Chapter 4General Building Requirements and Services
4.1 General
This part sets out the standard space requirements of various parts of a building (for all types of buildings – low/ high rise).
Table 4.1Occupant Load
Sl.No.
Type of Occupancy
Occupant Load per 100 sq m. of Plinth or Covered Area
1
Residential
8.0
2
Educational
25.0
3
Institutional
6.60
4
Assembly with fixed or loose seats and dance floor without seating facilities including dining rooms
166.666.6
5
Mercantile street floor and sales basement upper sale floor
33.316.6
6
Business and industrial
10.0
7
Storage
3.3
8
Hazardous
10.0
* The occupant load in dormitory portions of homes for the aged, orphanages or mental hospitals etc. where sleeping accommodation is provided shall be calculated at not less than 13.3 persons per 100 sq.m.
** The plinth or covered area shall include, in addition to the main assembly room or space, any occupied connecting room or space in the same storey or in the storeys above or below where entrance is common to such rooms and space and the area available for use by the occupants of the assembly place. No deduction shall be made in the plinth/covered area for corridors, closets and other sub-divisions; that area shall include all space serving the particular assembly occupancy.
4.2 Requirements for Parts of Buildings
4.2.1 Plinth
4.2.1.1 Main Buildings
The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm from the surrounding ground level.
4.2.1.2 Interior Courtyards and Covered Parking
Every interior courtyard shall be raised at least 150 mm above the determining ground level and shall be satisfactorily drained.
4.3Habitable Rooms
4.3.1 Height
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab) provided that the minimum clear headway under any beam shall not be less than 2.4 m. In the case of pitched roof, the average height of rooms shall not be less than 2.75 m. The minimum clear head room under a beam, folded plates or eaves shall be 2.4 m. In the case of air-conditioned rooms, a height of not less than 2.4 m measured from the
surface of the floor to the lowest point of air-conditioning duct or the false ceiling shall be provided.
4.3.1.1 The requirements of clause 4.3.1 apply to residential, business and mercantile buildings. For educational and industrial buildings, the following minimum requirements apply:
Table 4.2Minimum height requirement for educational and industrial buildings
Sl.No
Types of building
Ceiling height
1
Educational Buildings
Ceiling height 3.6 m for all regions; in cold regions, 3 m
2
Industrial Buildings
Ceiling height 3.6 m, except when air-conditioned, 3 m (Factory Act 1948 and Rules therein shall govern such heights, where applicable).
4.3.1.2 Size
The area of habitable room shall not be less than 9 . 5 m 2 , where there is only one room with a minimum width of 2.4 m. Where there are two rooms, one of these shall not be less than 9.5 m2 and the other not less than 7 . 5 m 2 , with a minimum width of 2.1 m.
4.4Kitchen
4.4.1 Height
The height of a kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.75 m, except for the portion to accommodate floor trap of the upper floor.
4.4.2 Size
The area of a kitchen where separate dining area is provided, shall be not less than 5.0 m 2 with a minimum width of 1.8 m. Where there is a separate store, the area of the kitchen may be reduced to 4 . 5 m 2 . A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7 . 5 : m 2 with a minimum width of 2.1 m.
4.4.3 Other Requirements
Every room to be used as kitchen shall have:
a) unless separately provided in a pantry, means for the washing of kitchen utensils which shall lead directly or through a sink to a grated and trapped connection to the waste pipe;
b) an impermeable floor;
c) a flue, if found necessary; and
d) a window or ventilator or opening of size not less than as specified in clause 4.31.1 subject to increase in area of opening in accordance with Note 3.
4.5Bathrooms and Water-Closets
4.5.1 Height
The height of a bathroom or water-closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.1 m.
4.5.2 Size
The area of a bathroom shall not be less than 1 . 8 m 2 with a minimum width of 1.2 m. The floor area of water-closet shall be 1.1 m2 with a minimum width of 0 . 9 m . If bath and water-closet are combined, its floor area shall not be less than 2 . 8 m 2 with a minimum width of 1.2 m.
