(a)MEANS of Egress Identification
Signs shall comply with NFPA 101, Section 7.10 unless otherwise modified herein.
(i) Required Locations: Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 30.48 m. or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Exceptions:
(1) Exit signs are not required in rooms or areas that require only one means of egress.
(2) Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the Authority Having Jurisdiction.
(ii) Power Requirements: Exit signs shall be illuminated at all times. To ensure continued illumination for duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator.
Illumination of exit sign and directional signs shall be supplied by life safety branch of the electrical system as described in NFPA 99, Standard for Health Care Facilities.
(b)MEANS of Egress Illumination (nfpa 101, 7.8)
(i) Lighting Requirements: Means of egress illumination shall be a minimum of 10.8 lux at the floor level throughout the means of egress (including the exit discharge) at all times the building is occupied.
(ii) Power Requirements: Means of egress illumination shall be on emergency power supplied by life safety branch of the electrical system as described in NFPA 99, Standard for Health Care Facilities.
The power supply shall normally be provided by the premises’ electrical supply. In the event of power failure, an emergency electrical system shall automatically illuminate the following areas:
(1) Aisles and unenclosed stairways in rooms requiring two or more means of egress.
(2) Corridors, exit enclosures, and exit passageways in buildings required to have two or more exits.
(3) Interior exit discharge elements in buildings required to have two or more exits.
(c)EMERGENCY Power Systems
An emergency power system complying with IBC Section 2702 shall be provided for the following emergency power loads:
(i) Exit signs and means of egress illumination
(ii) Elevator car lighting
(iii) Emergency voice/alarm communications systems
(iv) Automatic fire detection systems
(v) Fire alarm and monitoring systems
(vi) Power and lighting for the fire command center
(vii)Electrically powered fire pumps
(viii) Ventilation and automatic fire detection equipment for smoke proof enclosures
(ix) Not less than one elevator serving all floors, with standby power transferable to any elevator
(x) Mechanical equipment for smoke control systems.
(xi) Horizontal sliding doors
(xii)Standby generators shall be located in a room having a minimum 2 hour fire resistance-rated separation from the remainder of the building.
(d)EMERGENCY and Standby Power Branch Circuits
Emergency and standby power shall be provided in accordance with NFPA 99: 4.4.2.2.2 and shall be supplied by an on-site generator.
i) Life Safety Branch
(1) Illumination of means of egress.
(2) Exit signs and exit directional signs.
(3) Fire alarm systems.
(4) Alarms required for systems used for the piping of non-flammable medical gases.
(5) Hospital communication systems when used for emergency instructions.
(6) Emergency generator room lighting and selected receptacles.
(7) Elevator cab lighting, control, communication, and signal systems.
(8) Automatically operated doors used for building egress.
(9) Lighting in rooms where life-support systems are in use.
ii) Critical Branch
(1) Critical care areas that use anesthetizing gases, task illumination, selected receptacles, and fixed equipment.
(2) Isolated power systems in special environments.
(3) Task illumination and selected receptacles in the following:
(a) Patient care areas including infant nurseries, selected acute nursing areas, psychiatric bed areas, and ward treatment rooms.
(b) Medication preparation areas.
(c) Pharmacy dispensing areas.
(d) Nurses’ stations.
(4) Additional specialized patient care task illumination and receptacles where required.
(5) Nurse call systems.
(6) Blood, bone, and tissue banks.
(7) Telephone equipment rooms and closets.
(8) Task illumination, select receptacle and selected power circuits for:
(a) General care beds (at least one duplex receptacle per patient bedroom).
(b) Angiographic labs.
(c) Cardiac catheterization labs.
(d) Coronary care units.
(e) Hemodialysis rooms or areas.
(f) Emergency room treatment areas (selected).
(g) Human physiology labs.
(h) Intensive care units.
(i) Post-operative recovery rooms (selected).
(9) Additional task illumination, receptacles, and selected power circuits needed for effective facility operation. Single-phase fractional horsepower exhaust fan motors that are interlocked with three-phase motors on the equipment system shall be permitted to be connected to the critical branch.
iii) Source: On-site generator.
iv) Transfer Time: For life safety and critical branch 10 seconds or UPS where required.
v) Fuel Supply: An on-premises fuel supply sufficient not less than 2 hours full demand operation of the system shall be provided.