The minimum size of the mezzanine floor if it is to be used as a living room shall not be less than 9.5 sq. m. The aggregate area of such mezzanine floor in a building shall in no case exceed onethird the plinth area of the building.
6.7.3 Other Requirements :
A mezzanine floor may be permitted over a room or a compartment, provided,—
(a) it conforms to the standard of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5 sq. m. or more;
(b) It is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
(c) Such mezzanine floor is not subdivided into smaller compartments;
(d) Such mezzanine floor or any part of it shall not be used as a kitchen; and
(e) In no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
6.8 Corner site :
When the site fronts on two streets, the frontage would be as on the street having larger width. In cases, where the two streets are of same width, then the larger depth of the site will decide the frontage and open spaces. In such case the location of a garage (on a corner plot) if provided within the open space shall be located diagonally opposite the point of intersection.
6.9 Damp site :
Wherever the dampness of a site or the nature of the soil renders such precautions necessary, the ground surface of the site between the walls of any building erected thereon shall be rendered damp proof to the satisfaction of the authority.
Chapter 6Space Requirement for Different Parts of Building
6.1 Main Building :
The plinth of any part of a building or house shall be located with respect to average road level of site so that adequate drainage of the site is assured but not at a height less than 45 cm.—
(a) Habitable rooms shall have minimum plinth height of 0.45 m from the ground level.
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 109
(b) Parking garage may have no plinth.
(c) The ground floor of a building may be permitted on stills/pillars instead of a solid plinth with a height of 2.4 m. In case of slabs with beams height should not exceed 2.8 m. and further that this space shall at all the time be kept free from any enclosure except for genuine stair-case :
Provided further that an electric m room, room for telephone D.B. bath-room, watch room, stair case room, pump room, water closet, servant room, security cabin may be permitted subject to maximum built up area of 15 Sq. m. allowed with a minimum plinth height of 30 cm and this area shall not be considered towards computation of FAR.
6.2 Interior courtyards, covered parking spaces and garages :
These shall be raised at least 15 cm above the surrounding ground level and shall satisfactorily drained.
6.3 Habitable room size and width :
The minimum size and width shall be as given NBC-2016.
6.4 Non –residential Buildings :
The minimum area for office/room/shop or any other space to be used as workspace shall not be less than 6.0 sq. m. with a minimum width of 2.1 m.
6.5 Kitchen :
Any room to be used as kitchen shall have :
(a) Unless separately provided in pantry, means for washing of kitchen utensils, which shall lead directly or through a sink to a grated and trapped -connection to the waste pipe ;
(b) An impermeable floor ;
(c) At least a window not less than 1 Sq.m in area open directly to an interior or exterior open space, but not into a shaft ; and
(d) In residential building 15 m. or more in height refuse chutes.
6.10Distance from electric line :
An overhead line shall not cross an existing building as far as possible and no building shall be constructed under an existing overhead line. No accessible point from any Verandah, balcony, or the like shall be allowed to be erected or re-erected or any additions or alterations made to a building not having the following minimum clearances from an overhead electric supply line, in accordance with the current Central Electricity Authority (Measures Relating to Safety and Electric Supply) Regulations, 2010 as amended from time to time :
(a) Clearance of buildings from lines of voltages and service lines not exceeding 650V :
(i) An overhead line shall not cross over an existing building as far as possible and no building shall be constructed under an existing overhead line.
(ii) Where an overhead line of voltage not exceeding 650 V passes above or adjacent to or terminates on any building, the following minimum clearances from any accessible point, on the basis of maximum sag, shall be observed.
(iii) For any Flat Roof, Open Balcony, Verandah roof and Lean-to-roof :
Where the line passes above the building, a vertical clearance of 2.5 m from the highest point, and
When the line passes adjacent to the building, a horizontal clearance of 1.2 m from the nearest point, and
(iv) For pitched roof :
Where the line passes above the building, a vertical clearance of 2.5 m immediately under the line, and
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 113
When the line passes adjacent to the building, a horizontal clearance of 1.2 m.
(v) The horizontal clearance shall be measured when the line is at a maximum deflection from the vertical due to wind pressure.
(vi) Any conductor so situated as to have a clearance less than that specified above shall be adequately insulated and shall be attached at suitable intervals to a bare earthed bearer wire having a breaking strength of not less than 350 kg.
(b) Clearances front buildings of lines of voltages exceeding 650 V :
(i) An overhead line shall not cross over an existing building as far as possible and no building shall be constructed under an existing overhead line.
(ii) Where an over head line of voltage exceeding 650 V passes above or adjacent to any building or part of a building, it shall have on the basis of maximum saga vertical clearance above the highest part of the building immediately under such line, of not less than:
For lines of voltages exceeding 650V
3.7 m up to and including 33 KV; and
For lines of voltages exceeding 33 KV
3.7 m plus 0.30 m for every additional 33 KV or part thereof.
(iii) The horizontal clearance between the nearest conductor and any part of such building shall, on the basis of maximum deflection due to wind pressure, be not less than:
For lines of Voltages exceeding 650 V and up to and including 11 k
1.2 m
For lines of voltages exceeding 11 KV and up to and including 33 KV.
2.0 m
For lines of voltages exceeding 33 KV
2.0 m plus 0.30 m for every additional 33 KV or part thereof.
[No. 39-4
(iv) For high voltage direct current (FTVDC) systems, vertical clearance and horizontal clearance, on the basis of maximum deflection due to wind pressure, from building shall be maintained as below:—
Table 6-1Vertical and Horizontal Clearence for High Voltage Direct Current
S. No.
D.C Voltage
Vertical Clearance
Horizontal Clearance
1
100
4.6
2.9
2
200
5.8
4.1
3
300
7
5.3
4
400
7
6.2
5
500
9.1
7.4
6
600
10.3
8.6
7
800
12.4
10.7
Source:—NBC 2016
6.11 Loft and Ledge
6.11.1 Height :
The minimum headroom for loft and ledge shall be 2.2 m.
