VIII Building Services, Section‐I Lighting and Ventilation, National Building Code, and to the satisfaction of the Competent Authority.
17.3.8 Change of Ventilation System
No permission shall be granted to convert an existing air‐conditioned theatre to a non‐airconditioned theatre.
17.4 Heating and Air Conditioning
Adequate heating and air conditioning as published in the National Building Code of India, Part VIII – Building Services, Section 3‐ Air Conditioning, shall be provided in all parts of a building and to the satisfaction of the Competent Authority.
17.4.1 Air‐conditioning of Special Buildings
Auditorium or cinema halls shall be air‐conditioned as per following specifications:
-
Temperature Range‐ 22 to 26.5 degrees Celsius (72º F to 80º F).
-
Change of Air per hour‐ approximately 10 times.
-
Relative Humidity‐ 50 to 60%
-
Fresh Air Requirement‐ 7.5 CFM per person.
17.5 Water‐related Requirement
17.5.1 Water Storage Tank
Water storage tank shall be maintained to be perfectly mosquito‐proof condition, by providing a properly fitting hinged cover and every tank more than 1.50 m in height shall be provided with a permanently fixed non‐ferrous metal ladder to enable inspection by antimalaria staff.
17.5.2 Drinking Water Supply
In all buildings other than residential buildings, suitable provision of drinking water shall be made for the people with a disability near the accessible toilet provided under Performance regulation 27.