The following Rules shall be applicable for all Special Buildings in addition to the other Performance Rules.
12.1 Visibility
Auditoriums or cinema halls shall provide minimum visibility requirements as per following specifications:
1 The seat nearest to the screen shall not be nearer than the effective width of the normal picture (ratio 1:1.33). This distance shall be 3/4 in case of cinema scope and other wide angles techniques and one half in case of 70 mm presentations.
2 The elevation of the balcony seats shall be such that line of sight is not inclined more than 30° to the horizontal.
3 The seats should preferably be staggered sideways in relation to those in front, so that a spectator in any row is not looking directly over the head of the person immediately in front of him.
4 The position and height of the screen shall be regulated in such a way that the maximum angle of the line of vision from the front seat to the top of the screen shall not exceed 50°.
12.2 Mixed Occupancy
1 Places of assembly in buildings of other occupancy, such as all rooms in hotels, restaurants, stores and assembly rooms in schools, shall be so located, separated, or protected as to avoid any undue danger to the occupants of the place of assembly from a fire / smoke originating in the other occupancy.
2 Every place of assembly, every tier of balcony, and every individual room used as a place of assembly shall have exits sufficient to provide for the total capacity therein as required such that door width for assembly building shall not be less than 2000 mm for every 600 persons.
3 Every place of assembly shall have at least four separate exits as remote from each other as practicable.
4 At least one row of seating area shall be made accessible by ramps or elevators for disabled visitors.
5 Clear aisles not less than 1.2 m in width shall be formed at right angles to the line of seating in such number and manner that no seat shall be more than seven seats away from an aisle. Rows of seats opening to an aisle at one end only shall have not more than seven seats. Under the condition, where all these aisles do not directly meet the exit doors, cross‐ aisles shall be provided parallel to the line of seating so as provide direct access to the exit, provided that not less than one cross aisle for every 10 rows shall be required. The width of cross‐aisles shall be minimum of 1 m. Steps shall not be placed in aisles to overcome differences in levels unless gradient exceeds 1 in 10.
6 The fascia of boxes, balconies and galleries shall have substantial railings not less than 1000 mm high above the floor. The railings at the end of aisles extending to the fascia shall be not less than 1000 mm high for the width of the aisle or 1100 mm high at the foot of steps.
7 Cross aisles except where the back of seats on the front of the aisle project 600 mm or more above the floor of the aisle shall be provided with railings not less than 900 mm high.
8 No turnstiles or other devices to restrict the movement of persons shall be installed in any place of assembly in such a manner as to interfere in any way with the required exit facilities.
9 In theatres and similar places of public assembly where persons are admitted to the building at a time when seats are not available for them are allowed to wait in lobby or similar place until seats are available, such use of lobby or similar space shall not encroach upon the required clear width of exits. Such waiting shall be restricted to areas separated from the exit ways by substantial permanent partition or fixed rigid railing not less than 105 cm high. Exits shall be
Page No 115
16
18
19
20
21
17
provided for such waiting spaces on the basis of 1 person for each 0.3 sq m of waiting space / area. Such exits shall be in addition to exits specified for the main auditorium area and shall conform in construction and arrangement to the general Rules of exits given above.
No display or exhibit shall be so installed or operated as to interfere in any way with access to any required exit, or with any required exit sign. All displays or exhibits of combustible material or construction and all booths and temporary constructions in connection therewith shall be so limited in combustibility or protected so as to avoid any undue hazard of fire which might endanger occupants before they have opportunity to use the available exits, as determined by the Competent Authority.
Places of assembly in buildings of other occupancy may use exits common to the place of assembly and the other occupancy, provided the assembly area and the order occupancy are considered separately, and each has exits sufficient to meet the requirements of the code.
Exits shall be sufficient for simultaneous occupancy of both the place of assembly and other parts of the building, unless authority determines that the simultaneous occupancy will not occur.
13 At least half the required means of exit shall lead directly outdoors or through exit ways completely separated from exits serving other parts of the building.