6.11.2 Size :
A loft and ledge in a habitable room shall not cover more than 25 per cent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
6.12 Chimneys:
The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 115
tops hall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
6.13 Parapet :
Parapet walls and hand rails provided on the edges of roof Terraces, Balcony, Verandah etc. shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
Note:—
(a) The above shall not apply where roof terrace is not accessible by a staircase.
(b) However, on terrace floor in the portion where installations like DG Set, Water Tank and other, screening parapet of a suitable height may be constructed to hide such equipments etc. and there is no need to have uniform increase in the height of the parapet.
6.14 Cabin :
The size of cabins shall not be less than 3.0 Sq. m. with a minimum width of 1.0 m. The clear passages within the divided space of any floor shall not be less than 0. 75 m and the distance from the farthest space in a cabin to any exit shall not be more than 18.5 m. In case the subdivided cabin does not derive direct lighting and ventilation from any open spaces/mechanical means. The maximum height of the cabin shall be 2.2m.
6.15Boundary Wall :
The requirements of the boundary Wall are given below:—
(a) Except with the special permission of the Authority. The maximum height of the compound wall shall be 1.75 m above the centre line of the front street. Compound wall up to 2.5 m height may be permitted if the top 0.75 m is of open type construction of a design to be approved by the Authority.
(b) In the case of a corner plot, the height of the boundary wall shall be restricted to 0.75 m for a length of 10 m on the front and side of the intersections and the balance height of 0. 75 m, if required in accordance with (a) may
[No. 39-4
be made up of open type construction (through railings) and of design to be approved by the Authority.
(c) However, the provisions of (a) and (b) are not applicable to boundary walls of jails. In industrial buildings, electric substations, transformer stations, institutional buildings like sanitoria, hospitals, industrial buildings like workshops, factories and educational buildings like schools, colleges, including hostels, and other uses of public utility undertakings and strategically sensitive buildings a height up to 2.4 m. may be permitted by the Authority.
6.16Wells :
Wells, intended to supply water for human consumption or domestic purposes, where provided.
6.7.1 Location :
The well shall be located,—
(a) Not less than 15 m from any ash pit, refuse pit, earth closet or privy and shall be located on a site upwards from the earth closet or privy;
(b) Not less than 18 m from any cesspit soak away or bore hole latrine and shall be located on a site upwards from the earth closet or privy ;
(c) Such that contamination by the movement of sub-soil or other water is unlikely ; and
(d) Not under a tree or otherwise it should have a canopy over it, so that leaves and twigs may not fall into the well and rot.
6.7.2 Requirements :
The well shall—
(a) Have a minimum internal diameter of not less than 1m; be constructed to a height not less than 1 m. above the surrounding ground level, to form a parapet or kerb and to
The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 117
prevent surface water from flowing in to a well, and shall be surrounded with a paving constructed of impervious material which shall extend for a distance of not less than 1.8 m in every direction from the parapet from the kerb forming the well head and the upper surface of such a paving shall be sloped away from the well ;
(b) Be of sound and permanent construction (Pucca) throughout. Temporary or exposed (Kutcha) wells shall be permitted only in fields or gardens for purposes of irrigation ; and
(c) have the interior surface of the lining or walls of the well be render dim pervious for a depth of not less than 1.8m measured from the level of the ground immediately adjoining the well-head.
6.17 Office-Cum-Letter Box Room :
In the case of multi-storeyed multifamily dwelling apartments constructed by existing and proposed Cooperative Housing Societies or Apartment Owners Associations, limited companies and proposed societies, an office-cum-letter box room of dimension 3.6 m X 3 m shall be provided on the ground floor. In case the number of flats is more than 20, the maximum size of the office-cum-letter box room shall be 20 sq. m.
6.18Meter Rooms :
For all buildings above 15 m in height and in special occupancies, like educational assembly, institutional, Industrial storage hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500 sq. m on each floor, provision shall be made for an independent and ventilated m (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric supply from the licensee's service and alternative supply cables. The doors provided for the service room shall have fire resistance of not less than two hours.
6.6Bathroom and W.C. :
Every bathroom or water closet shall—
(a) Be so situated that at least one of its walls open to external air and shall have a minimum opening in the form of window or ventilation to the extent of 0.37 sq. m.
(b) Not to be directly over any room other than another latrine, washing place, bath or terrace unless it has a watertight floor.
(c) Have the platform or seat made of watertight non-absorbent material.
(d) Be enclosed by walls or partitions and the surface of every such wall partition shall be finished with a smooth impervious material to a height of not less than 1.0 m. above the floor of such a room.
(e) Be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards Verandah or any other place.
(f) Have a window or ventilator, opening to a shaft or open space, of area not less than 0.3 Sq. m. with side not less than 0.3 m.
(g) No room containing water closets shall be used for any purpose except as a lavatory.
(h) Every water closed and/or a set of urinals shall have flushing cistern of adequate capacity attached to it.
(i) A toilet on terrace having a maximum of 2.2 m height shall be permitted to condition that the area of toilet be counted in FAR.
(j) All the sewerage outlets shall be connected to the Municipal Sewerage system. Where no such system exists,
No. 39-4] The J&K Official Gazette, 24th Dec., 2021/3rd Agra., 1943. 111
a septic tank shall be provided within the plot conforming to the requirements.