21.0 Exit Requirements
21.1 General : - The following general requirements shall apply to exits : -
(a) Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants in case of fire or other emergency;
(b) In every building, exits shall comply with the minimum requirements of these regulations, except for those not accessible for general public use;
(c) All exits shall be free of obstructions;
(d) No building shall be altered to reduce the number, width or provision of exits to less than that required;
, , T , 3 3-, 2/ -,
(e) Exits shall be clearly visible and the routes to reach the exits shall be clearly marked and sign posted to guide the occupants to the floor concerned ;
(f) All exit ways shall be properly illuminated ;
(g) Fire fighting equipment, where provided along exits, shall be suitably located and clearly marked but must not obstruct the exit way and yet there should be clear indication about its location from either side of the exit way ;
(h) Alarm devices shall be installed for buildings above 15 m in height, to insure prompt evacuation of the occupants concerned through the exits ;
(I) All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street and ;
Exits shall be so arranged that they shall be reached without passing through another occupied unit.
21.2 Types of Exits -
Exits shall be either of horizontal or vertical type. An exit may be doorway, corridor, and passageways to an internal staircase or external staircase or ramps or a verandah and/or terraces which have access to the street or to roof of a building. An exit may also include a horizontal exit leading to an adjoining building at the same level. Lifts and escalators shall not be considered as exits.
21.3 Number and Size of Exits - The requisite number and size of various exits shall be provided, based on number of occupants in each room and floor based on the occupant load, capacity of exits; travel distance and height of building as per provisions below –
(a) Arrangement of Exits - Exits shall be so located that the travel distance on the floor shall not exceed that given in Table 11 below.
| Type of Building | Travel Distance |
|---|---|
| 1) Residential, Educational, Institutional and Hazardous occupancies | 22.5 m |
| 2) Assembly, Business, Mercantile and Storage occupancies | 30.0 m |
| 3) Industrial | 45.0 m |
Wherever more than one exit is required for a floor of a building, they shall be placed as remote from each other as possible. All the exits shall be accessible from the entire floor area at all floor levels.
(b) Occupant Load - For determining the exits required, the number of persons within any floor area or the occupant load shall be based on the actual number of occupants but in no case, less than that worked out from the Table 12 below.
ER , - , , 3 -,R/ -, 3
| Sr. No. | Occupancy Group | Gross Area per Occupant * (in sqm per person) |
| (1) | (2) | (3) |
| 1 | Residential | 12.5 |
| 2 | Educational | 4 |
| 3 | Institutional | 15 (see Note-1) |
| 4 | Assembly | |
| (a) with fixed or loose seats and dance floors | 0.6 (see Note-2) | |
| (b) without seating facilities including dining rooms | 1.5 (see Note-2) | |
| 5 | Mercantile (a) Street sales floor and basement (b) Upper sales floors | |
| 3 | ||
| 6 | ||
| 6 | Business and industrial | 10 |
| 7 | Storage | 30 |
| 8 | Hazardous | 10 |
The gross area shall mean plinth area or covered area
Note 1 - Occupant load in dormitory portions of homes for the aged, orphanages, insane asylums, etc. where sleeping accommodation is provided shall be calculated at not less than 7.5 sqm gross area per person.
Note 2 - The gross area shall include, in addition to the main assembly room or space, any occupied connecting room or space in the same storey or in the storeys above or below where entrance is common to such rooms and spaces and they are available for use by the occupants of the assembly space. No deductions shall be made in the gross area for corridors, closets or other sub-divisions. The area shall include all space serving the particular assembly occupancy.
