9.0 Standard Requirements of Various Parts of Buildings.
This part sets out the standard space requirements of various parts of building, light and ventilation, the building services, fire safety, etc. The following parts of a building, wherever present, shall conform to the requirements given herein:
9.1 Plinth
i) The plinth of building shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall not be less than 30cm. above the surrounding ground level. In areas subjected to flooding, the height of the plinth shall be at least 45cm. above the high flood level.
ii) Covered parking spaces and garages shall be raised at least 15 cm. above the surrounding ground level and shall be satisfactory drained.
9.2Habitable Rooms
9.2.1 Size and Dimension of Habitable Rooms
Size and dimension of habitable rooms, shall be as per requirement and convenience of the owner.
9.2.2 Height of Habitable Rooms
The minimum and maximum height of a habitable room shall be given in Table No.9A hereunder:
Table No. 9 A
No.
Occupancy
Minimum Height (m)
Maximum Height (m)
(1)
(2)
(3)
(4)
1
Flat Roof -
a) Any habitable room
2.75
4.5
a1) Habitable room in EWS / LIG Housing.
2.75
4.2
b) Air-conditioned habitable room
2.4
4.5
c) Assembly Halls, Residential Hotels of 3 star category and above, Institutional, Educational, Industrial, Hazardous or storage occupancies, Departmental Stores, Malls, IT Buildings, Office Buildings, Exhibition Centre, Convention Hall, Theatre, Film Studio, Entrance Halls and Lobbies to these buildings.
3.0(2.40 m. in case of Air conditioned room)
6.00 or higher according to the requirement of occupancy.
d) Shops
3.00
4.5
2
Pitched roof-
a) Any habitable room
2.75 (average with 2.0 m. at the lowest point)
4.5 (average with 3.2 m. at the lowest point)
b) Habitable room in EWS / LIG Housing.
2.6 (average with 2.0 m. at the lowest point)
4.2 (average with 3.2 m. at the lowest point)
Provided that the minimum head-way under any beam shall be 2.4 m.Provided further that height more than that specified above, if required for particular occupancy, shall not be counted towards calculation of FSI.
9.3
KITCHEN
9.3.1
Size of KitchenThe size of kitchen or a cooking alcove serving as cooking space shall be as per requirement and convenience of the owner.
9.3.2
Height of KitchenThe height of a kitchen measured from the surface of the floor, to the lowest point in the ceiling (bottom of slab) shall not be less than 2.75 m. except for the portion to accommodate floor trap of the upper floor.
9.4
BATH ROOMS, WATER CLOSETS, COMBINED BATH ROOM AND WATER CLOSET
9.4.1
Size of bath room and water closetMinimum size shall be as underi) Independent Bath room 1.00 m. x 1.20 m.ii) Independent Water closet 0.9 m. x 0.9 m.iii) Combined bath room and water closet 1.50 Sq.m. with minimum width or 1.00m.
9.4.2
Height of bath room and water closetThe height of a bathroom or water closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall be not less than 2.1m.
9.4.3
Other requirements of bath room and water closetEvery bathroom or water-closet shall -i) be so situated that it derives ventilation from ventilation shaft or external air,ii) have a window or ventilator, opening to a shaft or open space, of area not less than 0.3sq.m. with side not less than 0.3m.iii) all the sewerage outlets shall be connected to the sewerage system. Where no such systems exist, a septic tank shall be provided within the plot conforming to the requirements of Regulation No.9.25
9.5Ledge or Tand / Loft
9.5.1 Location and extent
Ledge or Tand may be provided at suitable places as per requirement. Lofts may be provided over kitchen, habitable rooms, bathrooms, water closets, and corridor within a tenement in residential buildings, over shops and in industrial building, as mentioned in below Table No. 9 B subject to the following restrictions-
i) The clear head room under the Loft shall not be less than2.1 m.
ii) Loft in commercial areas and industrial building shall be located 2 m. away from the entrance.
iii) Loft shall not interfere with the ventilation of the room under any circumstances.
iv) The maximum height of loft shall be 1.5m.
Table No.9 B - Provision of Loft
Sr. No.
Rooms over which Permitted
Maximum Coverage (Percentage to area or room below)
(1)
(2)
(3)
1
Kitchen/Habitable room
25
2
Bathroom, water closet, corridor
100
3
Shops with width up to 3m.
33
4
Shops with width exceeding 3m.
50
5
Industrial
33
9.5.2 Location and extent of Ledge for Air Conditioning unit
Ledge for Air Conditioning unit may be provided on the exterior of wall of the rooms of size not exceeding 0.5 m. x 1.0 m. at suitable location.
9.6.1 In residential buildings, cantilever projections of cupboards, floor to floor level, may be permitted except on ground floor. Such projections excluding window area, may project upto 0.60 m. in the setbacks for buildings. However, the window frame shall be placed on the inner side of the wall and such cupboard shall be allowed only on one wall of each room. Moreover, such projection shall be at least 6m. from plot boundary in case of special buildings.
9.6.2 For height 24 m. and more no cupboard shall reduce the marginal open space to less than 6 m. on first floor and 4.5 m. on upper floor. In congested area cupboard may be permitted on upper floors projecting in front setbacks except over lanes having width 4.50 m. or less and in marginal distances subject to 1.0 m. clear marginal distance from the plot boundary to the external face of the cupboard.
