7.1 General
All electric and renewable energy equipment and systems shall comply with the mandatory requirements of §7.2.
7.2 Mandatory Requirements
7.2.1 Transformers
7.2.1.1 Maximum Allowable Power Transformer Losses
Power transformers of the proper ratings and design must be selected to satisfy the minimum acceptable efficiency at 50% and full load rating.
Permissible total loss values shall not exceed
a) 5% of the maximum total loss values mentioned in IS 1180 for oil type transformers in voltage class above 11 kV but not more than 22 kV
b) 7.5% of the maximum total loss values mentioned in above IS 1180 for oil type transformers in voltage class above 22 kV and up to and including 33 kV
c) values listed in Table 7.1 for dry type transformers
| Rating (kVA) | Impedance(%) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) |
| Rating (kVA) | Impedance(%) | ECBC Building | ECBC Building | ECBC+ Building | ECBC+ Building | SuperECBC Building | SuperECBC Building |
| Rating (kVA) | Impedance(%) | 50 % Load | 100% Load | 50 % Load | 100% Load | 50 % Load | 100% Load |
| 16 | 4.5 | 150 | 480 | 135 | 440 | 120 | 400 |
| 25 | 4.5 | 210 | 695 | 190 | 635 | 175 | 595 |
| 63 | 4.5 | 380 | 1,250 | 340 | 1,140 | 300 | 1,050 |
| 100 | 4.5 | 520 | 1,800 | 475 | 1,650 | 435 | 1,500 |
| 160 | 4.5 | 770 | 2,200 | 670 | 1,950 | 570 | 1,700 |
| 200 | 4.5 | 890 | 2,700 | 780 | 2,300 | 670 | 2,100 |
| 250 | 4.5 | 1,050 | 3,150 | 980 | 2,930 | 920 | 2,700 |
| 315 | 4.5 | 1,100 | 3,275 | 1,025 | 3,100 | 955 | 2,750 |
| 400 | 4.5 | 1,300 | 3,875 | 1,225 | 3,450 | 1,150 | 3,330 |
| 500 | 4.5 | 1,600 | 4,750 | 1,510 | 4,300 | 1,430 | 4,100 |
| 630 | 4.5 | 2,000 | 5,855 | 1,860 | 5,300 | 1,745 | 4,850 |
| 1000 | 5 | 3,000 | 9,000 | 2,790 | 7,700 | 2,620 | 7,000 |
| 1250 | 5 | 3,600 | 10,750 | 3,300 | 9,200 | 3,220 | 8,400 |
| 1600 | 6.25 | 4,500 | 13,500 | 4,200 | 11,800 | 3,970 | 11,300 |
| 2000 | 6.25 | 5,400 | 17,000 | 5,050 | 15,000 | 4,790 | 14,100 |
| 2500 | 6.25 | 6,500 | 20,000 | 6,150 | 18,500 | 5,900 | 17,500 |
| Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. | Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. | Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. | Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. | Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. | Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. | Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. | Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS. An increase of 7% on total for thermal class H is allowed. |
| Rating (kVA) | Impedance(%) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) | Max. Total Loss (W) |
| Rating (kVA) | Impedance(%) | ECBC Building | ECBC Building | ECBC+ Building | ECBC+ Building | SuperECBC Building | SuperECBC Building |
| Rating (kVA) | Impedance(%) | 50 % Load | 100% Load | 50 % Load | 100% Load | 50 % Load | 100% Load |
| 16 | 4.5 | 150 | 480 | 135 | 440 | 120 | 400 |
| 25 | 4.5 | 210 | 695 | 190 | 635 | 175 | 595 |
| 63 | 4.5 | 380 | 1250 | 340 | 1140 | 300 | 1050 |
| 100 | 4.5 | 520 | 1800 | 475 | 1650 | 435 | 1500 |
| 160 | 4.5 | 770 | 2200 | 670 | 1950 | 570 | 1700 |
| 200 | 4.5 | 890 | 2700 | 780 | 2300 | 670 | 2100 |
| 250 | 4.5 | 1050 | 3150 | 980 | 2930 | 920 | 2700 |
| 315 | 4.5 | 1100 | 3275 | 1025 | 3100 | 955 | 2750 |
| 400 | 4.5 | 1300 | 3875 | 1225 | 3450 | 1150 | 3330 |
| 500 | 4.5 | 1600 | 4750 | 1510 | 4300 | 1430 | 4100 |
| 630 | 4.5 | 2000 | 5855 | 1860 | 5300 | 1745 | 4850 |
| 1000 | 5 | 3000 | 9000 | 2790 | 7700 | 2620 | 7000 |
| 1250 | 5 | 3600 | 10750 | 3300 | 9200 | 3220 |
7.2.1.2 Measurement and Reporting of Transformer Losses
All measurement of losses shall be carried out by using calibrated digital meters of class 0.5 or better accuracy and certified by the manufacturer. All transformers of capacity of 500 kVA and above would be equipped with additional metering class current transformers (CTs) and potential transformers (PTs) additional to requirements of Utilities so that periodic loss monitoring study may be carried out.
7.2.1.3 Voltage Drop
Voltage drop for feeders shall not exceed 2% at design load. Voltage drop for branch circuit shall not exceed 3% at design load.
