(1) Air-conditioning system should be installed and maintained so as to minimise the danger of spread of fire, smoke or fumes thereby from one floor of fire area to another or from outside into any occupied building or structure.
(2) Air-conditioning systems circulating air to more than one floor area should be provided with dampers designed to close automatically in case of fire and thereby prevent spread of fire or smoke. Such a system should also be provided with automatic controls to stop fans in case of fire, unless arranged to remove smoke from a fire, in which case these should be designed to remain in operation.
(3) Air-conditioning system serving large places of assembly (over one thousand persons), large departmental stores, or hostels with over 100 rooms in a single block should be provided with effective means for preventing circulation of smoke through the system in the case of fire in air filters or from other sources drawn into the system even though there is insufficient heat to actuate heat smoke sensitive devices controlling fans or dampers. Such means shall consist of approved effective smoke sensitive controls.
(4) Air-conditioning should conform to the following
(a) Escape routes like staircase, common corridors, lift lobbies; etc. should not be used as return air passage.
(b) The ducting should be constructed of metal in accordance with BIS 655:1963.
(c) Wherever the ducts pass through fire walls or floor, the opening around the ducts should be sealed with fire resisting material of same rating as of walls/floors.
(d) Where duct crosses a compartment which is fire rated, the ducts shall be fire rated for same fire rating. Further depending on services passing around the duct work, which may get affected in case of fire temperature rising, the ducts shall be insulated.
(e) Metallic ducts should be used even for the return air instead of space above the false ceiling.
(f) Where plenum is used for return air passage, ceiling and its fixtures shall be of noncombustible material.
(g) The materials used for insulating the duct system (inside or outside) shall be of noncombustible material [IS4355:1977]; glass wool shall not be wrapped or secured by any material of combustible nature and non-conductor of heat.
(h) Air ducts serving main floor areas, corridors, etc. shall not pass through the staircase enclosure.
(i) The air-handling units shall be separate for each floor and air ducts for every floor shall be separated and in no way inter-connected with the ducting of any other floor.
(j) Area more than 750sq.m on individual floor should be segregated by a firewall and automatic fire dampers for isolation should be provided.
(k) In case of buildings more than 24m in height, in non-ventilated lobbies, corridors, smoke extraction shaft should be provided.
(l) If the air-handling unit serves more than one floor, the recommendations given above shall be compiled with in addition to the conditions given below:
(i) Proper arrangements by way of automatic fire dampers working on smoke detector/or fusible link for isolating all ducting at every floor from the main riser shall be made.
(ii) When the automatic fire alarm operates, the respective air-handling units of the air-conditioning system shall automatically be switched off.
(iii) The vertical shaft for treated fresh air shall be of masonry construction.
(iv) The air filters of the air-handling units shall be of non-combustible materials or fire rated as given in the Tables 1-18 of Part IV of the NBC 2005.
(v) The air-handling unit room shall not be used for storage of any combustible materials.
(vi) Inspection panels shall be provided in the main trunking to facilitate the cleaning of ducts of accumulated dust and to obtain access for maintenance of fire dampers.
(vii) No combustible material shall be fixed nearer than 150 mm to any duct unless such duct is properly enclosed and protected with non-combustible material (glass wool or spyglass with neoprene facing enclosed and wrapped with aluminum sheeting) at least 3.2 mm thick and which would not readily conduct heat.
(5)Fire Dampers
(a) These shall be located in air ducts and return air ducts/passages at the following points:
(i) At the fire separation wall.
(ii) Where ducts/passages enter the central vertical shaft.
(iii) Where the ducts pass through floors.
(iv) At the inlet of supply air duct and the return air duct of each compartment on every floor.
(b) The dampers shall operate automatically and shall simultaneously switch off the air-handling fans. Manual operation facilities shall also be provided.
Note: For blowers, where extraction system and dust accumulators are used, dampers shall be provided.
(c) Fire/smoke dampers (for smoke extraction shafts) for building more than 24m in height.
(d) For apartment houses in non-ventilated lobbies /corridor operated by detection system and manual control sprinkler system.
(e) For other buildings on operation of smoke/ heat detection system and manual control/sprinkler system.
(f) Automatic fire dampers shall be so arranged so as to close by gravity in the direction of air movement and to remain tightly closed on operation of a fusible link.