Chapter 6Space Requirement for Different Parts of Building
6.1 Main Building :
The plinth of any part of a building or house shall be located with respect to average road level of site so that adequate drainage of the site is assured but not at a height less than 45 cm.—
(a) Habitable rooms shall have minimum plinth height of 0.45 m from the ground level.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 109
(b) Parking garage may have no plinth.
(c) The ground floor of a building may be permitted on stills/pillars instead of a solid plinth with a height of 2.4 m. In case of slabs with beams height should not exceed 2.8 m. and further that this space shall at all the time be kept free from any enclosure except for genuine stair-case :
Provided further that an electric m room, room for telephone D.B. bath-room, watch room, stair case room, pump room, water closet, servant room, security cabin may be permitted subject to maximum built up area of 15 Sq. m. allowed with a minimum plinth height of 30 cm and this area shall not be considered towards computation of FAR.
6.2 Interior courtyards, covered parking spaces and garages :
These shall be raised at least 15 cm above the surrounding ground level and shall satisfactorily drained.
6.3 Habitable room size and width :
The minimum size and width shall be as given NBC-2016.
6.4 Non –residential Buildings :
The minimum area for office/room/shop or any other space to be used as workspace shall not be less than 6.0 sq. m. with a minimum width of 2.1 m.
6.5 Kitchen :
Any room to be used as kitchen shall have :
(a) Unless separately provided in pantry, means for washing of kitchen utensils, which shall lead directly or through a sink to a grated and trapped -connection to the waste pipe ;
(b) An impermeable floor ;
(c) At least a window not less than 1 Sq.m in area open directly to an interior or exterior open space, but not into a shaft ; and
(d) In residential building 15 m. or more in height refuse chutes.
6.6Bathroom and W.C. :
Every bathroom or water closet shall—
(a) Be so situated that at least one of its walls open to external air and shall have a minimum opening in the form of window or ventilation to the extent of 0.37 sq. m.
(b) Not to be directly over any room other than another latrine, washing place, bath or terrace unless it has a watertight floor.
(c) Have the platform or seat made of watertight non-absorbent material.
(d) Be enclosed by walls or partitions and the surface of every such wall partition shall be finished with a smooth impervious material to a height of not less than 1.0 m. above the floor of such a room.
(e) Be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards Verandah or any other place.
(f) Have a window or ventilator, opening to a shaft or open space, of area not less than 0.3 Sq. m. with side not less than 0.3 m.
(g) No room containing water closets shall be used for any purpose except as a lavatory.
(h) Every water closed and/or a set of urinals shall have flushing cistern of adequate capacity attached to it.
(i) A toilet on terrace having a maximum of 2.2 m height shall be permitted to condition that the area of toilet be counted in FAR.
(j) All the sewerage outlets shall be connected to the Municipal Sewerage system. Where no such system exists,
No. 39-4] The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 111
a septic tank shall be provided within the plot conforming to the requirements.
6.7Mezzanine floor
6.7.1 Height :
It shall have a minimum height of 2.2 M.
6.7.2 Size :
The minimum size of the mezzanine floor if it is to be used as a living room shall not be less than 9.5 sq. m. The aggregate area of such mezzanine floor in a building shall in no case exceed onethird the plinth area of the building.
6.7.3 Other Requirements :
A mezzanine floor may be permitted over a room or a compartment, provided,—
(a) it conforms to the standard of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5 sq. m. or more;
(b) It is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
(c) Such mezzanine floor is not subdivided into smaller compartments;
(d) Such mezzanine floor or any part of it shall not be used as a kitchen; and
(e) In no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
6.8 Corner site :
When the site fronts on two streets, the frontage would be as on the street having larger width. In cases, where the two streets are of same width, then the larger depth of the site will decide the frontage and open spaces. In such case the location of a garage (on a corner plot) if provided within the open space shall be located diagonally opposite the point of intersection.
6.9 Damp site :
Wherever the dampness of a site or the nature of the soil renders such precautions necessary, the ground surface of the site between the walls of any building erected thereon shall be rendered damp proof to the satisfaction of the authority.
