(1) Plinth area shall be considered from Plot boundary Center line sharing the approach road. The plinth of the main building shall be sited with respect to surrounding ground level for proper drainage of the plot. The height of the plinth shall not be less than 450 mm and more than 1.5 meters in the case of independent building not sharing party wall. If the party wall is shared the plinth level shall be the same as already laid for the party wall.
(2) The plinth of courtyard shall be at least 150 mm above the level of the street from where entry to plot has been taken and shall be satisfactorily drained.
(3) In no case, any part of the ramp/steps connecting building plinth to street/road shall lie on street/road and obstruct traffic movement.
8.6 Minimum area, size, height, light and ventilation required for different components of Residential buildings
(1) Minimum area of a habitable room, kitchen and water closet shall be followed in accordance with tablet given as under:
| Sr.No. | Room type | Minimum area (in square meters) | Minimum width (in meters) | Minimum clear Height (in meters) | Light and Ventilation (area of openable windows, ventilators) |
|---|---|---|---|---|---|
| 1 | Habitable room | 9.5 | 2.4 | 2.40 | Not less than 1/8th of the total floor area of the room. |
| 2 | Kitchen | 5.5 | 1.8 | 2.40 | Not less than 1/8th of the total floor area of the room. |
| 3 | Pantry | 3.00 | 1.40 | 2.10 | Not applicable |
| 4 | Bathroom | 1.80 | 1.20 | 2.10 | Not applicable |
| 5 | Water Closet | 1.1 | 0.90 | 2.10 | Not applicable |
| 6 | Combined Bath and Water Closet | 2.8 | 1.2 | 2.10 | 0.3 square meters on wall not less than 0.3 meters wide. |
| 7 | Store | No restriction | No restriction | 2.10 | Not applicable |
| 8 | Garage | 14.85 | 2.75 x 5.40 | 2.40 | Not applicable |
| 9 | Doorways Habitable room | Not applicable | 0.90 | 1.95 | Not applicable |
| 10 | Doorways for kitchen, bath, W.C | Not applicable | 0.75 | 2.10 | Not applicable |
(2) Habitable room Size and height
(i) in case of Group Housing scheme, the dwelling unit having more than one room may have one of the rooms with a clear floor area not less than 7.5 sq. meters with one side not less than 2.4 meters,
(ii) in case of air-conditioned rooms, the height shall not be less than 2.4 meters measured from the surface of the floor to the lowest point of air conditioning duct or false ceiling; and,
(iii) all doors and windows shall open directly or through a verandah or to a permanent open space or an open space abutting the building not less than 1.8 meters in width.
(3) Bathroom and Water Closet (W.C.)
(i) Every bathroom and water closet shall:
(a) preferably be so situated that at least one of its walls shall have opening for circulation of external air, with provision of exhaust fan, and,
(b) toilet be provided with impervious floor covering sloping towards the drain with a suitable gradient.
(ii) where the water-closet in a building is not connected to exterior, it shall be ventilated by mechanical means or through a vertical shaft open to sky of a minimum size stated in the Model Building Bye Laws 2016, for ventilation to toilet, bath, and water closet, and shall be counted in covered area.
(iii) no room containing water-closet shall be used for any other purposes except as lavatory and no such room shall open directly into any kitchen or cooking space by a door/ window or another opening, and every room containing water- closet shall have a door completely closing its entrance.
(iv) soil or ventilating pipes shall not be allowed on the exterior face of any building, provided these shall either be embedded in the walls or pipe ducts to be provided to accommodate them.
(v) Security rooms each measuring maximum area of 3.0 square meters is permitted only at the entry-exit gates of premises.
(vi) All commercial buildings should necessarily design a public toilet with winter friendly technology and universal design. Buildings with plinth areas more than 75 sqm shall be accessible from outside of main building block.