4.5.3 Other Requirements
Every bathroom or water-closet shall:
a) be so situated that at least one of its walls shall open to external air;
b) not be directly over or under any room other than another water-closet, washing place, bath or terrace, unless it has a water-tight floor;
c) have the platform or seat made of water-tight non-absorbent material;
d) be enclosed by walls or partitions and the surface of every such wall or partition shall be finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room;
e) be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards VERANDAH or any other room; and
f) have a window or ventilator, opening to a shaft or open space, of area not less than 0 . 3 m 2 with side not less than 0.3 m.
4.5.4 No room containing water-closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
4.6 Ledge or Tand/Loft
4.6.1 Height
The minimum head-room of ledge or TAND/loft shall be 2.2 m. The maximum height of loft shall be 1.5 m.
4.6.2 Size
A ledge or TAND/loft in a habitable room shall not cover more than 25 percent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
4.7Mezzanine Floor
4.7.1 Height
It shall have a minimum height of 2.2 m.
4.7.2 Size
The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9 . 5 m 2
The aggregate area of such mezzanine floor in a building shall in no case exceed onethird the plinth area of the building.
4.7.3 Other Requirements
A mezzanine floor may be permitted over a room or a compartment provided:
a) it conform to the standard of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9 . 5 m 2 or more (see 4.31.1);
Page 53
b) it is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
c) such mezzanine floor is not sub-divided into smaller compartments;
d) such mezzanine floor or any part of it shall not be used as a kitchen; and
e) in no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
4.8 Store Room
4.8.1 Height
The height of a store room shall be not less than 2.2 m.
4.8.2 Size
The size of a store room, where provided in a residential building, shall be not less than 3 m2.
4.9 Garage
4.9.1 Height
The height of a garage shall be not less than 2.4 m.
4.9.2 Size
The size of garages shall be as below:
a) Private Garage - 3.0 m × 6.0 m, minimum; and
b) Public Garage - Based on the number of vehicles parked by ECU.(Appendix ‘A-1’)
4.14Boundary Wall
The requirements of the boundary wall shall be as follows:
a) Except with the special permission of the Authority, the maximum height of the compound wall shall be 1.5 m above the centre line of the front street. Compound wall up to 2.4 m height may be permitted if the top 0.9 m is of open type construction of a design to be approved by the Authority.
b) In the case of a corner plot, the height of the boundary wall shall be restricted to 0.75 m for a length of 10 m on the front and side of the inter-sections and the balance height of 0.75 m if required in accordance with (a) may be made up of open type construction (through railings) and of design to be approved by the Authority.
c) However, the provisions of (a) and (b) are not applicable to boundary walls of jails. In industrial buildings, electric sub-stations, transformer stations, institutional buildings like sanitoria, hospitals, industrial buildings like workshops, factories and educational buildings like schools, colleges, including hostels, and other uses of public utility undertakings and strategically sensitive buildings, a height up to 2.4 m may be permitted by the Authority.
4.10Basement
4.10.1 The basement shall not be used for residential purposes.
4.10.2 The construction of the basement shall be allowed by the Authority in accordance with the land use and other provisions specified under the Development Control Rules.
4.10.3 The basement to be constructed within the building envelope and subject to maximum coverage on floor 1 (entrance floor) may be put to only the following uses:
a) Storage of household or other goods of ordinarily non-combustible material;
b) Strong rooms, bank cellars, etc;
c) Air-conditioning equipment and other machines used for services and utilities of the building; and
d) Parking spaces.