6.10Distance from electric line :
An overhead line shall not cross an existing building as far as possible and no building shall be constructed under an existing overhead line. No accessible point from any Verandah, balcony, or the like shall be allowed to be erected or re-erected or any additions or alterations made to a building not having the following minimum clearances from an overhead electric supply line, in accordance with the current Central Electricity Authority (Measures Relating to Safety and Electric Supply) Regulations, 2010 as amended from time to time :
(a) Clearance of buildings from lines of voltages and service lines not exceeding 650V :
(i) An overhead line shall not cross over an existing building as far as possible and no building shall be constructed under an existing overhead line.
(ii) Where an overhead line of voltage not exceeding 650 V passes above or adjacent to or terminates on any building, the following minimum clearances from any accessible point, on the basis of maximum sag, shall be observed.
(iii) For any Flat Roof, Open Balcony, Verandah roof and Lean-to-roof :
Where the line passes above the building, a vertical clearance of 2.5 m from the highest point, and
When the line passes adjacent to the building, a horizontal clearance of 1.2 m from the nearest point, and
(iv) For pitched roof :
Where the line passes above the building, a vertical clearance of 2.5 m immediately under the line, and
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 113
When the line passes adjacent to the building, a horizontal clearance of 1.2 m.
(v) The horizontal clearance shall be measured when the line is at a maximum deflection from the vertical due to wind pressure.
(vi) Any conductor so situated as to have a clearance less than that specified above shall be adequately insulated and shall be attached at suitable intervals to a bare earthed bearer wire having a breaking strength of not less than 350 kg.
(b) Clearances front buildings of lines of voltages exceeding 650 V :
(i) An overhead line shall not cross over an existing building as far as possible and no building shall be constructed under an existing overhead line.
(ii) Where an over head line of voltage exceeding 650 V passes above or adjacent to any building or part of a building, it shall have on the basis of maximum saga vertical clearance above the highest part of the building immediately under such line, of not less than:
For lines of voltages exceeding 650V
3.7 m up to and including 33 KV; and
For lines of voltages exceeding 33 KV
3.7 m plus 0.30 m for every additional 33 KV or part thereof.
(iii) The horizontal clearance between the nearest conductor and any part of such building shall, on the basis of maximum deflection due to wind pressure, be not less than:
For lines of Voltages exceeding 650 V and up to and including 11 k
1.2 m
For lines of voltages exceeding 11 KV and up to and including 33 KV.
2.0 m
For lines of voltages exceeding 33 KV
2.0 m plus 0.30 m for every additional 33 KV or part thereof.
[No. 39-4
(iv) For high voltage direct current (FTVDC) systems, vertical clearance and horizontal clearance, on the basis of maximum deflection due to wind pressure, from building shall be maintained as below:—
Table 6-1Vertical and Horizontal Clearence for High Voltage Direct Current
S. No.
D.C Voltage
Vertical Clearance
Horizontal Clearance
1
100
4.6
2.9
2
200
5.8
4.1
3
300
7
5.3
4
400
7
6.2
5
500
9.1
7.4
6
600
10.3
8.6
7
800
12.4
10.7
Source:—NBC 2016
6.11 Loft and Ledge
6.11.1 Height :
The minimum headroom for loft and ledge shall be 2.2 m.
6.11.2 Size :
A loft and ledge in a habitable room shall not cover more than 25 per cent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
6.12 Chimneys:
The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 115
tops hall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
6.13 Parapet :
Parapet walls and hand rails provided on the edges of roof Terraces, Balcony, Verandah etc. shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
Note:—
(a) The above shall not apply where roof terrace is not accessible by a staircase.
(b) However, on terrace floor in the portion where installations like DG Set, Water Tank and other, screening parapet of a suitable height may be constructed to hide such equipments etc. and there is no need to have uniform increase in the height of the parapet.
6.14 Cabin :
The size of cabins shall not be less than 3.0 Sq. m. with a minimum width of 1.0 m. The clear passages within the divided space of any floor shall not be less than 0. 75 m and the distance from the farthest space in a cabin to any exit shall not be more than 18.5 m. In case the subdivided cabin does not derive direct lighting and ventilation from any open spaces/mechanical means. The maximum height of the cabin shall be 2.2m.
