46 Risk Based Classification of building proposals.- (1) Hazardous buildings.- These shall include any building or part there of which is used for the storage, handling, manufacture or processing of highly combustible or explosive materials or products which are liable to burn with extreme rapidity and/or which may produce poisonous fumes or explosions for storage, handling, manufacturing or processing which involve highly corrosive, toxic or noxious alkalis, acids or other liquids or chemicals producing flame, fumes and explosive, poisonous, irritant or corrosive gases and for the storage, handling or processing of any material producing explosive mixtures of dust which result in the division of matter into fine particles subject to spontaneous ignition. The examples of buildings in this class are the buildings, which are used for:-
(i) storage under pressure of more than 0.1 N/mm2 and in quantities exceeding 70 m3, of acetylene, hydrogen, illuminating and natural gases, ammonia, chlorine, phosgene, sulphur dioxide, carbon dioxide, methyloxide and all gases subject to explosion, fume or toxic hazard, cryogenic gases, etc;
(ii) storage and handling of hazardous and highly flammable liquids, liquefiable gases like LPG, rocket propellants, etc;
(iii) storage and handling of hazardous and highly flammable or explosive materials (other than liquids); and
(iv) manufacture of artificial flowers, synthetic leather, ammunition, explosives and fireworks.
Note:-
A list of hazardous substances giving quantities, for which or exceeding which owners handling such substances are required to be covered under the Public Liability Insurance Act, 1991, has been notified under the Rules on Emergency Planning, Preparedness and Response for Chemical Accidents by the Government of India, Ministry of Environment and Forests vide Notification No. G.S.R. 347(E), dated the 01st August 1996.
(2) Classification of risk based storage building.- The provisions for site inspection of risk based storage building, as per storage material specifications are as per table given below:-
PUNJAB GOVT. GAZ., SEPTEMBER 10, 2021 2441 (BHDR 19, 1943 SAKA)
| Classification of risk based storage building | ||||
| Category | Storage Material Specifications | Stacking Height (in m) | Designated officer for site Inspection | |
| Medium | High | |||
| Category-I(Low Risk) | Articles such as Carpets, Non synthetic/synthetic yarn and fabrics. Mechanical and electrical goods (dominantly metal parts), Glassware and crockery, fiberboards, groceries, metal goods, Papers other than those listed under categories Moderate and High, Powdered and canned foods, Plastic/glass bottles containing non-flammable liquids, etc. | 4 | 6.5 | Assistant Town Planner/Assistant Engineer/Senior Divisional Engineer |
| Category-II(Medium Risk) | Articles such as Batteries, Baled cotton/synthetic fibers, Books, Baled cork, Baled waste paper, Cartons containing alcohols (in cans/bottles), Cartons of canned lacquers which dry by solvent evaporation, Chipboard, Cardboard rolls (horizontally Stored), Cereals/Grains/Foodstuff/Flour/Sugar in sacks, Cellulose/Cellulose pulp, Electrical goods other than those stated in Category low, Flammable liquids in non-combustible containers, Leather goods, Palletized liquor stocks, Plastics (non-foamed, other than cellulose nitrate), Rolled pulp and paper and asphalted paper (Horizontal storage), Veneer sheets, Wooden patterns, Metal/wooden furniture with plastic seats, etc. | 3 | 5.5 | District Town Planner/Executive Engineer. |
| Category-III(High Risk) | Articles such as Bitumen/Wax coated paper, Candles, Carbon black, Card board rolls (vertically stored), Charcoal, Coal, cellulose nitrate, Foamed plastic | 2 | 4.5 | Senior Town Planner/Senior Engineer. |
(c) The aisle width between the storage stacks shall not be less than 2.5 m and the maximum area of each storage stack shall not be more than 150m2. If these parameters are exceeded, the design density applicable shall be loaded by 2.5 L/min/m2.
| and foam rubber products, Flammable liquids in combustible containers, Linoleum products, Matches, Plastics other than those stated in Category Moderate, Rolled pulp and paper and asphalted paper (vertical storage), Rubber goods including tyres and tubes, Sawn timber, Ventilated wood stacks, Waxed and asphalt coated papers and containers in cartons, Wood wool, wooden pallets and flats (idle), Ail materials having wrappings or pre-formed containers of foamed plastics, etc. | ||||
|---|---|---|---|---|
| Category-IV(Extreme High Risk) | Off cuts and random pieces of foamed plastic or rubber rolls of sheets of foamed plastic or foamed rubber, Foam mattress, Expanded polystyrene packaging, Foam upholstery, etc | 1.25 | 3.5 | Senior Town Planner/Senior Engineer. |
Notes:-
(a) The deflector of the sprinkler fitted in the ceiling shall be at more than 1.5 m from the goods stored below. However, in case of jute storage, no jute stock shall reach within 2 m of the deflectors of the sprinkler heads.
(b) In case of storage in racks or shelves, if the height of storage is more than what is specified, intermediate sprinklers shall be provided for each shelf/ rack in addition to the ceiling sprinklers and overall design density and Assumed Maximum Area of Operation shall be maintained as per Table of IS: 15105.
(d) In case of mixed storage (both moderate and high hazard storage) in buildings, the parameters will be governed by the most hazardous occupancy.
(e) Goods stored not higher than what is stated above table for the appropriate category or not higher than the eaves height of the roofs or within 1 m of a flat ceiling whichever is the lowest shall be regarded as moderate hazard storage. If the above conditions are not met, the risk shall be regarded as high hazard storage.
(f) Any new use which increases the number of occupants to a figure comparable with other classes of occupancy shall change the classification of the building to that of the new use (for example, Warehouse used for office purposes).
(g) Warehouse buildings shall not include any article which is highly combustible or explosive materials or products which are liable to bum with extreme rapidity and or which may produce poisonous fumes or explosions for storage, handling and which involve highly corrosive, toxic or noxious alkalis, acids or other liquids or chemicals producing flame, fumes and explosive, poisonous, irritant or corrosive gases; and for the storage, handling of any material producing ex-plosive mixtures of dust which result in the division of matter in to fine particles subject to spontaneous ignition as such buildings fall in Hazardous Building Category.
(3) Classification of risk based industrial building.- The provisions for site inspection of risk based industrial building(s) are as per table given below:-
Classification of risk based industrial building
| Category | Nature of risk | Designated officer for site Inspection |
|---|---|---|
| Low risk | This subdivision shall include any building in which the contents are of such comparative low combustibility and the industrial processes or operations conducted therein are of such a nature that there is hardly any possibility for any self- propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source. | Assistant Town Planner/ Assistant Engineer/ Senior Divisional Engineer |
| Medium risk | This subdivision shall include any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with moderate rapidity or result in other hazardous situation and may give off a considerable volume of smoke, but from which neither toxic fumes nor explosions are to be feared in the event of fire. |
Punjab Govt. GAZ., September 10, 2021 (bhdr 19, 1943 Saka)
2447