4.10.4 The basement shall have the following requirements:
a) Every basement shall be in every part at least 2.4 m in height from the floor to the underside of the roof slab or ceiling;
b) Adequate ventilation shall be provided for the basement. The ventilation requirements shall be the same as required by the particular occupancy according to byelaws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems, etc;
c) The minimum height of the ceiling of any basement shall be 0.9m and the maximum, 1.2 m above the average surrounding ground level;
d) Adequate arrangements shall be made such that surface drainage does not enter the basement;
e) The walls and floors of the basement shall be watertight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
f) The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors.
g) Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of (d). The exist requirements in basements shall comply with the provisions of Part 4 ‘Fire and Life Safety
4.11 Chimneys
The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney top shall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
4.12 Parapet
Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
i. The above shall not apply where roof terrace is not accessible by a staircase.
ii. However on terrace floor in the portion where installations like DG Set, Water Tank and other, screening parapet of a suitable height may be constructed to hide such equipment’s etc and there is no need to have uniformly increased the height of the parapet.
4.13 Cabin
The size of cabins shall not be less than 3.0 m2 with a minimum width of 1.0 m. The clear passages within the divided space of any floor shall not be less than 0.75 m and the distance from the farthest space in a cabin to any exit shall not be more than 18.5 m. In case the sub-divided cabin does not derive direct lighting and ventilation from any open spaces/ mechanical means, the maximum height of the cabin shall be 2.2 m.
4.15Septic Tanks
Where a septic tank is used for sewage disposal, the location, design and construction of septic tank shall conform to requirements of Part 9 ‘Plumbing Services, Section 1 Water Supply, Drainage and Sanitation (Including Solid Waste Management)’ of NBC, 2005.
4.15.1 Location of the Septic Tanks and Subsurface Absorption Systems
A sub-soil dispersion system shall not be closer than 18 m from any source of drinking water, such as well, to mitigate the possibility of bacterial pollution of subsurface water. It shall also be as far removed from the nearest habitable building as economically feasible but not closer than 6 m, to avoid damage to the structures.
4.15.2 Requirements
a) Dimensions of septic tanks - Septic tanks shall have a minimum width of 750 mm, a minimum depth of 1 m below the water level and a minimum liquid capacity of 1 m3. The length of tanks shall be 2 to 4 times the width;
b) Septic tanks may be constructed of brickwork, stone masonry, concrete or other suitable materials as approved by the Authority;
c) Under no circumstances shall effluent from a septic tank be allowed into an open channel drain or body of water without adequate treatment;
d) The minimum nominal diameter of the pipe shall be 100 mm. Further, at junctions of pipes in manholes, direction of flow from a branch connection shall not make an angle exceeding 45° with the direction of flow in the main pipe;
e) The gradients of land drains, under-drainage as well as the bottom of dispersion trenches and soakways shall be between 1:300 and 1:400;
f) Every septic tank shall be provided with ventilating pipe of at least 50 mm diameter. The top of the pipe shall be provided with a suitable cage of mosquitoproof wire mesh. The ventilating pipe shall extend to a height which would cause no smell nuisance to any building in the area. Generally, the ventilating pipe may extend to a height of about 2 m, when the septic tank is at least 15 m away from the nearest building and to a height of 2 m above the top of the building when it is located closer than 15 m;
When the disposal of septic tank effluent is to a seepage pit, the seepage pit may be of any suitable shape with the least cross sectional dimension of 0.90 m and not less than 1.00 m in depth below the invert level of the inlet pipe. The pit may be lined with stone, brick or concrete blocks with dry open joints which should be backed with at least 75 mm of clean coarse aggregate. The lining above the inlet level should be finished with mortar. In the case of pits of large dimensions, the top portion may be narrowed to reduce the size of the RCC cover slabs. Where no lining is used, specially near trees, the entire pit should be filled with loose stones. A masonry ring may be constructed at the top of the pit to prevent damage by flooding of the pit by surface runoff. The inlet pipe may be taken down a depth of 0.90 m from the top as an anti-mosquito measure; and
h) When the disposal of the septic tank effluent is to a dispersion trench, the dispersion trench shall be 0.50 m to 1.00 m deep and 0.30 m to 1.00 m wide excavated to a slight gradient and shall be provided with 150 mm to 250 mm of washed gravel or crushed stones. Open jointed pipes placed inside the trench shall be made of unglazed earthenware clay or concrete and shall have a minimum internal diameter of 75 mm to 100 mm. Each dispersion trench shall not be longer than 30 m and trenches shall not be placed closer than 1.8 m.