6.15Boundary Wall :
The requirements of the boundary Wall are given below:—
(a) Except with the special permission of the Authority. The maximum height of the compound wall shall be 1.75 m above the centre line of the front street. Compound wall up to 2.5 m height may be permitted if the top 0.75 m is of open type construction of a design to be approved by the Authority.
(b) In the case of a corner plot, the height of the boundary wall shall be restricted to 0.75 m for a length of 10 m on the front and side of the intersections and the balance height of 0. 75 m, if required in accordance with (a) may
[No. 39-4
be made up of open type construction (through railings) and of design to be approved by the Authority.
(c) However, the provisions of (a) and (b) are not applicable to boundary walls of jails. In industrial buildings, electric substations, transformer stations, institutional buildings like sanitoria, hospitals, industrial buildings like workshops, factories and educational buildings like schools, colleges, including hostels, and other uses of public utility undertakings and strategically sensitive buildings a height up to 2.4 m. may be permitted by the Authority.
6.16Wells :
Wells, intended to supply water for human consumption or domestic purposes, where provided.
6.7.1 Location :
The well shall be located,—
(a) Not less than 15 m from any ash pit, refuse pit, earth closet or privy and shall be located on a site upwards from the earth closet or privy;
(b) Not less than 18 m from any cesspit soak away or bore hole latrine and shall be located on a site upwards from the earth closet or privy ;
(c) Such that contamination by the movement of sub-soil or other water is unlikely ; and
(d) Not under a tree or otherwise it should have a canopy over it, so that leaves and twigs may not fall into the well and rot.
6.7.2 Requirements :
The well shall—
(a) Have a minimum internal diameter of not less than 1m; be constructed to a height not less than 1 m. above the surrounding ground level, to form a parapet or kerb and to
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 117
prevent surface water from flowing in to a well, and shall be surrounded with a paving constructed of impervious material which shall extend for a distance of not less than 1.8 m in every direction from the parapet from the kerb forming the well head and the upper surface of such a paving shall be sloped away from the well ;
(b) Be of sound and permanent construction (Pucca) throughout. Temporary or exposed (Kutcha) wells shall be permitted only in fields or gardens for purposes of irrigation ; and
(c) have the interior surface of the lining or walls of the well be render dim pervious for a depth of not less than 1.8m measured from the level of the ground immediately adjoining the well-head.
6.17 Office-Cum-Letter Box Room :
In the case of multi-storeyed multifamily dwelling apartments constructed by existing and proposed Cooperative Housing Societies or Apartment Owners Associations, limited companies and proposed societies, an office-cum-letter box room of dimension 3.6 m X 3 m shall be provided on the ground floor. In case the number of flats is more than 20, the maximum size of the office-cum-letter box room shall be 20 sq. m.
6.19Stairway :
Stairway shall conform to the following provisions in addition to items (a) to (g) below. In addition, in order to satisfy firefighting requirements any stairway identified as an exit stairway shall confirm to the requirement in fire protection regulations provided in these regulations:—
(a) Width: The minimum width of a staircase other than a fire escape shall be as given in Table hereunder:—
Table 62: The minimum width of a staircase (m)
S. No.
Type of occupant
Minimum width of staircase/ Stairway/Corridors in m
1.
Residential building Low rise Hotels and High rise
1.21.5
2.
Education building Up to 24 m. High Over 24 m. High
1.52.0
3.
Institutional buildings (i.e. Hospital) Up to 10 beds Over to beds
1.52.0
4.
Assembly buildings
2.0
5.
Mercantile, business, Industrial Storage, Hazardous Buildings Low rise High rise
1.52.0
(b) Flight : No flight shall contain more than 12 rises but in residential buildings in narrow plots and in high density Housing a single flight staircase may be permitted.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 119
(c) Risers : The maximum height of a riser shall be 19 cm in residential buildings and 16 cm in any other occupancy. However, in an internal stairway within a dwelling area, a riser may be 25 cm high.
(d) Treads : The minimum width of the tread without nosing shall be 25 cm for staircase of a residential building, other than fire escapes. In other occupancies the minimum width of the tread, shall be 36 cm. It shall have a non-slippery finish and shall be maintained in that fashion.
