4.1 General
The building envelope shall comply with the mandatory provisions of §4.2, and the prescriptive criteria of §4.3.
Roofs shall comply with the maximum assembly U-factors in Table 4-4 through Table 4-6. The roof insulation shall be applied externally as part of structural slab and not as a part of false ceiling.
| Composite | |
|---|---|
| All building types, except below | 0.33 |
| School <10,000 m2 AGA | 0.47 |
| Hospitality > 10,000 m2 AGA | 0.20 |
| Composite | |
|---|---|
| Hospitality Healthcare Assembly | 0.20 |
| Business Educational Shopping Complex | 0.26 |
| Composite | |
|---|---|
| All building types | 0.20 |
All roofs that are not covered by solar photovoltaic, or solar hot water, or any other renewable energy system, or utilities and services that render it unsuitable for the purpose, shall be either cool roofs or vegetated roofs.
a) For qualifying as a cool roof, roofs with slopes less than 20° shall have an initial solar reflectance of no less than 0.60 and an initial emittance no less than 0.90. Solar reflectance shall be determined in accordance with ASTM E903-96 and emittance shall be determined in accordance with ASTM E408-71 (RA 1996).
b) For qualifying as a vegetated roof, roof areas shall be covered by living vegetation
U-factors shall be determined for the overall fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. U-factors for sloped glazing and skylights shall be determined at a slope of 20 degrees above the horizontal. For unrated products, use the default table in Appendix A.
SHGC shall be determined for the overall single or multi glazed fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer.
Exceptions to §4.2.1.2:
a) Shading coefficient (SC) of the center of glass alone multiplied by 0.86 is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration area.
b) Solar heat gain coefficient (SHGC) of the glass alone is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration product.
Visual light transmittance (VLT) shall be determined for the fenestration product in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default table in Appendix A.
U-factors shall be calculated for the opaque construction in accordance with ISO-6946. Testing shall be done in accordance with approved ISO Standard for respective insulation type by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default tables in Appendix A.
Above grade floor areas shall meet or exceed the useful daylight illuminance (UDI) area requirements listed in Table 4-1 for 90% of the potential daylight time in a year. Mixed-use buildings shall show compliance as per the criteria prescribed in §2.5. Compliance shall be demonstrated either through daylighting simulation method in §4.2.3.1 or the manual method in §4.2.3.2. Assembly buildings and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area, are exempted from meeting the requirements listed in Table 4-1.
| Building Category | Percentage of above grade floor area meeting the UDI requirement | ||
| ECBC | ECBC+ | SuperECBC | |
| Business, Educational | 40% | 50% | 60% |
| No Star Hotel Star Hotel Healthcare | 30% | 40% | 50% |
| Resort | 45% | 55% | 65% |
| Shopping Complex | 10% | 15% | 20% |
| Assembly* | Exempted | ||
| *and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area | |||
Only BEE approved software shall be used to demonstrate compliance through the daylighting simulation method. Buildings shall achieve illuminance level between 100 lux and 2,000 lux for the minimum percentage of floor area prescribed in Table 4-1 for at least 90% of the potential daylit time. Illuminance levels for all spaces enclosed by permanent internal partitions (opaque, translucent, or transparent) with height greater or equal to 2 m from the finished floor, shall be measured as follows:
a) Measurements shall be taken at a work plane height of 0.8 m above the finished floor.
b) The period of analysis shall be fixed for 8 hours per day, anytime between 8:00 AM IST to 5:00 PM IST, resulting in 2,920 hours in total for all building types except for Schools. Schools shall be analyzed for 7 hours per day, anytime between 7:00 AM IST to 3:00 PM IST.
c) Available useful daylight across a space shall be measured based on point-by-point grid values. UDI shall be calculated for at least one point for each square meter of floor area.
d) Fenestration shall be modeled with actual visible light transmission (VLT) as per the details provided in the material specification sheet.
e) All surrounding natural or man-made daylight obstructions shall be modeled if the distance between the façade of the building (for which compliance is shown) and surrounding natural or man-made daylight obstructions is less than or equal to twice the height of the man-made or natural sunlight obstructers. If the reflectance of the surfaces is not known, default reflectance of 30% and 0% shall be used for all vertical surfaces of man-made and natural obstructers respectively.
f) Interior surface reflectance shall be modeled based on the actual material specification. If material specification is not available, following default values shall be used:
| Surface Type | Reflectance |
|---|---|
| Wall or Vertical Internal Surfaces | 50% |
| Ceiling | 70% |
| Floor | 20% |
| Furniture (permanent) | 50% |
This method can be used for demonstrating compliance with daylighting requirements without simulation. Daylight extent factors (DEF) mentioned in Table 4-3 shall be used for manually
calculating percentage of above grade floor area meeting the UDI requirement for 90% of the potential daylit time in a year.
| Shading | Latitude | Window Type | VLT < 0.3 | VLT ≥0.3 | ||||||
| North | South | East | West | North | South | East | West | |||
| No shading or PF < 0.4 | ≥15°N | All window types | 2.5 | 2.0 | 0.7 | 0.5 | 2.8 | 2.2 | 1.1 | 0.7 |
| < 15°N | 2.4 | 2.0 | 1.3 | 0.6 | 1.7 | 2.2 | 1.5 | 0.8 | ||
| Shading with PF≥ 0.4 | All latitudes | All window types without light shelf | 2.8 | 2.3 | 1.5 | 1.1 | 3.0 | 2.5 | 1.8 | 1.5 |
| Window with Light shelf | 3.0 | 2.5 | 1.8 | 1.6 | 3.5 | 3.0 | 2.1 | 1.8 | ||
a) To calculate the daylit area:
i. In a direction perpendicular to the fenestration, multiply daylight extent factor (DEF) by the head height of the fenestration or till an opaque partition higher than head height of the fenestration, whichever is less.
ii. In the direction parallel to the fenestration, daylit area extends a horizontal dimension equal to the width of the fenestration plus either 1 meter on each side of the aperture, or the distance to an opaque partition, or one-half the distance to an adjacent fenestration, whichever is least.
iii. For skylights, calculate the horizontal dimension in each direction equal to the top aperture dimension in that direction plus either the floor-to-ceiling height (H) for skylights, or 1.5 H for monitors, or H or 2H for the sawtooth configuration, or the distance to the nearest 1 meter or higher opaque partition, or one-half the distance to an adjacent skylight or vertical glazing, whichever is least.
b) A separate architectural plan shall be prepared with all daylit areas marked on the floor plans. A summary shall be provided showing compliance as per Table 4-1.