4.15.3 Office-cum-Letter Box Room
In the case of multi-storeyed multi-family dwelling apartments constructed by existing and proposed Cooperative Housing Societies or Apartment Owners Associations, limited companies and proposed societies, an office-cum-letter box room of dimension 3.6 m × 3 m shall be provided on the ground floor. In case the number of flats is more than 20, the maximum size of the office-cum-letter box room shall be 20 m2.
4.15.4 Business Buildings
Provision shall be made for letter boxes on the entrance floor as per the requirements of the postal department.
4.17Staircase/Exit Requirements
4.17.1 The minimum clear width, minimum tread width and maximum riser of staircases for buildings shall be as given as below (see also Part 4 ‘Fire and Life Safety of NBC 2005).
4.17.2 Minimum width
The minimum width of staircase shall be as follows:
A
Residential buildings (dwellings) NOTE - For row housing with 2 storeys, the min. width of shall be 0.75
1.0 m
B
Residential hotel buildings
1.5 m
C
Assembly buildings like auditoria, theatres and cinemas
2.0 m
D
Educational building
1.5 m
E
Institutional buildings
2.0 m
F
All other buildings
1.5 m
4.17.3 Minimum tread
The minimum width of tread without nosing shall be 250 mm for residential buildings. The minimum width of tread for other buildings shall be 300 mm.
4.17.4 Maximum riser
4.17.4.1 The maximum height of riser shall be 190 mm for residential buildings and 150 mm for other buildings and these shall be limited to 12 per flight.
4.17.4.2 The minimum head-room in a passage under the landing of a staircase shall be 2.2 m. The minimum clear head-room in any staircase shall be 2.2 m.
4.17.5 Exit Requirements
All aspects of exit requirements for corridors, doors, stair cases, ramps, etc in respect of widths, travel distance shall be as per Part 4 ‘Fire and Life Safety’ of NBC,2005.
4.16Meter Rooms
For all buildings above 15 m in height and in special occupancies, like educational, assembly, institutional, industrial, storage, hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500 m2 on each floor, provision shall be made for an independent and ventilated meter (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric supply from the licensee’s service and alternative supply cables. The door/doors provided for the service room shall have fire resistance of not less than two hours.
4.21Group housing
a) Building requirement in respect of dwelling units upto 45 sq.mt. in size will correspond to Table 3.3 and as applicable to plots upto 50 sq m.
b) Building requirement in respect of dwelling units above 45 sq m. may be referred from the Table 3.3 applicable to above 50 sq m. plot size.
c) Projection into Open Spaces without counting towards FAR.
i) All open spaces provided either in interior or exterior shall be kept free from any erections thereon and shall open to the sky. Nothing except cornice, chhajja or weather shade (not more than 0.75 m. wide) shall overhang or project over the said open space so as to reduce the width to less than minimum required.
Note: Such projections shall not be allowed at height less than 2.2 m. from the corresponding finished floor level:
ii) One canopy per block on the ground floor not exceeding 4.5 m. in length and 2.4 m. in width
iii) Balcony at roof slab level of 1.2 m. width and area not exceeding 3.5 sq m. per bedroom but not exceeding 3 in number per flat.
iv) Balcony having entrance from the toilet/bathroom and width as 1.2 m. for drying clothes.
4.22 Non-residential buildings
The minimum area for office room/shop or any other space to be used as workspace shall not be less than 6.0 sq m. with a minimum width of 2.1 m.
4.25Provision of exterior open spaces and height limitation around the building
4.25.1 The open spaces / setbacks covered area, FAR shall be as per Master Plan/Zonal Plan requirements as given in the development controls of Master Plan. (Building Bye Laws-Annexure VI)/ NBC, 2005
4.25.2 Every room that is intended for human habitation shall abut on an interior or exterior open space or on to a verandah open to such interior or exterior open space.