(e) Head room : The minimum head room in passage under the landing of a staircase, shall be 2.2 M.
(f) Floor indicator : The number of each floor shall be conspicuously painted in figures at least 15 cm in large on the wall facing the flight of a stairway or at such suitable place is distinctly visible from the flights.
(g) Handrail : Handrail of a minimum height of 0.9 m from the centre of the tread shall be provided.
(h) Exit Requirements: All aspects of exit requirements for corridors, doors, stair cases, ramps, etc in respect of widths, travel distance shall be as per Part 4 ‘Fire and Life Safety’ of NBC-2016.
6.18Meter Rooms :
For all buildings above 15 m in height and in special occupancies, like educational assembly, institutional, Industrial storage hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500 sq. m on each floor, provision shall be made for an independent and ventilated m (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric supply from the licensee's service and alternative supply cables. The doors provided for the service room shall have fire resistance of not less than two hours.
6.20Roofs :
(a) In the areas receiving snowfall, the roof should be sloping and the slope shall be dictated by the amount of snowfall.
(b) The roof of a building shall be so designed and constructed as to effectively drain water by means of sufficient rain water pipes of adequate size, wherever required, so arranged, jointed and fixed as to ensure that the rain water is carried away from the building without causing dampness in any part of the walls, roof or foundations of the building or an adjacent building.
(c) The Authority may require rainwater pipes to be connected to a drain or sewer to a covered channel formed beneath the public footpath to connect the rain-water pipe to the road gutter or in any other approved manner.
(d) Rain-water pipes shall be affixed to the outside of the external walls of the building or in recesses or chases cut or formed in such external walls or in such other manner as may be approved by the Authority.
(e) It is desirable to conserve rainwater using suitable rainwater harvesting techniques including by roof water collection. In this context, reference shall be made to Part 9 'Plumbing Services (including Solid Waste Management), Section 2-Drainage and Sanitation’ of the NBC 2016.
6.22Stairs, Lifts, Lobbies and Corridor :
The width of lobbies or corridors in building shall be as under :
(a) In case of residential and non-residential building except individual detached building minimum clear width of corridor shall be as under:—
Table 63: Width of corridor as per length of the corridor (m)
Length of Corridor in M
Width of Corridor in M
Residential
Non-Residential
Up to 6
1.0
1.2
Up to 9
1.2
1.5
Up to 15
1.2
2.0
Above 15
1.5
2.5
Notes :—
(i) For every additional 9.00 m. length or part there of the width of the corridor shall be increased by 0.30 m up to a maximum of 3.00 m.
(ii) In case of starred hotels, the width of the corridor shall be as per the authorized standards of the starred hotels.
(iii) Whereas in case of residential dwelling unit occupied by single family and constructed up to three floors width of the stairs shall not be less than 1.0 m.
(b) In case of all non-residential and high-rise residential building the clear width of stair landing exclusive of parapet shall not be less than1.5 m.
(c) Minimum stair width for more than 6 tenements on each floor shall be 1.5 m.
(d) The stair-case and lifts (elevators) shall be so located that it shall be within accessible distance of not more than 25 m from any entrance of tenement or an office provided on each floor.
(e) The number and type of lifts to be provided in different buildings shall be as given in Appendix ‘F’ & ‘F-1’.
6.21Ramps :
(a) Ramps for pedestrians :
(i) General : The provisions applicable to stairway shall generally apply to ramps. A ramp in a hospital shall not be less than 2.4 m wide for stretcher and not for vehicular movement in addition to satisfying the firefighting requirements.
(ii) Slope : A ramp shall have slope of (not more than 1:10). It shall be of non-slippery material.
(iii) Handrail : A handrail shall be provided on both the sides of the ramp.
(b) Ramps for handicapped people: The provision of the ramp with handrails for every public building is compulsory for handicapped people as per the National Building Code, 2016.
(c) The ramp to basement and parking floors shall not be less than 7.2m wide for two-way traffic and 4m wide for onewa y traffic, provided with Gradient of 1:10 for L.M.V.
