Annexure 5Water Supply and Sanitation Requirements in Buildings
1 Plumbing and Sanitary Services
(1) The planning, design, construction and installation of water supply, drainage and sanitation and gas supply system shall be in accordance with Part-9: Plumbing Services, Section-l Water supply, Drainage and sanitation (including Solid Waste Management) and Section-2 Gas supply of NBC, 2005.
(2) Requirement of Water Supply for various occupancies in buildings shall be as given in Tables A.1, A.2 and A.3.
(3) Requirement of Sanitary fittings and installations for different occupancies in buildings shall be as given in Tables A.4 to A.17 for calculation of occupancy.
(4) Sewage treatment plant of capacity of treating 100% waste water to be installed. (Ref Table - 37)
3Other factors to be considered:
(1) Wastewater conveyance/treatment and prevention of contamination-
Since sewers may not be available in many cities, in most cases the toilet blocks will have on-site sanitation, which would require periodic cleaning of tanks / pits. Location on site should allow easy and hygienic emptying of the pits / tanks and ensure that ground water table is not contaminated by wastewater percolation.
(2) Adequacy in provision-
The size of the block (i.e. on number of seats) must meet visitors’ need. Inadequacy results in long queues and encourages open urination. Care is to be taken for balancing problems and other special needs of children and the elderly.
(3) Design considerations
(i) Adequate Ventilation.
(ii) Door Design / Direction of swing of the door (preferred outwards),
(iii) Adequate Waiting area and
(iv) Adequate volumes of water storage.
(4) The facilities should include:
(i) Separate toilet blocks for men and women with separate entries.
(ii) Seats for children to be provided in both sections for men and women.
(iii) Waiting / Holding area.
(iv) Space for Facility caretaker and maintenance staff – from where they can monitor and maintain both facilities for men and women.
(v) Urinal facilities for men
(vi) Waste water disposal system
(vii) Janitor / Store room for cleaning material / equipment.
Note: Table A.12 may be referred for number of seats / urinals for this section.
4 Norms for differently-abled within segregated toilets:
(1) One special W.C. in a set of toilet shall be provided for the use of differently abled persons, with essential provision of wash basin near the entrance.
(2) Minimum clear opening of the door shall be 900 mm. and the door shall swing out.
(3) Suitable arrangement of vertical/horizontal handrails with 50 mm. clearance from wall shall be made in the toilet.
(4) The W.C. seat shall be 500 mm. from the floor.
2Segregated sanitation for Visitors in Public Buildings
(1) Special requirement of segregated sanitation for Visitors in Public Buildings (Government Buildings, Hospitals, Educational Institutions, Commercial Building etc). Provisions and occupancies shall be referred at Table A.10. ** This section is provided for Segregated toilet facilities for visitors in Public Buildings (within the premises of the building, but outside the building block).
(2) Public toilets are meant for floating population, usually located near railway stations, bus stands, market places, government hospitals, religious centers etc. These toilets have a greater demand for urinals than community toilets.
(3) The key considerations for siting such facilities on the site are (i) Size of the toilet block (i.e. number of seats) and
(ii) Location of the toilet block with respect to the main building block.
(iii) Convenience of the visitors in accessing and using the facility.
(4) Surveys conducted by the central government show that people, especially women and aged, are unlikely to use the facility if it beyond 500 meters. The preferable location shall be within 200-500m from the main entry of the building.
(5) The site shall be earmarked on Site Plan or a Layout plan. The Authority shall clearly state advantages and disadvantages of the location for the owner/ engaged Competent Professional for building plan design (as per Annexure - 1) to make an informed decision on the siting.
(6) It must be accessible to visitors and general public during the operational hours of the building. However, fiscal generation for maintenance may be planned w.r.t user charges from visitors and general public.
(Experience in sample cities has shown that toilet blocks are more likely to remain clean if they are centrally located; those on periphery sooner fall into disrepair.)
6Construction Site
(1) At construction job sites, one toilet must be provided per 20 employees. In a work zone with between 21 and 199 employees, a toilet seat and one urinal must be provided for every 40 employees. For 200 or more workers, regulations call for a toilets eat and a urinal per 50 workers. The toilet must be located within 200 m or 5 minute walk.
(2) Job sites that are not equipped with a sanitary sewer must, unless prohibited by local codes, provide privies, in locations where their use will not contaminate either ground or surface water. Other alternatives to a privy could be chemical toilets, re-circulating toilets, or combustion toilets.
(3) Toilets should be cleaned regularly and maintained in good order, running water, must be provided along with soap and individual hand towels.
