(a) The projection on door and window shall not exceed 0.91 meters. (3'-0").
(b) The projection shall not be at a lesser height than 2.06 meters (6'-9") clear above the plinth level of the building.
(c) In case of corner plots, sunshade not exceeding 0.60 meters (2 feet) on window opening on to the side shall be permitted at a height not less than 2.06 meters (6'-9).
(d) If the projection or balcony is provided more than the provision of above Tables. then the area of the additional projection shall be counted toward Floor Area Ratio.
(e) Wrap around continuous balconies shall be allowed as long as their area does not exceed 50 percent of the total open area.
(4) Parking.- (i) Parking of vehicles shall be permissible as given below: -
(a) Surface Parking.
(b) Under stilts of building(s).
(c) Under Basement or Multilevel Basement of the building(s): Provided that the provisions of the basement shall be in accordance with sub-rule (5) of rule 30 of these rules.
(d) Under podium of a building(s):
The provisions of the podium shall be in accordance with provisions of the National Building Code of India, 2016, as amended from time to time.
(e) Under separate multi-level parking block maximum up-to 20 percent of the plot area and such area shall not be counted towards Floor Area Ratio.
(ii) Minimum 10 per cent of the total required parking shall be surface parking on ground level.
(iii) Upto 20 percent of the total required parking shall be allowed as mechanical parking, except in residential buildings. However, it shall be provided fully automatic in which lower cars do not have to be manually moved out to take out the cars parked in upper stacks. Mechanical parking shall be permitted subject to mechanical and structural safety and should be covered with permanent or temporary roof structure:
Provided that to establish the automatic stacks, brochure showing the working of the stacks shall be taken as part of application for the approval of building plans and completion certificate shall be issued only after verifying that the installed stacks parking works accordingly.
(iv) Parking in independent floors under stilts shall be permissible beyond stilts within the plot area, if the parking under stilts is not sufficient as per norms. Clear height from the finished level of the ground floor to the under surface of the beam, joint girders or any other horizontal structure member shall be 7’-6”.
(v) In case parking is provided under stilts or podium or basement, it shall not be counted towards Floor Area Ratio and height for calculating the setback of the building for light and ventilation only.
(vi) Parking spaces shall be paved and clearly marked for different types of vehicles.
(vii) In buildings of mercantile (commercial), industrial (except Information Technology Industry) and storage type, in addition to the parking spaces provided, a space at the rate of 3.5 m × 7.5 m, shall be provided for loading and unloading activities, for each 1000 m2 of floor area or fraction thereof.
(viii) For the provision of car parking spaces, the space standards shall be as under.-
(a) For open parking: 23 square meters per equivalent car space.
(b) For ground floor covered parking: 28 square meters per equivalent car space.
(c) For basement or podium or multilevel floors: 32 square meter per equivalent car space.
(ix) Vehicular ramp is mandatory in accordance with sub-rule (12) of rule 30 for multilevel parking i.e. stilt or basement or podium, if used for vehicular parking. However, in case of car showrooms or car workshops, car lift may be allowed subject to condition that the plot area is not more than 3000 sq.m.
(x) In the case of parking spaces provided in basement(s) or multilevel podium (s)/ floor(s) at least two ramps of width and slope in accordance with sub-rule 30(12) of rule 30 shall be provided, located preferably at opposite ends.
(xi) If there is any doubt regarding the category of any building, for the purpose of calculation of parking the decision of the Government shall be final. Parking for the disabled persons shall comply the provisions of the Rights of Persons with Disabilities Act, 2016 (Central Act 49 of 2016), National Building Code of India, 2016 and Harmonised Guidelines and Space Standards for Barrier-Free Built Environment for persons with Disability and Elderly Persons, 2016.