(d) Ramp may also be provided in side setbacks only to basement and not for upper floors which can be sloped considering unhindered movement for fire engine of minimum 6m wide and in no case the gradient shall be less than 1:10.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 121
(e) All structural design/safety aspects as per latest BIS Codes and NBC, 2016 shall be complied along with consideration of weight of Fire Engine and its manoeuvrings.
(f) Handrails shall be provided on both sides of the ramp.
(g) Ramps shall lead directly to outside open space at ground level or courtyards or safe place.
6.24Provision of exterior open spaces and height limitation around the building :
(a) The open spaces/setbacks covered area, FAR shall be as per Master Plan/Zonal Plan/building Bye-laws Chapter V.
(b) Every room that is intended for human habitation shall abut on an interior or exterior open space or on to a Verandah open to such interior or exterior open space.
(c) In case of High rise, the exterior open spaces around a building as in Building Bye-Laws shall be of green or hard surface capable of taking load of fire engine weighing up to 45 tonnes.
(d) In case, kitchen and toilets not abutting either interior or exterior open spaces, mechanical ventilation shall be accepted.
(e) Up to 25% of the total setback area can be sunk for light, ventilation and access to basement, provided fire tender movement is not hindered.
6.25 Pollution Control
6.25.1 Air Pollution :
All building shall conform to provisions of Environment Act and Rules.
6.25.2 Water Pollution :
All building shall conform to provisions of water (Prevention and Control of Pollution) Act, 1974.
6.25.3 Noise Pollution :
All buildings shall maintain ambient air quality standards in respect of noise, as prescribed in the Noise pollution (Regulation and control) Rules, 2000.
6.23Swimming Pool :
(a) “Definition :” A constructed pool or a tank indoor or outside the building, used for the purpose of swimming, bathing, aquatic sports or games, training, treatment (Therapy) or recreation, meant exclusively for human being, having a depth of water not less than that 60 cm. and the surface area exceeding 23.25 Sq. m. both for the use of public or the institution concerned.
(b) “Capacity of Pools in Relation to Bathers:” The maximum number of persons in bathing attire within the pool enclosures of the bathing area shall not exceed one person per 20 Sq. ft. (1.86 Sq. m.) of pool i. e. the area of the water surface.
(c) “Hand Rail :” A side handrail extending up above and returning to the horizontal surface of the pool deck curb or coping shall be provided at each side of each ladder.
(d) “Depth Markers :” Depth of water shall be clearly marked at or above the water surface on the vertical pool wall and on the edge of the deck or walk-way next to the pool, at maximum points and at the points of break between the deep and shallow portions and at intermediate increments of depth, spaced at not more than 2.5// (7.62 cm) intervals. Depth markers, contrasting with background shall be on both sides of the pool.
(e) “Lighting and Wiring :” Where submarine lighting is used, not less than 0.5 watts shall be employed per Sq. ft. of pool area.
(f) “Area Lightning :” Where submarine lighting is employed, area lighting shall be provided for the deck areas and
123
directed towards the deck areas and away from the pool surface so far as practicable, in a total capacity of not less than 0.6 watt per sq. ft. of deck area.
(g) Where submarine lighting is not provided and night swimming is not permitted combined pool lightning shall be provided in an amount of not less than 2 watts per sq. ft. of total area. All submarine lightning shall be individually earthed and must be watertight and damp proof.
(h) “Over Head Wiring :” No electrical wiring for electrical or power shall be permitted to pass over within 20 feet of the pool enclosure.
(i) “Shallow Minimum Depth” : Every swimming pool shall have a minimum depth in the shallow area of the main swimming area of not less than 0.9 m (3 feet), but not more than 1.07m ( 3 ′ - 6 ′ ′ ) from the overflow level to the floor.
(j) “Shallow Areas :” In a swimming pool with a diving area, the shallow area of the pool shall be defined as the portion between the shallow end and the break point between the shallow area and the diving area. The slope of the floor shall be uniform from the break point between the diving area and the shallow portion to the outside edge of the shallow portion and shall not be greater than 1 in 2 m.
(k) “Vertical Wall Depth :” The pool walls shall be vertical at all points for a depth of not less than 2 ft. 6// (0. 76 m)