The minimum size of the mezzanine floor shall be as per requirement and convenience of owner. The aggregate area of such mezzanine floor shall in no case exceed 50% of ( ) carpet area of that room, shops, etc. Where loft is provided in the room, the mezzanine floor shall not be allowed.
The head room under mezzanine floor shall not be less than 2.1 m. Other requirements of mezzanine floor A mezzanine floor may be permitted in a room or within a space, provided i) it conforms to the standards of living rooms as regards lighting and ventilation in case the mezzanine floor is used as habitable room. ii) it is so constructed as not to interfere, under any circumstances, with the ventilation of the space over & under it. iii) such mezzanine floor or any part thereof will not be used as a kitchen. iv) it is atleast 1.8 m. away from front wall of such rooms. v) access to the mezzanine floor is from within the respective room only. vi) in no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
9.89.8.1
STORE ROOM Size of Store Room The area of a store room/ rooms, if provided in a residential building, where light, ventilation and height are provided at standards lower than as required for living room, shall be as per requirements and convenience of the owner.
9.99.9.1
GARAGE Size of private Garage The size of a garage in individual residential building shall not be less than 2.5 m. x 5.0 m. and not more than3.0m. x 6.0m.The garage, if located in the side open space, shall not be constructed within 3.0 m. from the main building, but at least 7.5 m. away from the any access road. The area of garage shall be including in FSI.
9.9.2
Height of private Garage The minimum and maximum height of garage shall be 2.4 m. and 2.75 m. respectively.
9.9.3
Plinth of private Garage The plinth of garage located at ground level shall not be less than 15 cm. above the surrounding ground level.
9.9.4
Set Back of private Garage The garage shall be set-back behind the building line for a street or road on which the plot abuts and shall not be located affecting the access ways to the building. When the site fronts on two streets, the location of a garage (in a corner plot) (if provided within the marginal distances) shall be on diagonally opposite the point of intersections.
9.109.10.1
ROOFS The roof of a building shall be so constructed or framed as to permit effectual drainage of the rainwater there from by means of sufficient rainwater pipes of adequate size, wherever required, so arranged, jointed and fixed as to ensure that the rainwater is carried away from the building without causing dampness in any part of the walls or foundations of the building or those of an adjacent buildings.
9.10.2
Top Terrace of a building shall not be sub-divided and it shall have only common access.However, intermediate terraces may be allowed to be attached with flat and shall not be counted in balcony area.
9.10.3
The Authority may require rainwater pipes to be connected to a drain or sewer through a covered channel formed beneath the public foot path to connect the rainwater pipe to the road gutter or in any other approved manner, if not used for rain water harvesting.Rainwater pipes shall be affixed to the outside of the walls of the buildings or in recesses or chases cut or formed in such walls or in such other manner as may be necessary.
9.11
BASEMENTS
9.11.1
Basement shall generally be constructed within the prescribed setbacks / margins with one or more level.Following uses shall be permissible at free of FSI.i) Air-conditioning equipment's and other machines used for services and utilities of the building;ii) Parking spaces;iii) D.G. set room, meter room and electric substation (which will conform to required safety requirements),Effluent Treatment Plant, suction tank, pump room;
9.11.1
Following uses shall be permissible and counted in FSI.a) Storage of household or other goods or ordinarily non-combustible material incidental to principle use;b) Strong rooms, bank lockers, safe deposit vaults, laundry room, Radio/ laser therapy, post mortem room, mortuary, medical shop and cold storage for hospital building etc.c) Commercial use in first basement in case of shopping centre/ shopping malls.d) Uses strictly ancillary to the Principal use.e) Nursing quarters as ancillary use to hospital in first basement, if it is 0.9 to 1.2 m. above ground level with proper ventilation.Provided that,i) If the basement is proposed flushing to average surrounding ground level, then such basement can be extended in side and rear margins upto 1.5 m. from the plot boundary.ii) Multilevel basements may be permitted if the basement is used for parking.
9.11.2
The basement shall have the following requirements -a) Every basement shall be in every part at least 2.4 m. in height from the floor to the soffit of beam.b) Adequate ventilation shall be provided for the basement with a ventilation area not less than 2.5% of the area of the basement. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans or air-conditioning systems, etc.;c) The minimum height of the ceiling of any basement shall be 0.9 m. and the maximum shall be 1.2 m. above the average surrounding ground level. However, it does not apply to the mechanically ventilated basements. In such cases, basement may also be allowed flushing to the average ground level;
d) Adequate arrangements shall be made so as to ensure that surface drainage does not enter the basement;
e) The walls and floors of the basements shall be water-tight and be so designed that the effect of the surrounding solid and moisture, if any, is taken into account in design and adequate damp proofing treatment is given. In case of special building, where, movement of fire fighting vehicle is proposed on the basement flushing to the ground level, the slab of the basement shall be designed to withstand the pressure of fire fighting vehicle.
f) The access to the basement shall be separate from the main and alternate staircase providing access and exit from higher floors. Where the staircase is continuous, the same shall be enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted subject to the provision of Regulation No. 9.12.