6.2.1 Lighting Control
6.2.1.1 Automatic Lighting Shutoff
a) 90% of interior lighting fittings in building or space of building larger than 3 0 0 m 2 shall be equipped with automatic control device.
b) Additionally, occupancy sensors shall be provided in
i. All building types greater than 2 0 , 0 0 0 m 2 B U A , in
a. All habitable spaces less than 3 0 m 2 , , enclosed by walls or ceiling height partitions.
b. All storage or utility spaces more than 1 5 m 2 in all building types with BUA greater than 2 0 , 0 0 0 m 2
c. Public toilets more than 2 5 ~ m 2 , controlling at least 80 % of lighting fitted in the toilet. The lighting fixtures, not controlled by automatic lighting shutoff, shall be uniformly spread in the area.
ii. In corridors of all Hospitality greater than 2 0 , 0 0 0 m 2 B U A , controlling minimum 70% and maximum 80% of lighting fitted in the public corridor. The lighting fixtures, not controlled by automatic lighting shut off, shall be uniformly spread in the area.
iii. In all Business and all conference or meeting rooms.
c) Automatic control device shall function on either:
i. A scheduled basis at specific programmed times. An independent program schedule shall be provided for areas of no more than 2,500 m2 and not more than one floor, or,
ii. Occupancy sensors that shall turn off the lighting fixtures within 15 minutes of an occupant leaving the space. Light fixtures controlled by occupancy sensors shall have
a wall-mounted, manual switch capable of turning off lights when the space is occupied.
Exception to § 6.2.1.1: Lighting systems designed for emergency and firefighting purposes.
6.2.1.2 Space Control
Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall
a) control a maximum of 250 m2 for a space less than or equal to 1,000 m2, and a maximum of 1,000 m2 for a space greater than 1,000 m2.
b) have the capability to override the shutoff control required in § 6.2.1.1 for no more than 2 hours, and
c) be readily accessible and located so the occupants can see the control.
Exception to § 6.2.1.2 (c): The required control device may be remotely installed if required for reasons of safety or security. A remotely located device shall have a pilot light indicator as part of or next to the control device and shall be clearly labeled to identify the controlled lighting.
6.2.1.3 Control in Daylight Areas
a) Luminaires, installed within day lighting extent from the window as calculated in § 4.2.3, shall be equipped with either a manual control device to shut off luminaires, installed within day lit area, during potential daylit time of a day or automatic control device that: i. Has a delay of minimum 5 minutes, or,
ii. Can dim or step down to 50% of total power.
b) Overrides to the daylight controls shall not be allowed.
c) For SuperECBC Buildings, Lighting Power Density adjustment factor of 20% shall be allowed to all spaces with more than 70% of their area under daylight controls.
6.2.1.4 Centralized Controls for ECBC+ and SuperECBC Buildings
ECBC+ and SuperECBC building shall have centralized control system for schedule based automatic lighting shutoff switches.
6.2.1.5 Exterior Lighting Control
a) Lighting for all exterior applications not exempted in §6.3.5 shall be controlled by a photo sensor or astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is available or the lighting is not required.
b) Lighting for all exterior applications, of Schools and Business with built up area greater than 20,000 m2, shall have lamp efficacy not less than 80 lumens per watt, 90 lumens per
watt, and 100 lumens per watt, for ECBC, ECBC+, and SuperECBC Buildings respectively, unless the luminaire is controlled by a motion sensor or exempt under §6.1.
c) Facade lighting and façade non-emergency signage of Shopping Complexes shall have separate time switches.
Exemption to §6.2.1.5: Exterior emergency lighting.
6.2.1.6 Additional Control
The following lighting applications shall be equipped with a control device to control such lighting independently of general lighting:
a) Display/ Accent Lighting. Display or accent lighting greater than 3 0 0 m 2 area shall have a separate control device.
b) Hotel Guest Room Lighting. Guest rooms and guest suites in a hotel shall have a master control device at the main room entry that controls all permanently installed luminaires and switched receptacles.
c) Task Lighting. Supplemental task lighting including permanently installed under shelf or under cabinet lighting shall have a control device integral to the luminaires or be controlled by a wall-mounted control device provided the control device complies with §6.2.1.2.
d) Nonvisual Lighting. Lighting for nonvisual applications, such as plant growth and foodwarming, shall be equipped with a separate control device.
e) Demonstration Lighting. Lighting equipment that is for sale or for demonstrations in lighting education shall be equipped with a separate control device accessible only to authorized personnel.
6.2.2 Exit Signs
Internally-illuminated exit signs shall not exceed 5 Watts per face.