7 Temporary Camp Toilets
Toilet facilities shall be provided within 60 m of the, site, which shall not be closer than 15 m of dining area or kitchen. Make sure that toilet area is cleaned at least once per day, it is sanitary, adequately lighted and is employee safe.
5Water requirement and facilities:
(1) Water requirement for the facility may be worked out and enough storage for ½ day operation is to be kept in storage.
(2) If municipal water supply is reliable, the toilet blocks may have underground sump that can store half a day’s requirement and overhead tanks for another half.
(3) If municipal water supply is not available, toilet block may have its own bore well and pump with no underground sump.
(4) Alternatively a hand tube well can be used for storing water in an elevated (not overhead) tank.
(5) To minimize the wastage of water, self-closing water taps should be used. The pans must be of Pour Flush (PF) design i.e. with a steep slope. Traps should be of a 20 mm water seal. (Use of 50 mm water seal traps will require more water for flushing.)
(6) If toilet is to be linked to city sewer, a master trap has to be provided at the sewer connection.
(7) Urinals may not be fitted with urinal pots as their replacement is expensive.
8Special / Contingency Toilets [Table A.19]
(1) For Special events like open air theater, religious/political gatherings, mela, etc. for which there are no permanent toilet facilities, contingency toilets/PSUs shall be provided. The following considerations shall determine the number of toilets to be provided for particular event:
(a) Duration of the event
(b) Type of crowd
(c) Weather conditions
(d) Whether finishing times are staggered if the event has multi-functions and the following guidelines shall be applied with minimum 50 percent female toilets.
(2) Special Purpose Toilets: Special toilet facilities shall be adequately provided in public projects (transport terminals/ healthcare and other public spaces) in million plus cities for the Third gender with appropriate cleanliness arrangements.
9General guidance for water supply arrangements
(1) For new construction: Provision shall be made for underground tank for the storage of water, having capacity at 200 l. per person with adequate pumping arrangements to supply water to upper floors. Filtered water
connection will be allowed only for use of drinking and bathing needs. For other purposes i.e. flushing and gardening etc., the individual shall be required to have own arrangements of tube well water within the premises. While according sanction to Layout Plan, the Authority shall make a special mention that provision for space shall be kept for the construction of underground reservoir of adequate capacity along with booster pumping station.
(2) Arrangements as given above shall also be provided in Group Housing Societies.
(3) The plumbing arrangement in case of new constructions shall be made in a way that the potable water shall be used for drinking, cooking & bathing only and for rest of the uses, provision for ground water can be made with dual piping system.
(4) Low capacity cistern should preferably be provided instead of normal 12.5 L capacity.
(5) Provisions for sustainable methods of Water and Wastewater Management and Water harvesting may be referred from the Chapter of Rain Water Harvesting in these Rules.
TABLE-A.1 Per Capital Water requirement for various Occupancies/Uses
Sl.No
Type of Occupancy
Consumption per head per day (in lt.)
1.
Residential a) In living units b) Hostels c) Hotels with lodging accommodation(per bed) d) Hotels(5 Star and above)
135135180340
2.
Educational a) Day Schools b) Boarding Schools
45135
3.
Institutional (Medical Hospitals) a) No. of beds not exceeding 100 b) No. of beds exceeding 100 c) Medical quarters and hostels
340450135
4.
Assembly- Cinema theatres, auditoria, etc. (per seat accommodation)
15
5.
Government or Semi public business
45
6.
Segregated toilets facilities for Visitors in public Buildings a) Each use of toilet (including g washing hands and floors ) b) Flushing urinals
70.20
7.
Mercantile(Commercial) a) Restaurants (per seat) b) Other business building
7045
8.
Industrial a) Factories where bath-rooms are to be provided b) Factories where bath-rooms are not be provided
4530
9.
Storage ( including Warehouses)
30
10.
Hazardous
30
11.
Intermediate Stations (excluding mail and express stops)
45 (25)*
12.
Junction Station
70 (45)*
13.
Terminal Stations
45
14.
International and Domestic Airports
70
* The values in parenthesis are for such stations, where bathing facilities are not provided.
Note: The number of persons for Sl.No.11 to 14 shall be determined by the average number of passenger handled by the station daily with due consideration given to the staff and workers likely to use the facilities.
TABLE-A.2 Flushing Storage Capacities
Sl.No.
Classification of Building
Storage Capacity
1
For tenements having common convenience
900 lt. net per W.C. seat
2
For residential premises other than tenement having common conveniences
270 lt. net for one W.C. seat each and 180 lt. for each additional seat in the same flat.