7.2.2 Energy Efficient Motors
Motors shall comply with the following:
a) Three phase induction motors shall conform to Indian Standard (IS) 12615 and shall fulfil the following efficiency requirements:
i. ECBC Buildings shall have motors of IE 2 (high efficiency) class or a higher class
ii. ECBC+ Buildings shall have IE 3 (premium efficiency) class motors or higher class
iii. SuperECBC Buildings shall have IE 4 (super premium efficiency) class motors
b) All permanently wired polyphase motors of 0.375 kW or more serving the building and expected to operate more than 1,500 hours per year and all permanently wired polyphase motors of 50kW or more serving the building and expected to operate more than 500 hour per year, shall have a minimum acceptable nominal full load motor efficiency not less than levels specified in the latest version of IS 12615.
c) Motors of horsepower differing from those listed in the table shall have efficiency greater than that of the next listed kW motor.
d) Motor horsepower ratings shall not exceed 20% of the calculated maximum load being served.
e) Motor nameplates shall list the nominal full-load motor efficiencies and the full-load power factor.
f) Motor users should insist on proper rewinding practices for any rewound motors. If the proper rewinding practices cannot be assured, the damaged motor should be replaced with a new, efficient one rather than suffer the significant efficiency penalty associated with typical rewind practices. Rewinding practices from BEE guideline for energy efficient motors shall be followed.
g) Certificates shall be obtained and kept on record indicating the motor efficiency. Whenever a motor is rewound, appropriate measures shall be taken so that the core characteristics of the motor is not lost due to thermal and mechanical stress during removal of damaged parts. After rewinding, a new efficiency test shall be performed and a similar record shall be maintained.
7.2.3 Diesel Generator (DG) Sets
BEE star rated DG sets shall be used in all compliant buildings. DG sets in buildings greater than 20,000 m2 BUA shall have:
a) minimum 3 stars rating in ECBC Buildings
b) minimum 4 stars rating in ECBC+ Buildings
c) minimum 5 stars rating in SuperECBC Buildings
7.2.4 Check-Metering and Monitoring
a) Services exceeding 1000 kVA shall have permanently installed electrical metering to record demand (kVA), energy (kWh), and total power factor. The metering shall also display current (in each phase and the neutral), voltage (between phases and between each phase and neutral), and total harmonic distortion (THD) as a percentage of total current.
b) Services not exceeding 1000 kVA but over 65 kVA shall have permanently installed electric metering to record demand (kW), energy (kWh), and total power factor (or kVARh).
c) Services not exceeding 65 kVA shall have permanently installed electrical metering to record energy (kWh).
d) In case of tenant based building, metering should be provided at a location from where each tenant could attach the services.
| 120 kVA to 250 kVA | Greater than 250 kVA | |
| Minimum requirement for metering of electrical load | ||
| Energy kWh | Required | Required |
| Demand kVA | Required | Required |
| Total power factor | Required | Required |
| Minimum requirement for separation of electrical load | ||
| HVAC system and components | Required | Required |
| Interior and Exterior Lighting * | Not required | Required |
| Domestic hot water | Not required | Required |
| Plug loads | Not required | Required |
| Renewable power source | Required | Required |
| Mandatory requirement for building type over the requirement stated above | ||
| Shopping Complex | Façade lighting | Elevator, escalators, moving walks |
| Business | Data centers | |
| Hospitality | Commercial kitchens | |
| * Hotel guestrooms and hospital in patient areas are exempted from the lighting sub-metering requirements. | ||
7.2.5 Power Factor Correction
All 3 phase shall maintain their power factor at the point of connection as follows:
a) 0.97 for ECBC Building
b) 0.98 for ECBC+ building
c) 0.99 for SuperECBC building
7.2.6 Power Distribution Systems
The power cabling shall be sized so that the distribution losses do not exceed
a) 3% of the total power usage in ECBC Buildings
b) 2% of the total power usage in ECBC+ Buildings
c) 1% of total power usage in SuperECBC Buildings
Record of design calculation for the losses shall be maintained. Load calculation shall be calculated up to the panel level.
7.2.7 Uninterruptible Power Supply (UPS)
In all buildings, UPS shall meet or exceed the energy efficiency requirements listed in Table 7-4. Any Standards and Labeling program by BEE shall take precedence over requirements listed in this section.
| UPS Size | Energy Efficiency Requirements at 100% Load |
|---|---|
| kVA< 20 | 90.2% |
| 20<=kVA <= 100 | 91.9% |
| kVA > 100 | 93.8% |
7.2.8 Renewable Energy Systems
All buildings shall have provisions for installation of renewable energy systems in the future on rooftops or the site.
7.2.8.1 Renewable Energy Generating Zone (REGZ)
a) A dedicated REGZ equivalent to at least 25 % of roof area or area required for generation of energy equivalent to 1% of total peak demand or connected load of the building, whichever is less, shall be provided in all buildings.
b) The REGZ shall be free of any obstructions within its boundaries and from shadows cast by objects adjacent to the zone
c) ECBC+ and SuperECBC building shall fulfil the additional requirements listed in Table 7-5 and Table 7-6 respectively.
Exception to § 7.2.8.1: Projects with solar hot water and/ or solar power generation systems.
| Building Type | Minimum Electricity to be Generated in REGZ |
|---|---|
| All building types except below | Minimum 2% of total electrical load |
| Star Hotel > 20,000 m² Resort > 12,500 m<sup>2</sup> University > 20,000 m² Business > 20,000 m² | Minimum 3% of total electricity load |
| Building Type | Minimum Electricity to be Generated in REGZ |
|---|---|
| All Building types except below | Minimum 4% of total electrical load |
| Star Hotel > 20,000 m² Resort > 12,500 m<sup>2</sup> University > 20,000 m² Business > 20,000 m² | Minimum 6% of total electrical load |
7.2.8.2 Main Electrical Service Panel
Minimum rating shall be displayed on the main electrical service panel. Space shall be reserved for the installation of a double pole circuit breaker for a future solar electric installation.
7.2.8.3 Demarcation on Documents
The following shall be indicated in design and construction documents:
a) Location for inverters and metering equipment,
b) Pathway for routing of conduit from the REGZ to the point of interconnection with the electrical service,
c) Routing of plumbing from the REGZ to the water-heating system and,