19.1.1 Main Building : The height of plinth of a building or out house, including the floor surface of a stilt floor, shall not be less than 60 cm above both, the surrounding
R T, , T , 3 3-, R/ R-, 3
ground level and the road/roads abutting the site, and shall ensure adequate.drainage of the site. In areas subject to flooding, the height of the plinth shall be at least 60 cm. above the high flood level. In the case of a storage building, the plinth height shall be that required for loading purposes.
19.1.2 Interior Courtyards/ Inner Chowks: - Every interior Courtyard shall be raised at least 15 cm. above the surrounding ground level and shall be satisfactorily drained.
19.4.1 Size - The minimum size shall be as under - (a) Independent Bathroom 1.0 m x 1.2 m (b) Independent Water Closet 0.9 m x 1.2 m
(c) Combined Bathroom and Water Closet 1.8 sqm with minimum width of 1.0 m.
19.4.2 Height - The Height of any bathroom or water closet shall not be less than 2.1 m.
19.4.3 Other Requirements - Every bathroom or water closet shall -
(a) be so situated that at least one of its wall shall open to external air with the size of opening (windows, ventilators, louvers) not less than 0.3 sqm in area and side not less than 0.3 m (See Regulation No. 19.10.3) ;
(b) have the platform or seat made of water tight non-absorbent materiall ;
(c) be enclosed by walls or partitions, the surface of which is finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room ;
(d) be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards verandah or any other room ;
(e) be used for any purpose other than as a lavatory and shall not open directly into any kitchen or cooking space by a door, window or other opening; and
(f) shall have a door completely closing the entrance to it.
19.5 Cupboards & Shelves - Cantilevered projections of cupboards and shelves may be permitted except on ground floor and would be exempted from covered area and built up area calculations. Such projections may project up to 45 cm in the setbacks for residential buildings provided the width of such cupboard/shelves does not exceed 2.4 m and each
R , , T , 3-, 2/ -,
room does not have more than one such cupboard/ shelf. Such projection shall be at least 2 m from plot boundary.
19.3.1 Size : The area of the kitchen shall not be less than 3.3 sq. m. with a minimum width of 1.5 m.
19.3.1.1 No provision for kitchen is necessary in a scheme of single-roomed tenements (item 2 in Table 8). However, an alcove (a cooking space having direct access from the main room without any inter-communicating door) of a size not less than 2.4 sqm with a minimum width of 1.2 m shall be provided.
ER T, T- a , T , 3 3-, RO/ -, T 3
19.3.2 Height : The room height of a kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.75 m or according to item 2 in Table 9.
19.3.3 Other Requirements : Every room to be used as a kitchen shall have -
(a) Means for washing of kitchen utensils, which shall lead directly or through a sink to grated and trapped connection to the waste pipe;
(b) Impermeable floor;
(c) A window of not less than 1.0 sq. m. area, opening directly on to an inner or outer chowk, but not into a ventilation shaft; and
(d) Refuse chutes, in the case of multi-storeyed residential buildings more than 24 m in height.
19.2.1 Size and Width : - The minimum size and width shall be as given in Table 8 hereunder.
| Sr. No. | Occupancy | Minimum size (sqm) | Minimum width (m) |
| (1) | (2) | (3) | (4) |
| 1 | Any habitable room | 9.5(other than those provided for below in this table and in Notes) | 2.4 |
| 2. | Single-roomed tenement | 12.5 | 2.4 |
| 3. | Rooms in a two-room tenement - (a) one of the rooms (b) other room | 9.57.5 | 2.42.4 |
| 4. | Rooms in a two-room tenement of a site and services project - (a)one of the rooms (b)other room | 9.35.6 | 2.42.3 |
| 5. | Single-bedded room in a hostel of a recognised educational institution | 7.5 | 2.4 |
| 6. | Shop | 6.0 | |
| 7. | Class room in an educational building | 38.0 or area at the rate of 0.8 sqm per student, whichever is more | 5.5 |
| 8. | Institutional building - (a) special room (b) general ward | 9.540.0 | 3.05.5 |
| 9. | Cinema hall, theatre, auditorium, assembly hall, etc. | In conformity with the Maharashtra Cinema Rules | |
Note : - (i) An additional bedroom for occupancy of a single person shall be of a size of 5.5 sqm with a minimum width of 1.8 m.
(ii) Other requirements - One full side of a habitable room must abut an exterior open space or an inner chowk as provided in Regulation 17.2.1.
ER , - , , 3 3-, R/ -, 3
19.2.2 Height : - The minimum and maximum height of a habitable room shall be as given in Table 9 below.
| Serial No. | Occupancy | Minimum height (m) | Maximum Height (m) |
| (1) | (2) | (3) | (4) |
| 1 | Flat Roof - | ||
| (a) Any habitable room | 2.75 | 4.2 | |
| (b) Habitable room in High Density Housing | 2.6 | 4.2 | |
| (c) Air-conditioned habitable room | 2.4 | 4.2 | |
| (d) Assembly halls, residential hotels of 3-star category and above, institutional, educational, industrial, hazardous or storage occupancies, department stores, entrance halls and lobbies to department stores and assembly halls | 3.6 | 4.2greater height may be permitted subject to written permission of the Chief Executive Officer, MIDC. | |
| 2 | Pitched Roof - | ||
| (a) Any habitable room | 2.75 average 2.1 at the lowest point | 4.2 average 3.2 at the lowest point | |
| (b) Habitable room in High Density Housing | 2.6 average 2.0 at the lowest point | 4.2 average 3.2 at the lowest point | |
Notes: (i) The minimum clear headroom under any beam shall be 2.4 m.
(ii) Room for ITE or any telematic equipment can have a height as required for effective functioning of that system.
(iii) In all occupancies, except those included in serial no. 1(d) in the Table 9 above, any height in excess of 4.2 m. shall be deemed to have consumed an additional F.S.I. of 50 per cent of the relevant floor area.
(i) Size: - The floor area of a store-room in a residential building, where height, light and ventilation are provided at a lower standard than those required for a living room, shall not be more than 3 sqm.
(ii) Height: - The height of a store-room shall not be less than 2.10 m.
19.7 Garage: In addition to regulation no. 17.4.1 (e), the following shall apply:
(i) The area of parking lock-up garage shall be included in F.S.I. calculations.
(ii) Size: - The size of a garage in individual residential building shall not be less than 2.5 m X 5 m. and not more than 3 m X 6 m.
(iii) Height: - The maximum headroom in a garage shall be 2.4 m.
(iv) The plinth of garage located at ground level shall not be less than 15 cm above the surrounding ground level.
(v) The garage shall be set back behind the building line for the street / road on to which the plot abuts and shall not be so located as to affect the access ways to the building.
(vi) Corner Site: When a plot fronts on two intersecting streets, the location of the garage, if proposed within the marginal open spaces, shall be diagonally opposite the point of intersection.
(vii) No garage shall be permitted in a building having stilt or basement provided for parking.