3
For factories and workshops
900 lt. per W.C. seat and 180 lt. per urinal.
4
For cinemas, public assembly hall, etc.
900 lt. per W.C. seat and 350 lt. per urinal.
TABLE-A.3 Domestic Storage Capacities
Sl.No.
No. of Floors
Storage Capacity
Remarks
For premise occupied tenements with common conveniences
1
Ground floor
Nil
Provided down take fittings are installed.
2
Floors 2, 3, 4, 5 and upper floors
500 litre per tenement
For premises occupied as flats or blocks
1
Ground floor
Nil
Provided down take fittings are installed.
2
Floors 2, 3, 4, 5 and upper floors
500 litre per tenement
Note:- 1. If the premises are situated at a place higher than the road level in from of the premises storage at ground level shall be provided on the same lines as on floors.
2.The above storage may be permitted to be installed provided that the total domestic storage calculated on the above basis is not less than the storage calculated on the number of down take fittings according to scale given below:
Down take taps
70 lt. each
Showers
135 lt. each
Bathtubs
200 lt. each
TABLE-A.4 Sanitation requirements for Shops and Commercial Offices
Sl.No.
Sanitary Unit / Fittings
For Personnel
1
Water closet
One for every 25 persons or part thereof exceeding 15 (including employees and customers). For female personnel 1 for every 15 persons or part thereof exceeding 10.
2
Drinking Water Fountain
One for every 100 per with a minimum of one on each floor.
3
Wash Basin
One for every 25 persons or part thereof.
4
Urinals
Same as Sl.No.3 of Table 4.14
5
Cleaners' Sink
One per floor minimum, preferably in or adjacent to sanitary rooms.
Note:- Number of customers for the purpose of the above calculation shall be the average number of persons in the premises for a time interval of one hour during the peak period. For male-female calculation a ratio of 1:1 may be assumed.
TABLE-A.5 Sanitary Requirements for Hotels
Sl.No
Sanitary Unit
For Residential Public Staff
For non Residential Staff
For non Residential Staff
Sl.No
Sanitary Unit
For Residential Public Staff
For Male
For Female
1
Water Closet(WC)
One per 8 Persons omitting occupants of the attached water closet minimum of 2 if both sexed are lodged
1 for 1-15 persons 2 for 16-35 persons 3 for 36-65 persons 4 for 66-100 persons
2 for 1-13 persons 4 for 13-25 persons 6 for 26-40 persons 8 for 41-57 persons 10 for 58-77 persons 12 for 78-100 persons Add 1 for every 6 persons or part thereof.
2.
Ablution Taps
One in each W C
One in each W C
One in each W C
3.
Urinals
Nil
Nil upto 6 persons 1 for 7-20 persons 2 for 21-45 persons 3 for 40-70 persons 4 for 71-10 persons
Nil
4.
Wash Basins
One per 10 persons omitting each basin installed in the room/suite
1 for 15 persons 2 for 16-35 persons 3 for 36-65 persons 4 for 71-100 persons
1 for 1-12 2 for 13-25 3 for 26-40 4 for 41-57
5.
Baths
One per 10 persons less occupants of room with bath in suite
Nil
Nil
6
Cleaner's Sink
One per 30 Bed rooms (One per floor minimum)
Nil
Nil
7.
Kitchen Sink
One in each Kitchen
One in each Kitchen
One in each Kitchen
Table-A.5 Contd: For Public Rooms
Sl.No.
Sanitary Unit
For Male
For Female
1.
Water Closet
One per 100 persons upto 400 persons; for over 400 add at the rate of one per 250 persons or part thereof.
Two for 100 persons upto 100 persons over; 200 add at the rate of one per 100 persons or part thereof.
2.
Ablution Taps
One in each W.C
One in each W.C
3.
Urinals
One for 50 persons or part thereof.
Nil upto 6 persons 1 for 7-20 persons 2 for 21-45 persons 3 for 46-70 persons 4 for 71-100 persons
4.
Washbasins
One per WC/Urinal
One per WC
5.
Kitchen Sink
One in each Kitchen
One in each Kitchen
6.
Bath (Showers)
One per 10 persons
One per 10 persons
7.
Cleaner's Sink
One per 30 Bed rooms(One per floor minimum)
One per 30 Bed rooms(One per floor minimum)
Note:- i) It may be assumed that the two-third of the number are males and onethird females.
ii) One water tap with drainage arrangement shall be provided for every 50 persons or part thereof in the vicinity of water closet and urinals.
Table-A.6 Sanitation Requirements for Educational Occupancy