The Management of the High Rise Hospital Building shall observe the following: General Fire Safety measures that shall be adhered to at all times for purposes of fully complying with the Manufacturer’s instructions and NBC/NFPA stipulations. NFPA 13, 25, 99,101, and 110 provide several options so that the more suitable option is adopted. The particular option adopted shall be clearly indicated and approval from Fire Services should be obtained.
(a)FLAMMABLE Liquids
The maximum allowable quantities (MAQ’s) of flammable materials shall comply with NFPA 30. The handling of such liquids shall not be permitted by unauthorized persons. (NFPA 99)
(b)HEATING Equipment:
The doors to furnace room shall be equipped with automatic closers and be kept closed.
The flues, pipes and steam lines shall be in good condition and properly insulated.
There shall be a gas cut-off outside the building.
(c)KITCHENS :
(i) The cooking equipment shall be provided with a steel range hood.
(ii) The cooking facilities shall be provided with a pre-engineering fire suppression system..
(iii) The discharge of automatic extinguishing system shall be monitored by the fire alarm system and provide occupant notification.
(iv) Cooking facilities shall be protected per NFPA 101, Section 18.3.2.5.
(d)LAUNDRY:
(i) The laundry doors to the main building shall be kept normally closed.
(ii) The electric devices and irons shall have operative automatic heat controls.
(iii) Keep the tumbler free from lint and dust.
(iv) Safety pilot lights shall be operative.
(e)LABORATORY:
(i) Flammable liquids shall be stored properly in listed flammable liquids cabinets or another approved manner.
(ii) The acids stored shall be handled and properly stored.
(iii) The connections of gas fired or open flame equipment shall be in good condition.
(f) Oxygen & Nitrous Oxide Storage:
(i) The oxygen and nitrous oxide cylinders shall be stored separately from other gases in accordance with the applicable NFPA standards.
(ii) ‘No Smoking’ signs and nitrous oxide warnings shall be posted on store room doors.
(iii) The cylinders shall be protected from the sun.
(iv) The cylinders shall be removed from steam pipes or radiators to prevent contact.
(g)GENERATORS:
(i) Generators shall be in good operating condition.
(ii) Generators shall start automatically.
(iii) Generators shall be tested under load monthly.
(h)WATER Heaters:
(i) The water heaters shall be properly vented.
(ii) The water heaters shall be equipped with 100% safety pilots.
(iii) The water heaters shall be equipped with pressure relief valves.
(i) General
(i) Corridors shall be kept free from storage of beds, linen, carts, etc.
(ii) The space beneath stairs and elevators shall be kept free from storage of any materials.
(iii) The trash and laundry chutes shall be sprinklered and additionally comply with NFPA 101 Section 18.5.4.
(iv) The covers on breaker panels and face plates shall be kept in good condition.
(v) The appliance cords shall be kept in good condition.
(vi) The appliance cords shall be protected against mechanical injury.
(vii) Only approved metal containers shall be used for all oily waste, polishing or cleaning materials.
(viii) Combustible liquids shall be kept in approved metal cans.
(ix) The refuse should be removed from the premises or burned daily.
(x) The sprinkler heads shall be unobstructed and adequate clearances maintained.
(xi) All employees shall be made aware of the location of fire extinguishers and be trained in its use and operation.
(xii) The fire alarm devices on each floor shall be maintained in good working condition.
(xiii) The signs giving location of pull stations should be properly maintained.
(xiv) The pull stations shall be unobstructed and plainly marked.
(xv) The plan for evacuation of patients shall be prepared and displayed at appropriate places.
(j) Fire Alarm System Sequence of Operation:
(a) Operation of any manual pull station, automatic smoke detector, heat detector, and duct mounted smoke detector or water flow switch shall cause the following actions and indications:
(i) The system common alarm LED on the CPU shall flash. The internal audible device shall sound.
(ii) The 80 character backlit alphanumeric display, shall display the device type, device location, time and date of alarm and a unique custom message.
(iii)Transfer common alarm contacts for sending an alarm signal to an approved central station. (Two dedicated telephone lines, connection and service by owner).
(iv)Activate the fire alarm audio/visual signals throughout the facility.
(v) Shutdown all AHUs over 2000 cfm.
(b) Operation of any operating room ceiling mounted smoke detector or return air duct smoke detector shall cause the following actions and indications:
(i) Return air damper shall transfer to fully close.
(ii) Outside air damper shall transfer to fully open.
(iii)Exhaust damper shall transfer to fully open and activate exhaust fan.
(c) Operation of outside air or supply air duct smoke detector unit shall shut down. Exhaust damper shall remain in full open position or transfer to that position and activate exhaust fan.