5.2.2.1 Chillers
a) Chillers shall meet or exceed the minimum efficiency requirements presented in Table 5-1 through Table 5-2 under ANSI/ AHRI 550/ 590 conditions.
b) The application of air-cooled chiller is allowed in all buildings with cooling load less than 530 kW. For buildings with cooling load equal to or greater than 530 kW, the number of air-cooled chiller shall be restricted to 33% of the total installed chilled water capacity unless the authority having jurisdiction mandates the application of air cooled chillers.
c) Minimum efficiency requirements under BEE Standards and Labeling Program for chillers shall take precedence over the minimum requirements presented in Table 5-1 through Table 5-2.
d) To show compliance to ECBC, minimum requirement of both COP and IPLV requirement of ECBC Building shall be met. To show compliance with ECBC+ Building and SuperECBC Building, minimum requirement of either COP or IPLV of respective efficiency level shall be met.
| Chiller Capacity (kWr) | ECBC Building | ECBC+ Building | SuperECBC Building | |||
| COP | IPLV | COP | IPLV | COP | IPLV | |
| <260 | 4.7 | 5.8 | 5.2 | 6.9 | 5.8 | 7.1 |
| ≥260 & <530 | 4.9 | 5.9 | 5.8 | 7.1 | 6.0 | 7.9 |
| ≥530 & <1,050 | 5.4 | 6.5 | 5.8 | 7.5 | 6.3 | 8.4 |
| ≥1,050 & <1,580 | 5.8 | 6.8 | 6.2 | 8.1 | 6.5 | 8.8 |
| ≥1,580 | 6.3 | 7.0 | 6.5 | 8.9 | 6.7 | 9.1 |
| Chiller Capacity (kWr) | ECBC Building | ECBC+ Building | SuperECBC Building | ||
| COP | IPLV | COP | IPLV | COP / IPLV | |
| <260 | 2.8 | 3.5 | 3.0 | 4.0 | NA |
| ≥260 | 3.0 | 3.7 | 3.2 | 5.0 | NA |
5.2.2.2 Unitary, Split, Packaged Air-Conditioners
Unitary air-conditioners shall meet or exceed the efficiency requirements given in Table 5-3 through Table 5-5. Window and split air conditioners shall be certified under BEE’s Star Labeling Program. EER shall be as per IS 8148 for all unitary, split, packaged air conditioners greater than 10 kWr.
| Cooling Capacity (kWr) | Water Cooled | Air Cooled |
|---|---|---|
| ≤ 10.5 | NA | BEE 3 Star |
| > 10.5 | 3.3 EER | 2.8 EER |
| Cooling Capacity (kWr) | Water Cooled | Air Cooled |
|---|---|---|
| ≤ 10.5 | NA | BEE 4 Star |
| > 10.5 | 3.7 EER | 3.2 EER |
| Cooling Capacity (kWr) | Water Cooled | Air Cooled |
|---|---|---|
| ≤ 10.5 | NA | BEE 5 Star |
| >10.5 | 3.9 EER | 3.4 EER |
5.2.2.3 Variable Refrigerant Flow
Variable Refrigerant Flow (VRF) systems shall meet or exceed the efficiency requirements specified in Table 5-6 as per the ANSI/ AHRI Standard 1230 while the Indian Standard on VRF is being developed. BEE Standards and Labeling requirements for VRF shall take precedence over the current minimum requirement.
| For Heating or cooling or both | |||
| Type | Size category (kWr) | EER | IEER |
| VRF Air Conditioners, Air cooled | < 40 | 3.28 | 4.36 |
| >= 40 and < 70 | 3.26 | 4.34 | |
| >= 70 | 3.02 | 4.07 | |
* The revised EER and IEER values as per Indian Standard for VRF corresponding to values in this table will supersede as and when the revised standards are published.
5.2.2.4 Air Conditioning and Condensing Units Serving Computer Rooms
Air conditioning and condensing units serving computer rooms shall meet or exceed the energy efficiency requirements listed in Table 5-7.
| Equipment type | Net Sensible Cooling Capacity a | Minimum SCOP-127 b | |
| Downflow | Upflow | ||
| All types of computer room ACs Air/ Water/ Glycol | All capacity | 2.5 | 2.5 |
| a. Net Sensible cooling capacity = Total gross cooling capacity -latent cooling capacity -Fan power b. Sensible Coefficient of Performance (SCOP-127): A ratio calculated by dividing the net sensible cooling capacity in watts by the total power input in watts (excluding re-heater and dehumidifier) at conditions defined in ASHRAE Standard 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners) | |||