The decoration of place of assembly shall be of non‐flammable materials. Fabrics and papers used for such purpose shall be treated with an effective flame-retardant material. Stage settings made of combustible materials shall likewise be treated with fire retardant materials of class 1 flame spread.
15 Seats in places of public assembly, accommodating more than 300 persons, shall be securely fastened to the floor except as permitted in (16) below. All seats in balconies and galleries shall be securely fastened to the floor, except that in nailed‐in enclosures like boxes with level floors and having not more than 14 seats, the seats need not be fastened. Tapestry of the seats shall be fire resistant.
Chairs not secured to the floor may be permitted in restaurants, night clubs and other occupancies where fastening of seats to the floor may not be practicable, provided that in the area used for seating, excluding dance floor, stage etc, there shall be not more than one seat for each 1.4 sq m of floor area and adequate aisles to reach exits shall be maintained at all times.
Seats without dividing arms shall have their capacity determined be allowing 45 cm per person.
The spacing of rows of seats from back shall neither be less than 85 cm nor less than 70 cm plus the sum of the thickness of the back and the inclination of the back. There shall be a space of at least 350 mm between the back of one seat and the front of the seat immediately behind it as measured between plumb lines.
Rooms containing high‐pressure boilers, refrigerating machinery other than domestic refrigerator type, or other service equipment subject to possible explosion shall not be located directly under or adjacent to required exits. All such rooms shall be effectively cut off from other parts of the building and provided with adequate vents to the outer air.
All rooms or areas used for storage of any combustible material or equipment, or for painting, refinishing, repair or similar purposes shall be effectively cut off from assembly areas or protected with a standard system of automatic sprinklers. They shall be located away from staircases.
Every stage equipped with fly galleries, grid irons and rigging for movable theatre type scenery shall have a system of automatic sprinklers over and under such stage areas or spaces and auxiliary spaces, such as dressing rooms, storerooms, and workshops. The proscenium opening shall be provided with a fire‐resisting curtain, capable of withstanding a lateral pressure of 4 KN/ sq m over the entire area. The curtain shall have an emergency closing device capable of causing the curtain to close without the use of power and when so closed, it shall be reasonably tight against the passage of smoke.
22 The stage roof of every theatre using movable scenery or having a motion picture screen of highly combustible construction shall have a ventilator or ventilators in or above it, openable from the stage floor by hand and also opening by fusible links or some other approved automatic heat/ smoke actuated device, to give a free opening equal to at least one‐eighth the area of the floor of the stage.
Page No 116
23 The proscenium wall of every theatre using movable scenery or decorations shall have exclusive of the proscenium opening, not more than two openings entering the stage, each not to exceed 2 sq m and fitted with self-closing fire-resistant doors.
24 Automatic smoke vents actuated by smoke detectors shall be installed above the auditorium or theatres, including motion picture houses, with capacity of 8 air change per hour.
12.3 Public Offices / Hospital Buildings
Page No 117
These shall conform to 6.3 Part IV National Building Code, amended from time to time and particular attention is drawn to the following:
In building or sections occupied by bedridden patients where the floor area is over 280 sq m, facilities shall be provided to move patients in hospital beds to the other side of a smoke barrier from any part of such building or section not directly served by approved horizontal exits or exits from first floor (floor 2) of a building to the outside.
- Not less than two exits of one or more of the following types shall be provided for every floor, of every building or section:
a Doors leading directly outside the building.
b Stairways
c Ramps
d Horizontal Exits and
e Fire Escape Staircase
3 All required exits as per Table in Rule No10.1.12 of corridor width.
4 No building constructed in whole or in part of combustible materials shall be used to confine inmates in cells or sleeping quarters unless automatic sprinkler protection is provided.
12.4 Public Safety
Closed Circuit Television (CCTV) Network shall be installed in public areas of assembly buildings and other places of entertainment as per protocols laid down by the Competent Authority.