To comply with the Code, buildings shall meet the requirements of §5.2.3.1 through §5.2.3.5.
5.2.3.1 Timeclock
Mechanical cooling and heating systems in Universities and Training Institutions of all sizes and all Shopping Complexes with built up area greater than 20,000 m2 shall be controlled by timeclocks that:
a) Can start and stop the system under different schedules for three different day-types per week,
b) Are capable of retaining programming and time setting during loss of power for a period of at least 10 hours, and
c) Include an accessible manual override that allows temporary operation of the system for up to 2 hours.
Exceptions to §5.2.3.1:
a) Cooling systems less than 17.5 kWr
b) Heating systems less than 5.0 kWr
c) Unitary systems of all capacities
5.2.3.2 Temperature Controls
Mechanical heating and cooling equipment in all buildings shall be installed with controls to manage the temperature inside the conditioned zones. Each floor or a building block shall be installed with at least one control to manage the temperature. These controls should meet the following requirements:
a) Where a unit provides both heating and cooling, controls shall be capable of providing a temperature dead band of 3 . 0 ° C within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
b) Where separate heating and cooling equipment serve the same temperature zone, temperature controls shall be interlocked to prevent simultaneous heating and cooling.
c) Separate thermostat control shall be installed in each
i. guest room of Resort and Star Hotel,
ii. room less than 30 m2 in Business,
iii. air-conditioned class room, lecture room, and computer room of Educational,
iv. in-patient and out-patient room of Healthcare
5.2.3.3 Occupancy Controls
Occupancy controls shall be installed to de-energize or to throttle to minimum the ventilation and/or air conditioning systems when there are no occupants in:
a) Each guest room in a Resort and Star Hotel
b) Each public toilet in a Star Hotel or Business with built up area more than 2 0 , 0 0 0 m 2
c) Each conference and meeting room in a Star Hotel or Business
d) Each room of size more than 3 0 m 2 in Educational buildings
5.2.3.4 Fan Controls
Cooling towers in buildings with built up area greater than 2 0 , 0 0 0 m 2 , , shall have fan controls based on wet bulb logic, with either:
a) Two speed motors, pony motors, or variable speed drives controlling the fans, or
b) Controls capable of reducing the fan speed to at least two third of installed fan power
5.2.3.5 Dampers
All air supply and exhaust equipment, having a Variable Frequency Drive (VFD), shall have dampers that automatically close upon:
a) Fan shutdown, or,
b) When spaces served are not in use
c) Backdraft gravity damper is acceptable in the system with design outdoor air of the system is less than 150 liters per second in all climatic zones except cold climate, provided backdraft dampers for ventilation air intakes are protected from direct exposure to wind.
d) Dampers are not required in ventilation or exhaust systems serving naturally conditioned spaces.
e) Dampers are not required in exhaust systems serving kitchen exhaust hoods.