5.2.1 Ventilation
a) All habitable spaces shall be ventilated with outdoor air in accordance with the requirements of §5.2.1 and guidelines specified in the National Building Code 2016 (Part 8: Building Services, Section 1: Lighting and Natural Ventilation, Subsection 5: Ventilation).
b) Ventilated spaces shall be provided with outdoor air using one of the following:
i. Natural ventilation
ii. Mechanical ventilation
iii. Mixed mode ventilation
5.2.1.1 Natural Ventilation Design Requirements
Naturally ventilated buildings or spaces in a mixed-mode ventilated buildings shall:
a) Comply with guidelines provided for natural ventilation in NBC.
b) Have minimum BEE 3-star rated ceiling fans, if provided with ceiling fans.
c) Have exhaust fans complying with minimum efficiency requirements of fans in §5.3, if provided.
5.2.1.2 Mechanical Ventilation Air Quantity Design Requirements
Buildings that are ventilated using a mechanical ventilation system or spaces in mixed-mode ventilated buildings that are ventilated with a mechanical system, either completely or in conjunction with natural ventilation systems, shall:
a) Install mechanical systems that provide outdoor air change rate as per NBC.
b) Have a ventilation system controlled by CO sensors for basement carpark spaces with total car park space greater than or equal to 600 m2.
Note 5-1 Adaptive Thermal Comfort

Human body has the ability to adapt to environmental conditions and become accustomed to them over time. People accustomed to the variability of environmental parameters in non-air-conditioned buildings can live and work through a larger temperature range without experiencing thermal discomfort. This logic informs the
adaptive thermal comfort model for buildings. Adaptive comfort models offer an opportunity to reduce energy use as buildings can be operated at more moderate temperatures. Energy used to maintain stringent comfort conditions through mechanical equipment can thus be avoided. Operative temperatures for the model can be calculated using the formulae below.
Naturally Ventilated Buildings
Indoor Operative Temperature = (0.54 x outdoor temperature) + 12.83
Where, indoor operative temperature (°C) is neutral temperature, & outdoor temperature is the 30-day outdoor running mean air temperature (°C).
The 90 % acceptability range for the India specific adaptive models for naturally ventilated buildings is ± 2.38 °C.
For example, Indoor Operative Temperature for a naturally ventilated building in Delhi (0.54 × 33.0) + 12.83 = 30.68°C
Mixed Mode Buildings
Indoor Operative Temperature = (0.28 x outdoor temperature) + 17.87
Where indoor operative temperature (°C) is neutral temperature & outdoor temperature is the 30-day outdoor running mean air temperature (°C).
The 90% acceptability range for the India specific adaptive models for mixed-mode buildings is ± 3.46°C.
For example, Indoor Operative Temperature for a mixed mode building in Delhi = (0.28 x 33.0) + 17.87 = 27.1 °C
Air Conditioned Buildings
Indoor Operative Temperature = (0.078 x outdoor temperature) + 23.25
Where indoor operative temperature (°C) is neutral temperature & outdoor temperature is the 30-day outdoor running mean air temperature (°C).
The 90% acceptability range for the adaptive models for conditioned buildings is ±1.5°C.
For example, Indoor Operative Temperature for an air-conditioned building in Delhi = (0.078 x 33.0) + 23.25
5.2.1.3 Demand Control Ventilation
Mechanical ventilation systems shall have demand control ventilation if they provide outdoor air greater than 1,500 liters per second, to a space greater than 50 m2, with occupant density exceeding 40 people per 100 m2 of the space, and are served by one or more of the following systems:
a) An air side economizer
b) Automatic outdoor modulating control of the outdoor air damper
Exceptions to § 5.2.1.3: Following shall be exempt from installing demand control ventilation systems:
a) Classrooms in Schools, call centers category under Business
b) Spaces that have processes or operations that generate dust, fumes, mists, vapors, or gases and are provided with exhaust ventilation, such as indoor operation of internal combustion engines or areas designated for unvented food service preparation, or beauty salons
c) Systems with exhaust air energy recovering system