Shafts that do not extend to the bottom of the building or structure shall:
(a) Be enclosed at the lowest or highest level of the shaft with construction of the same fire resistive rating as the lowest floor through which the shaft passes, but not less than the rating of the shaft enclosure, or,
(b)Terminate in a room having a use related to the purpose of the shaft. The room shall be separated from the rest of the building by a fire barrier having a fire-resistance rating and opening protection at least equal to the protection required for the shaft enclosure, or,
(c) Be protected by approved fire dampers installed in accordance with their listings at the lowest or highest floor level of the shaft, as applicable.
(3)Opening Protection
Opening protection (doors) for 2-hour rated enclosures shall have a 1½ hour fire resistance rating and shall be self-closing or automatic - closing and positive latching. Openings shall be limited to only those that are necessary for the purpose of the shaft. Fire window assemblies are not permitted in interior walls of shafts.
(4)Stair Penetrations
(a) Penetrations into and openings through an exit enclosure assembly shall be prohibited except for the following:
Electrical conduits, required exit doors, ductwork and equipment necessary for independent stair pressurization, water and steam piping necessary for the heating or cooling of the exit enclosure, sprinkler piping, standpipes
(b)Penetrations shall also be prohibited between adjacent exit enclosures.
(5)Refuse and Laundry Chutes
(a)Access Rooms
Access openings for refuse and laundry chutes shall be located in rooms or compartments enclosed by a fire barrier that has a fireresistance rating of not less than 1 hour. Openings into the access rooms shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour. Doors shall be self- or automatic-closing upon the detection of smoke in accordance with IBC Section 715.4.7.3.
(b)Termination Rooms
Refuse and laundry chutes shall discharge into an enclosed room separated from the remainder of the building by a fire barrier that has a fire-resistance rating of not less than 1 hour. Openings into the termination room shall be protected by opening protectives having a fire protection rating of not less than ¾ hour. Doors shall be self- or automatic closing upon the detection of smoke in accordance with IBC Section 715.4.7.3.
(r) Penetrations
Penetrations of fire resistance rated or smoke resistant construction shall be protected as follows.
(1)Fire Rated Assemblies
Fire stop systems and devices protecting through-penetrations and membrane-penetrations of fire resistance rated walls and horizontal assemblies shall be protected in accordance with NFPA 101, Section 8.3.5.
Where required per NFPA 5000, Section 8.8.8, fire dampers shall have minimum damper ratings as follows:
• 3 hours for fire resistance rated assemblies of 3 hours or greater
1-1/2 hours for fire resistance rated assemblies of less than 3 hours.
Fire dampers shall also comply with NFPA 101, Section 8.3.5 for penetrations.