(c) Capacity of Exits: - The capacity of exits (doors and stairways) indicating the number of persons that could be safely evacuated through a unit exit width of 50 cm shall be as given in Table 13 below:
| Sr. No. | Group or Occupancy | Number of Occupants per unit exit width of 50 cm. | ||
| Stairways | Pedestrian Ramps | Doors | ||
| (1) | (2) | (3) | (4) | (5) |
| 1 | Residential | 25 | 50 | 75 |
| 2 | Educational | 25 | 50 | 75 |
| 3 | Institutional | 25 | 50 | 75 |
| 4 | Assembly | 40 | 50 | 60 |
| 5 | Business | 50 | 60 | 75 |
| 6 | Mercantile | 50 | 60 | 75 |
| 7 | Industrial | 50 | 60 | 75 |
| 8 | Storage | 50 | 60 | 75 |
| 9 | Hazardous | 25 | 30 | 40 |
9(.fq.y.)---8037
, , T, 3-, / -, 3
(d) Staircases for Special Buildings : - For all buildings identified in Regulation No. 8.2.6.1 there shall be a minimum of two staircases. They shall be of an enclosed type stairway. At least one of them shall be on the external walls of buildings and shall open directly to the exterior/ interior open space or to any open place of safety.
(e) Minimum Width Provisions for Stairways : - Provisions of Regulation 32 of the ‘Principal Regulations’ shall apply.
21.4 Other Requirements of Individual Exits- The detailed requirements of individual exits are given below :
(I) Stairways : (also refer to Regulation no. 40.5 of ‘Principal Regulations’)
(a) Interior stair shall be constructed of non-combustible materials throughout;
(b) Interior staircase shall be constructed as a self-contained unit with at least one side adjacent to an external wall and shall be completely enclosed;
(c) A staircase shall not be arranged round a lift shaft unless the latter is entirely enclosed by a material of required fire- resistance rating. For buildings more than 16 m in height, the staircase location shall be to the satisfaction of Chief Fire Officer of the Special Planning Authority.
(d) Hollow combustible construction shall not be permitted;
(e) Minimum width of an internal staircase shall be as per the provisions of Table 16 of the ’Principal Regulations’.
(f) The minimum width of treads without nosing shall be 25 cm for an internal staircase for residential buildings. In the case of other buildings, the minimum treads shall be 30 cm. The treads shall be constructed and maintained in a manner to prevent slipping.
(g) The maximum height of riser shall be 20 cm in the case of residential buildings and 15 cm in the case of other buildings. They shall be limited to 12 per flight. For low income housing scheme in narrow plots, single flight staircase may be provided.
(h) Handrails shall be provided with a minimum height of 90 cm from the tread.
(i) Minimum unobstructed headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
(j) No living space, store or other fire risk spaces shall open directly into the external staircase or staircases.
(k) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through a large lobby.
ER T, - , T , 3 3-, R0/ -, 93
(l) In the case of assembly, institutional, residential, hotels, industrial and hazardous occupancies, the exit sign with arrow indicating the way to the escape route shall be provided on the wall / floor and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further, all landings of floor shall have floor indication boards indicating the floor number. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of appropriate size.
(m) In case of single staircase, it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. Wherever the building is served by more than one staircase, one of the staircases may lead to basement levels, provided the same is separated at ground level by either a ventilated lobby or cut-off screen wall without opening, having a fire resistance of not less than 2 hours with discharge point at two different ends or through enclosures. It shall also be cut off from the basement areas at various basement levels by a protected and ventilated lobby / lobbies. The staircase shall be lighted and ventilated and the minimum size of openings on walls abutting to open spaces shall be 0.5 sqm per landing.
(II) Fire escape or external stairs
For buildings above 15 m in height, fire escape stairs shall be provided subject to the following conditions : -
(a) Fire escape shall not be taken into account in calculating the evacuation time of building ;
(b) All fire escapes shall be directly connected to the ground;
(c) Entrance to fire escape shall be separate and remote from the internal staircase ;
(d) The route to fire escape shall be free of obstructions at all times, except a doorway leading to the fire escape which shall have the required fire resistance ;
(e) Fire escape shall be constructed of non-combustible materials ;
(f) Fire escape stairs shall have straight flights not less than 75 cm wide with 25 cm treads and risers not more than 20 cm. The number of risers shall be limited to 16 per flight ;
(g) Handrail shall be of height not less than 90 cm.
(h) Fire escape staircase shall be connected to other staircases through common passage at every floor.
(.f9.y.)---803
ER T, T- , T , 3 3-, RO/ R-, T 3
(i) Unprotected steel frame staircase will not be accepted as a means of escape. However, steel staircase in an enclosed fire rated compartment of 2 hours will be accepted as means of access.
