4.10.1 The basement shall not be used for residential purposes.
4.10.2 The construction of the basement shall be allowed by the Authority in accordance with the land use and other provisions specified under the Development Control Rules.
4.10.3 The basement to be constructed within the building envelope and subject to maximum coverage on floor 1 (entrance floor) may be put to only the following uses:
a) Storage of household or other goods of ordinarily non-combustible material;
b) Strong rooms, bank cellars, etc;
c) Air-conditioning equipment and other machines used for services and utilities of the building; and
d) Parking spaces.
4.10.4 The basement shall have the following requirements:
a) Every basement shall be in every part at least 2.4 m in height from the floor to the underside of the roof slab or ceiling;
b) Adequate ventilation shall be provided for the basement. The ventilation requirements shall be the same as required by the particular occupancy according to byelaws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems, etc;
c) The minimum height of the ceiling of any basement shall be 0.9m and the maximum, 1.2 m above the average surrounding ground level;
d) Adequate arrangements shall be made such that surface drainage does not enter the basement;
e) The walls and floors of the basement shall be watertight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
f) The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors.
g) Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of (d). The exist requirements in basements shall comply with the provisions of Part 4 ‘Fire and Life Safety
4.11 Chimneys
The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney top shall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
4.12 Parapet
Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
i. The above shall not apply where roof terrace is not accessible by a staircase.
ii. However on terrace floor in the portion where installations like DG Set, Water Tank and other, screening parapet of a suitable height may be constructed to hide such equipment’s etc and there is no need to have uniformly increased the height of the parapet.
4.13 Cabin
The size of cabins shall not be less than 3.0 m2 with a minimum width of 1.0 m. The clear passages within the divided space of any floor shall not be less than 0.75 m and the distance from the farthest space in a cabin to any exit shall not be more than 18.5 m. In case the sub-divided cabin does not derive direct lighting and ventilation from any open spaces/ mechanical means, the maximum height of the cabin shall be 2.2 m.