(i) Building(s) of 15m in height or above, and
(ii) Special buildings, such as,
(a) hotel, educational, institutional, business, mercantile, industrial, storage, hazardous and mixed occupancies, where any of these buildings have floor area more than 500 m2 on any one or more floors;
(b) educational buildings having height 9 m and above;
(c) institutional buildings having height 9 m and above;
(d) all assembly buildings;
(e) buildings having area more than 300 sq.m of incidental assembly occupancy on any floor; and
(f) buildings with two basements or more, or with one basement of area more than 500 m2.
(iii) All exit staircases shall discharge, at the level of exit discharge, to the exist discharge, either,
(a) directly, or
(b) through an exit passageway, or
(c) through a large lobby.
At least 50 percent of the staircases shall discharge as per (a) and/or (b) above.