(III) Spiral stairs (fire escape) - The use of spiral staircase shall be limited to low occupant load and to a building of up to 9 m height unless such spiral stairs are connected to platforms, such as balconies and terraces to allow escapee to pause.
A spiral fire escape shall not be less than 150 cm in diameter and shall be designed to give adequate headroom.
(IV) Corridors
(a) Minimum width of a corridor shall not be less than 90 cm in case of 2 storeyed residential row house building and 150/200 cm in case of other buildings. Actual width shall be calculated based on the provisions of Regulation No. (a) to (c) of 21.3.
(b) In case of more than one main staircase of the building interconnected by a corridor or other enclosed space, there shall be at least one smoke stop door across the corridor or enclosed space between the doors in the enclosing walls of any two staircases.
(c) The passages (covered or uncovered) including an arcade, a courtyard, a porch or portico, spaces to be left open to sky in accordance with these Regulations in any premises shall not be used for any other purpose than the one permissible.
(V) Doorways
(a) Every exit doorway shall open into an enclosed stairway, a horizontal exit or a corridor or passageway providing continuous and protected means of egress.
(b) No exit doorway shall be less than 90 cm in width in case of residential and 100 cm. in width in case of other buildings. Doorways for bathrooms, water closets, stores etc. shall not be less than 75 cm wide. Doorways shall not be less than 200 cm in height.
(c) Exit doorways shall open outwards, that is away from the room but shall not obstruct the travel along any exit. No door, when open, shall reduce the required width of stairway or landing to less than 90 cm. Overhead or sliding doors shall not be installed.
(d) Exit door shall not open immediately upon a flight of stairs. A landing equal to at least the width of the door shall be provided in the stairway at each doorway. Level of landing shall be the same as that of the floor which it serves.
(e) Exit doorways shall be openable from the side which they serve without the use of a key.
R , , T , 3-, 2/ -,
(VI) Revolving Doors
(a) Revolving doors shall not be used as required exits except in residential, business and mercantile occupancies, but shall not constitute more than half the gross door width required;
(b) When revolving doors are considered as required exit way the following assumptions shall be made: -
(i) Each revolving door shall be credited one half a unit exit width; and
(ii) Revolving doors shall not be located at the foot of a stairway. Any stairway served by a revolving door shall discharge through a lobby or foyer.
(VII) Ramps
(1) Ramps for pedestrians
(a) Ramps with a slope of not more than 1 in 10 may be substituted for and shall comply with all the applicable requirements of required stairways as to enclosure capacity and limiting dimensions. Ramps shall be surfaced with approved non--slipping material ;
(b) Minimum width of ramps in hospitals shall be 2.25 m ;
(c) Handrails shall be provided on both sides of the ramp.
(2) Ramps for Basement or Storeyed Parking : - For parking spaces in a basement and upper floors, at least two ramps of minimum 3 m width and a slope not steeper than 1:8, shall be provided preferably on the opposite ends. Such ramps may be permitted in the side and rear marginal open spaces after leaving sufficient space as mentioned in Regulation No.17.4.1 (f) for movement of firefighting vehicles. Provided that when a building abuts 3 or more roads, the ramps shall be allowed in front marginal open space facing the smaller road or less important road from traffic point of view.
(VIII) Refuge Area: - For buildings more than 24 m in height, refuge area of 15 sqm or an area equivalent to 0.3 sqm per person, whichever is higher, to accommodate the occupants of two consecutive floors shall be provided as under: -
The refuge area shall be provided at least on one side of the periphery of the floor preferably on a cantilevered projection open to air and protected with suitable railings.
a) For floors above 24 m and up to 39 m – One refuge area on the floor immediately above 24 m.
b) For floors above 39 m – One refuge area on the floor immediately above 39 m and so on after every 15 m.
c) It shall have a minimum width of 3.0 m.
, a , T, 3-, / -, 3
d) Refuge area provided in excess of the requirements shall be counted towards F.S.I.
Note : - All refuge areas shall be accessible from common passages/staircases.