17.1 Architectural Elements
17.1.1 Boundary Wall/ Compound Wall
For all Buildings other than Industrial
-
The height of a boundary wall towards the road‐side shall not exceed 1.50 m from the crown of the adjacent road and 1.80 m from the crown of the adjacent road for all other sides of the building‐unit.
-
For building‐units at junction of roads, a grill fence shall be provided with the following provisions:
(a) At least 50% perforation in the grill.
(b) The base of the fence shall not exceed 0.80 m from the level of the crown of the adjacent road for a length of 9.00 m from the corner of the building‐unit at the junction.
For Industrial Buildings
The height of a boundary wall on all sides shall not exceed 3.00 m from the crown of the adjacent road.
17.1.2 Boundary Gate/ Compound Gate
-
Boundary gate shall not open outward and shall be provided with a means to prevent the gate from opening outward on the pavement or road.
-
The minimum width of a boundary gate for all uses except Detached dwelling unit, Semi-detached dwelling unit, Row House, Tenement, etc. shall be 6.00 m.
-
For building‐units at junction of roads, the following shall be applicable:
(a) A gate shall not be permitted on the curvature of the boundary wall.
(b) If the adjacent road width is equal or more than 12.00 m, the opening in the boundary wall shall be located at a minimum distance of 15.00 m from the corner of the building‐unit at the junction. If the length of the road side edge is less than 15.00 m, the opening in the boundary wall shall be provided at the farthest end from the junction.
17.1.3 Paving in Building‐unit
Maximum of 50% of the total open space including marginal open spaces and common plot of a building‐unit shall be paved. The remaining shall be permeable for rain water percolation.
17.1.4 Access Path
-
Access path from the building‐unit entry to the building entry or plinth shall have a minimum width of 1.80 m with an even surface and devoid of steps.
-
In case of a sloping access path, the gradient shall not be greater than 1:12.
-
Any difference between the road level and building‐unit level shall be accommodated within the building‐unit boundary.
For all Buildings (Except Detached dwelling unit, Semi-detached dwelling unit, Row House, Tenement)
-
Minimum one entrance shall be provided that is accessible by people with disability and accompanied by appropriate signages as per Regulation 17.6.
-
Minimum width of this ramped access path shall be 1.20 m, 1.50 m and 1.80 m for the ramp length of 3.60 m, up to 9.00 m and more than 9.00 m respectively.
-
The pedestrian ramp leading main entrance required as per these regulations may be provided in the margin.
4. In case of sloping access path or ramp:
(a) The gradient shall not be greater than 1:12.
(b) Minimum width of ramp shall be 1.20 m and the maximum continuous length shall be 9.00 m. Such ramp shall have 800 mm high hand rail on both sides extending 300 mm beyond top and bottom of the ramp. Minimum gap from the adjacent wall to the hand rail shall be 50 mm.
(c) Entrance landing should be provided adjacent to the ramp with minimum dimension of 1.20 m x 1.50 m.
(d) Curbs, wherever provided should blend to a common level.
17.1.5 Location of Opening
Every person who undertakes construction work on a building shall so locate every opening abutting on any open space that the sill of such opening shall not be less than 90 cm above the level of the floor from which such opening is accessible.
Provided that if such opening is to be constructed flush with floor level its lower portion for a height of 90 cm shall be protected by bars or grill or similar other devices to the satisfaction of the Competent Authority.
17.1.6 Minimum Clearance Height in Buildings
17.1.6.1 For Residential Units or Commercial Buildings
(a) All habitable spaces shall have minimum height of 2.90 m between finished floor levels.
(b) All circulation and service spaces such as verandah, bathroom, washroom, toilet, passage, puja room, store room and stair cabin shall have a minimum clearance height of 2.10 m.
17.1.6.2 For Industrial Uses
all occupiable spaces shall have a minimum clearance height of 3.00 m.
17.1.6.3 In Case of Folded Roof, Minimum Clearance Height
shall be 3.00 m (measured from the lowest point of the fold).
17.1.6.4 In Case of Sloping Roof
minimum clearance height shall be 2.20 m (measured from the lowest point of the roof). The average height of the room shall not be less than the minimum clearance height as applicable according to the building use and stipulated above.
17.1.6.5 In Case of Trussed Roof
minimum clearance height shall be measured from the floor level to the bottom of the tie beam and shall be 2.80 m.
17.1.6.6 For Hollow Plinth
Spaces of hollow plinth for the purpose of parking with maximum height of 3.50 m from finished ground level to finished first floor level and minimum height shall be 3.00 m from finished ground level to finished first floor level.
17.1.6.7 For Basement
Basement exclusively used for parking shall have minimum height of 2.80 m and maximum height of 3.80 m, measured from finished basement floor level to finished upper floor level. In case of mechanical parking, more height may permitted.
17.1.7 Mezzanine
Mezzanine floor shall have a minimum clear height of 2.10 m which may be allowed in a room at a minimum clear height of 2.10 m from the floor level if the area does not exceed 30% of the area of the enclosed space.
17.1.8 Terrace
Terrace of a building shall be accessible by a common staircase and free from partitions.
17.1.9 Staircase
Stairway shall confirm to the following provisions in addition to items (1.) to (5.) below.
- Width: The minimum width of a staircase other than a fire escape shall be as given in Table here under:
| Sr. No. | TYPE OF OCCUPANCY | MINIMUM WIDTH OF STAIRCASE/ STAIRWAY/CORRIDOR(IN METERS) |
|---|---|---|
| 1 | Residential building (a) Low rise (b) Hotels and High rise | 1.21.5 |
GDCR 2016
| 2 | Educational building (a) Up to 24 m high (b) Over 24 m. high | 1.52.0 |
|---|---|---|
| 3 | Institutional buildings(i.e. hospital) (a) Up to 10 beds (b) Over 10 beds | 1.52.0 |
| 4 | Assembly buildings | 2.0 |
| 5 | Mercantile, business,industrial storage, hazardous, buildings (a) Low Rise (b) High Rise | 1.52.0 |
-
Flight: No flight shall contain more than 12 risers, but in residential buildings, in narrow plots and in high density Housing a single flight staircase may be permitted.
-
Risers: The maximum height of a riser shall be 19 cm in a residential building and 16 cm in any other occupancy. However, on an internal stairway within a dwelling unit a riser may be 25 cm high.
-
Treads: The minimum width of the tread without nosing shall be 25 cm for staircase of a residential building, other than fire escapes. In other occupancies the minimum width of the tread shall be 30 cm It shall have a non-slippery finish and shall be maintained in that fashion.
-
Head room: The minimum head room in a passage under the landing of a staircase under the staircase shall be 2.20 m.
-
Floor indicator: The number of each floor shall be conspicuously painted in figures at least 15 cm large on the wall facing the fight of a stairway or at such suitable place as is distinctly visible from the fights.
-
Hand Rail: Hand rail a minimum height of 0.90 m from the centre of the tread shall be provided.
17.2 Lighting
Adequate natural and artificial lighting as published in the National Building Code of India, Part VIII – Building Services, Section I, shall be provided in all parts of a building to the satisfaction of the Competent Authority.