(1) Every building intended to be used as multiple residential building or commercial or educational and institutional or industrial building shall be provided with required number of staircases (accessible from a maximum distance of 30 meters (45 meters, if building has automatic sprinklers for firefighting) from any part of the building, extending from ground floor level to the highest floor, having following specifications:
| Sr.No. | Type of building | Type of building | Minimum permissible clear width of staircase (in meters) | Minimum permissible width of tread (in meters) | Maximum permissible height of riser (in meters) |
| 1 | Residential | Plots up to 15 meters height | 0.9 | 0.25(Without) | 0.19 |
| 1 | Residential | Plots above 15 meters height | 1.2 | 0.25(Without) nosing) | 0.19 |
| 2 | Commercial | Plots up to 50 square meters area | 0.9 | 0.25(Without nosing) | 0.15 |
| 2 | Commercial | Plots above 50 square meters area | 1.2 | 0.30(Without nosing) | 0.15 |
| 3 | Assembly building | Assembly building | 2.0 | 0.30(Without nosing) | 0.15 |
| 4 | Educational building | Educational building | 1.5 | 0.30(Without nosing) | 0.15 |
| 5 | Institutional building | Institutional building | 2.0 | 0.30(Without nosing) | 0.15 |
| 6 | Inland Container Depot & Custom bounded area | Inland Container Depot & Custom bounded area | 1.5 | 0.30(Without nosing) | 0.15 |
| 7 | Industrial building; | Industrial building; | 1.5 | 0.30(Without nosing) | 0.15 |
| 8 | Any other buildings | Any other buildings | 1.5 | 0.30(Without nosing) | 0.15 |
(2) minimum headroom in a passage under the landing of a staircase and the minimum clear headroom in any staircase shall be 2.1 meters.
(3) maximum numbers of risers in single flight are limited to 14 nos.
(4) if a service or a spiral staircase is provided, its width shall not be less than 1.0 meter and its average tread width shall not be less than mention in table of sub-Code (1).
(5) notwithstanding anything contained in sub-Code (1), the staircases in the private portion of a public building and industrial building, not open to the general public, may be of the sizes mentioned for residential building.