4.25.3 In case of High rise the exterior open spaces around a building as in Building Bye Laws No. shall be of green or hard surface capable of taking load of fire engine weighing up to 45 tonnes.
4.25.4 In case, kitchen and toilets do not abut either interior or exterior open spaces, mechanical ventilation would be accepted.
4.25.5 Up to 25% of the total setback area can be sunk for light, ventilation and access to basement, provided fire tender movement is not hindered.
4.18Roofs
4.18.1 The roof of a building shall be so designed and constructed as to effectively drain water by means of sufficient rain-water pipes of adequate size, wherever required, so arranged, jointed and fixed as to ensure that the rain-water is carried away from the building without causing dampness in any part of the walls, roof or foundations of the building or an adjacent building.
4.18.1.1 The Authority may require rain-water pipes to be connected to a drain or sewer to a covered channel formed beneath the public footpath to connect the rainwater rainwater pipe to the road gutter or in any other approved manner.
4.18.1.2 Rain-water pipes shall be affixed to the outside of the external walls of the building or in recesses or chases cut or formed in such external walls or in such other manner as may be approved by the Authority.
4.18.1.3 It is desirable to conserve rain water using suitable rain water harvesting techniques including by roof water collection. In this context, reference may be made to Part 9 ‘Plumbing Services, Section 1 Water Supply, Drainage and Sanitation (Including Solid Waste Management)’ of NBC, 2005.
4.19 Special Requirements of Low Income Housing
Special requirements of low income housing shall be as given in relevant Section of this Model Building Bye-Law. For detailed information in this regard, reference may be made to the accepted standards.
4.20 Special Requirements for Cluster Planning for Housing
Special requirements for cluster planning for housing shall be as given in relevant sections of the Model Building Bye-Law.
4.24Means of access (including Fire Safety- Ref Chapter 11)
4.24.1 No Building shall be erected as to deprive any other building of its means of access.
4.24.2 Every person who erects a building shall not at any time erect or cause or permit to erect or re- erect any building, which in any way encroaches upon or diminishes the area set apart as means of access.
4.24.3 For buildings identified in clause 11.1 the following provisions of means of access shall be applicable.
a) The width of the main street on which buildings abut shall not be less than 12.0 m.
b) If there are any bends or curves in the approach road, sufficient width shall be permitted at the curve to enable the fire tenders to turn, the turning circle shall be at least of 9.0 m. radius.
c) The approach to the building and open spaces on its all sides (see Building Bye-Laws 4.8 and 4.9) upto 6.0 m. width and the layout for the same shall be done in consultation with the Chief Fire Officer and the same shall be of hard surface capable of taking the weight of fire tender, weighing upto 22 tones for low rise building and 45 tones for building 15 m., and above in height. The said open space shall be kept free of obstructions and shall be motorable.
d) Main entrance to the premises shall be of adequate width to allow easy access to the fire tender and in no case it shall measure less than 5 m. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for movement of the fire service vehicles. Ifarchway is provided over the main entrance, the height of the archway shall not be of height less than 5.0 m.
e) For multi-storeyed group housing schemes on one plot, the approach road shall be 20.0 m. or as per Master Plan/Development Plan provisions and between individual buildings, there shall be 6.0 m. space around.
f) In case of basement extending beyond the building line, it shall be capable of taking load of 45 tones for a building of height 15.0 m. and above and 22 tones for building height less than 15.0 m.
g) The external window shall not be blocked by louvres etc. In such case provisions shall be made so that one can enter the building to be rescued through the window by using hydraulic platform etc.
4.24.4 Number and size of Exits 4
The requisite number and size of various exits shall be provided, based on the occupants in each room and floor based on the occupant load, capacity of exits, travel distance and height of buildings as per provisions of Section 4.2 to 4.12 & 6.1 to 6.9 of Part 4- Fire and Life Safety, NBC 2005.
4 Types of Exits
a) Exits shall be either horizontal or vertical type. An exit may be doorway, corridor and passage to an internal staircase or external staircase, ramp to a verandah and/or terraces that have access to the street or to roof of a building. An exit may also include horizontal exit leading to an adjoining building at the same level.
b) Lifts escalators and revolving doors shall not be considered as exits.
