(a) If a window is partly fixed, the openable area shall be counted.
(b) No portion of a room shall be assumed to be lighted, if it is more than 7.5 m away from the opening assumed for lighting that portion.
(c) The area of openings above shall be increased by 25 percent in the case of a kitchen.
(d) In bathroom or water closet have a window or ventilator, opening to a shaft or open space, of area not less than 0.3 m2 with side not less than 0.3 m.
(e) No room containing water-closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing watercloset shall have a door completely closing the entrance to it.
(f) Mechanical light and ventilation shall be permissible in accordance with the National Building Code of India, 2016, as amended from time to time.
(3) Ledge or Tand. – (i) Height.- The minimum head-room of ledge or Tand or loft shall be 2.2 m. The maximum height of loft shall be 1.5 m.
(ii) Size.- A ledge or Tand or loft in a habitable room shall not cover more than 25 percent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
(4) Mezzanine Floor.- (i) Height.- It shall have a minimum height of 2.2 m. with no beams or protuberances below 1.8 m.
(ii) Size.- The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5 m2. The aggregate area of such mezzanine floor in a building shall in no case exceed one-third the plinth area of the building.
Notes:-
(a) A mezzanine floor may be permitted over a room or a compartment;
(b) It conforms to the standard of living/ habitable rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5 m2 or more;
(c) It is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
(d) Such mezzanine floor is not subdivided into smaller compartments;
(e) Such mezzanine floor or any part of it shall not be used as a kitchen; and
(f) In no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
(5) Basement.- (i) The multi-level basement in plots of an area above 2025 sq.m shall be allowed below the ground and beyond the building line at ground level subject to a clear minimum front margin of 4.5 m and side and rear margins of 3 m, subject to the provision of mechanical ventilation and all safety provisions and drainage. However, it is essential that the basement top slab below the external circulation at ground level should be designed for fire fighting vehicular loads as given in clause 4.6 of Part III of the National Building Code of India, 2016, as amended from time to time. The owner or the applicant, as the case may be, shall be bound to execute indemnity bond in the favour of competent authority as specified in Annexure 21.
(ii) In case of plot size upto 2025 sq.m, single story basement is allowed upto zoned area or upto the boundary of the plot except front and rear side, as the case may be, subject to the condition that the owner shall leave minimum 2.44 m (8'-0") setback from the respective side of the boundary wall of the plot, if adjoining plot has a building upto 2.44m from the plot line.
(iii) The basement shall not be allowed in the case of No construction Zone or Area or Master Plan Green area or any other restricted area or zone under the provision of any other Act or policy of the State or Central Government.
(iv) Other conditions:.- The following are the conditions for the basement, namely:-
(a) First level basement area may be used for habitable purposes subject to the condition that mandatory parking norms are fulfilled and compliance of all requirements for fire safety in accordance with Part 4- Fire and Life Safety of the National Building Code of India, 2016, as amended from time to time and necessary measures for required lighting, ventilation and water supply, drainage and sanitation is ensured;
(b) The minimum height of basement shall be 2.40 meters measured from the finished level of the floor to the under surface of the beam, joist girders or any other horizontal structural member. However, if basement is used for habitable purpose than the minimum height and space requirement of that area shall be in accordance with these rules;
(c) Adequate ventilation shall be provided for the basement. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air conditioning system and conform to fire safety and structural safety;
(d) The minimum height of the ceiling of first level basement shall be 0.9 meters and maximum 1.2 meters above the average surrounding ground level, except convenient shopping and residential plots. However, if sunken court is provided for light and ventilation or stilt is provided for parking or then the same shall not be mandatory;
(e) Adequate arrangement shall be made that surface drainage does not enter the basement;
(f) There shall be provisions of sufficient doors in case the basement is used for habitable purposes and maximum travel distance from any point to the door shall not exceed 15 meters;
(g) In case, where the basement is allowed beyond the building envelope in accordance with sub-rule (5), then the level of the basement shall be at the ground floor level and the slabs should be designed to bear the load of fire tenders;
(h) The walls and floors of the basement shall be watertight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given;
(i) The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors. Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of condition (e).
(j) In the case of parking spaces provided in basement(s), at least two ramps of width and slope in accordance with sub-rule (12) shall be provided, located preferably at opposite ends.
(k) Access to basements through ramps shall be permitted subject to provision of condition (e). The requirements for the ramps shall be in accordance with subrule (12) and the National Building Code of India, 2016, as amended from time to time;
(l) For all public buildings and uses including group housing, having basement going up to more than one level, access to all levels shall also be provided through lift. The exit requirements in basements shall comply with the provisions of Part 4- Fire and Life Safety of the National Building Code of India, 2016, as amended from time to time:
Provided that in case where basement used for habitable purpose shall be counted in Floor Area Ratio.
(6) Chimneys.- The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney top shall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
(7) Cabin.- The size of cabins shall not be less than 3.0 m2 with a minimum width of 1.0 m. The clear passages within the divided space of any floor shall not be less than 0.75 m and the distance from the farthest space in a cabin to any exit shall not be more than 18.5 m. In case, the sub-divided cabin does not derive direct lighting and ventilation from any open spaces or mechanical means, the maximum height of the cabin shall be 2.2 m.
(8) Boundary wall.- (i) In case of corner plot, radius of corner boundary wall shall be minimum 5’-0” or 1/8th of the width of the adjoining road whichever is more and maximum upto 20’-0” excepted residential plot or independent plots in which turning radius shall be 5’-0”.
(ii) In industrial buildings like workshops, factories, electric sub-stations, trans former stations and institutional buildings like sanatoria, hospitals, sports complex, stadium, and educational buildings like schools, colleges, including hostels, and other uses of public utility undertakings and strategically sensitive buildings, a height up to 2.4 m may be permitted on special request of the applicant. However, in case of security establishments, Jails, mental hospitals, etc. where additional height of the boundary wall is required by the applicant, the same may be allowed by the competent authority.
(iii) Boundary wall may be allowed to be constructed in No Construction Zone after leaving the road widening, if required, subject to the condition that the owner shall dismantle the boundary wall as and when required by any Government agency or authority without any claim.
(9) Septic tanks.-Where a septic tank is used for sewage disposal, the location, design and construction of the septic tank shall conform to requirements of Part 9- ‘Plumbing Services (including Solid Waste Management) and Section 2- Drainage and Sanitation of the National Building Code of India, 2016.
(10) Meter rooms.-For all buildings 15 m and above in height and in special occupancies, like educational, assembly, institutional, industrial, storage, hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500 m2 on each floor, provision shall be made for an independent and ventilated meter (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric supply from the licensee’s service and alternative supply cables. The door or doors provided for the service room shall have fire resistance of not less than two hours.
(11) Staircase or exit requirements.- The number of staircases in the building(s) shall be determined on the basis of the occupant load, travel distance, dead end restriction subject to minimum two staircases in respect of buildings identified under these rules:
Provided that where the travel distance and other requirements are complied with, one shall be a fire exit staircase out of two staircases.