At least one primary entrance to each building shall be usable by individuals in wheelchairs and shall be indicated by a sign
At least one entrance usable by individuals in wheelchairs shall be on a level that would make the elevators accessible.
4.24.5 Arrangement of Exits
a) Exits shall be so located so that the travel distance on the floor shall not exceed 22.50 m. for residential, educational, institutional and hazardous occupancies and 30.0 m. for assembly, business, mercantile, industrial and storage occupancies. Whenever more than one exit is required for a floor of a building they shall be placed as remote from each other as possible. All the exits shall be accessible from the entire floor area at all floor levels.
b) The travel distance to an exit from the remote point shall not exceed half the distance as stated above except in the case of institutional occupancy in which case it shall not exceed 6.0 m.
4.24.6 Capacity of Exits
The capacity of exits (staircase, ramps and doorways) indicating the number of persons could be safety evacuated through a unit exit width of 50 cm shall be as given below:
Table 4.3Occupants per unit Exit width
Sl. No.
Group of Occupancy
Number of Occupants
Stairways
Ramps
Doors
1
Residential
25
50
75
2
Educational
25
50
75
3
Institutional
25
50
75
4
Assembly
40
50
60
5
Business
50
60
75
6
Mercantile
50
60
75
7
Industrial
50
60
75
8
Storage
50
60
75
9
Hazardous
25
30
40
4.24.7 Minimum Width Provisions for Passageway/Corridors
The following minimum width provisions shall be made for each passage way/corridor.
a) Residential buildings, dwelling unit type. 1.00 m.
b) Residential buildings, e.g., hostels, etc. 1.25 m.
c) Assembly buildings like auditorium theatres and cinemas. 2.00 m.
d) All other buildings including hotels. 1.50 m.
e) Hospital, Nursing Homes, etc. 2.40 m.
4.24.7.1 Ramps
a. The ramp to basement and parking floors shall not be less than 7.2m wide for two way traffic and 4 m wide for one way traffic, provided with Gradient of 1:10 for cars and 1:15 for heavy vehicles. At curved portions of the ramp or for circular ramps the slope should not be more than 1:12.
b. Ramps may also be provided in the setbacks which can be sloped considering unhindered movement of fire engine and in no case the gradient shall be less than 1:10.
c. All structural design/safety aspects as per latest BIS Codes & NBC, 2005 shall be complied along with consideration of weight of Fire Engine & its maneuverings.
d. The minimum width of the ramps in hospitals shall be 2.4 m for stretcher and not for vehicular movement
e. In this case Handrails shall be provided on both sides of the ramp.
f. Ramps shall lead directly to outside open space at ground level or courtyards or safe place
Ramps with Gradients
a. Where ramps with gradients are necessary or desired, they shall conform to the following requirements.
b. A ramp when provided should not have a slope greater than 1 in 20 or maximum of 1 in 12 for short distance up to 9 000 mm.
c. A ramp shall have handrails on at least one side, and preferably two sides, that are 900 mm high, measured from the surface of the ramp, that are smooth, and that extend 300 mm beyond the top and bottom of the ramp. Where major traffic is predominantly children, the handrails should be placed 760 mm high.
Notes
i. Where handrails are specified to be of heights other than 80 cm, it is recommended that two sets of handrails be installed to serve all people. Where major traffic is predominantly children, particularly physically disabled children, extra care should be exercised in the placement of handrails, in accordance with the nature of the facility and the age group or groups being serviced
ii. Care should be taken that the extension of the handrails is not in itself a hazard. Extension up to 300 mm may be made on the side of a continuing wall.
iii. A ramp shall have a surface that is non-slip surface and if length is 3 500 mm, the minimum widthshall be 1 500 mm. greatly assists the challenged persons with semi-ambulatory and ambulatory disabilities. Non-slip surfaces are provided by many finishes and materials. The surfaces of the concrete ramps can be made nonskid by brooming the surface or by finishing with an indenting roller.
4.23Other general requirements
4.23.1 Swimming Pool
Definition: A constructed pool or a tank indoor or outside the building, used for the purpose of swimming, bathing, aquatic sports or games, training, treatment (Therapy) or recreation, meant exclusively for human being, having a depth of water not less than that 60 cm. and the surface area exceeding 23.25 sq m. both for the use of public or the institution concerned.
i) “Capacity of Pools in Relation to Bathers”: The maximum number of persons in bathing attire within the pool enclosures of the bathing area shall not exceed one person per 20 sq ft. (1.86 sq m.) of pool i.e. the area of the water surface.
“Hand Rail”: A side handrail extending up above and returning to the horizontal surface of the pool deck curb or coping shall be provided at each side of each ladder.
“Depth Markers”: Depth of water shall be clearly marked at or above the water surface on the vertical pool wall and on the edge of the deck or walk-way next to the pool, at maximum points and at the points of break between the deep and shallow portions and at intermediate increments of depth, spaced at not more than 2.5” (7.62 cm) intervals. Depth markers, contrasting with background shall be on both sides of the pool.
“Lighting and Wiring”: Where submarine lightning is used, not less than 0.5 watts shall be employed per sq. ft. of pool area.
“Area Lightning”: Where submarine lightning is employed, area lightning shall be provided for the deck areas and directed towards the deck areas and away from the pool surface so far as practicable, in a total capacity of not less than 0.6 watt per sq. ft of deck area.
Where submarine lighting is not provided and night swimming is not permitted combined pool lightning shall be provided in an amount of not less than 2 watts per sq. ft. of total area. All submarine lightning shall be individually earthed and must be water tight and damp proof.
“Over Head Wiring”: No electrical wiring for electrical or power shall be permitted to pass over within 20 feet of the pool enclosure.
“Shallow Minimum Depth”: Every swimming pool shall have a minimum depth in the shallow area of the main swimming area of not less then 0.9 mt. (3 feet), but not more than 1.07mt. (3'-6”) from the overflow level to the floor
“Shallow Areas”: In a swimming pool with a diving area, the shallow area of the pool shall be defined as the portion between the shallow end and the break point between the shallow area and the diving area. The slope of the floor shall be uniform from the break point between the diving area and the shallow portion to the outside edge of the shallow portion and shall not be greater than 1 in 2 m.
“Vertical Wall Depth”: The pool walls shall be vertical at all points for a depth of not less than 2 ft 6" (0. 76 m.)
iv. A ramp shall have a level platform at the top which is at least 1 800 mm long, if a door swings out onto the platform or toward the ramp. This platform shall extend at least 300 mm beyond each side of the doorway.
v. Each ramp shall have at least 1 800 mm of straight clearance at the bottom.
vi. Ramps shall have level platforms at 10 m to 12 m intervals for purposes of rest and safety, and shall have platforms minimum 1.5 m length wherever they turn.
vii. For visually impaired people, ramps may be colour contrasted with landing.
viii. To minimize rise to wheelchair users, ramps should be equipped with herbs approximately 50 mm high at exposed sides.
4.24.7.2 Doorways
a. Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
b. No exit doorways shall be less than 1m in width except assembly and institutional buildings where Doorway shall not be less than 2 m.
c. Exit doorways shall open outwards, that is away from the room but shall not obstruct the travel along any exit. No door when opened shall reduce the required width of stairway or landing to less than 0.90 m Overhead or sliding door shall not be installed.
Note: In the case of buildings where there is a central corridor, the doors of rooms shall open inwards to permit smooth flow of traffic in the corridor
d. Exit door shall not open immediately upon a flight of stairs. A landing equal to at least, the width of the door shall be provided in the stairway at each doorway. Level of landings shall be the same as that of the floor, which it serves.
e. Exit doorways shall be openable from the side, which they serve without the use of a key.
f. Revolving doors shall not to be provided as means of fire exit.
g. Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.