Following areas of the building envelope, of all except naturally ventilated buildings or spaces, shall be sealed, caulked, gasketed, or weather-stripped:
a) Joints around fenestration, skylights, and door frames
b) Openings between walls and foundations, and between walls and roof, and wall panels
c) Openings at penetrations of utility services through roofs, walls, and floors
d) Site-built fenestration and doors
e) Building assemblies used as ducts or plenums
f) All other openings in the building envelope
g) Exhaust fans shall be fitted with a sealing device such as a self-closing damper
h) Operable fenestration should be constructed to eliminate air leakages from fenestration frame and shutter frame

Useful Daylight Illuminance (UDI) is defined as the annual occurrence of daylight between 100 lux to 2,000 lux on a work plane. This daylight is most useful to occupants, glare free and when available, eliminates the need for artificial lighting.
A 7,200 m2four story office building in Delhi is trying to achieve ECBC level compliance. Building is oriented along east west axis. It has a rectangular layout (60 m x 30 m). Total built up area is distributed evenly across all floors above grade. VLT of glazing in all orientations is 0.39. Windows have light shelves and external shading devices with P F ≥ 0 . 4 . . Head height of fenestrations is 3.0 m. Length of glazing on the north and south facing façade is 45 meter and on the east façade, 25 meter.
Table 4-1 lists the minimum daylight area requirements for ECBC Buildings. Row 2 of the table specifies that all ECBC Buildings other than resorts and shopping malls and, more than 3 stories above the ground shall have a minimum of 40% of its floor area exposed to daylight in range of 100 – 2,000 lux for at least 90% of the year.
This office building must then have at least 2,880 m2(40% of 7,200 m2) of floor area fulfilling the UDI requirements. Across each floor plate, this area should be then 2.880 / 4 = 720 m ²
Compliance with § 4.2.3 Daylight Requirements can be checked for through two approaches.
If the whole building performance approach is used, compliance for daylighting requirements can be checked by analysing the façade and floor plate design in an analytical software approved by BEE (§ 3.4). The image below, developed through an approved software, specifies the lux levels and time period of a year during which lighting levels would be available. With this information, designers can check if the required minimum area as per § 4.2.3 has the required daylight levels.
Opaque above grade external walls shall comply with the maximum assembly U-factors in Table 4-7 through Table 4-9.
| Composite | |
|---|---|
| All building types, except below | 0.40 |
| No Star Hotel < 10,000 m<sup>2</sup> AGA | 0.63 |
| Business < 10,000 m<sup>2</sup> AGA | 0.63 |
| School <10,000 m<sup>2</sup> AGA | 0.85 |
| Composite | |
|---|---|
| All building types, except below | 0.34 |
| No Star Hotel < 10,000 m<sup>2</sup> AGA | 0.44 |
| Business < 10,000 m<sup>2</sup> AGA | 0.44 |
| School < 10,000 m<sup>2</sup> AGA | 0.63 |
| Composite | |
|---|---|
| All building types | 0.22 |
Exceptions to §4.3.1.1: Opaque external walls of an unconditioned building of No Star Hotel, Healthcare, and School categories in all climatic zones, except for cold climatic zone, shall have a maximum assembly U-factor of 0 . 8 W / m 2 . K.
c) Glazed façades, with non-cardinal orientation, shall be categorized under a particular cardinal direction if its orientation is within ± 45 degrees of that cardinal direction.
d) Any surrounding natural or man-made daylight obstructions shall not be considered in this method.

UDI Analysis with a Daylighting Analysis Software
This approach will be suitable for projects adopting the prescriptive compliance approach. From Table 4-3 determine the daylight extent factor (DEF) for the building. For a building located in Delhi (latitude > 15 degrees), with glazing of V L T ≥ 0 . 3 , shading PF ≥0.4 shading and light shelves in windows, DEFs for windows in North = 3.5, in South = 3.0, in East = 2.1, and in West = 1.8. Head height is 3.0 m. There are no opaque partitions adjacent to the external walls and windows are arranged in a continuous strip.
Area complying with requirements of should be calculated as follows:
In a direction perpendicular to the fenestration, multiply daylight extent factor (DEF) by the head height of the fenestration or till an opaque partition higher than head height of the fenestration, whichever is less. Head height will be considered because there are no opaque partitions near the external walls.
In the direction parallel to the fenestration, daylit area extends a horizontal dimension equal to the width of the fenestration plus either 1 meter on each side of the aperture, or the distance to an opaque partition, or one-half the distance to an adjacent fenestration, whichever is least. In this case, 1 meter on each side of the windows at extreme ends of the window strip in each façade will be considered since there are no opaque partitions adjacent to wall and no opaque area between the windows.
| Orientation | DEF | Window/ Fenestration Width | X m (distance perpendicular to fenestration) | Y m (distance parallel to fenestration) | (X x Y m² ) Above ground area meeting the UDI requirement for 90% of the time in a year) |
| North | 3.5 | 45 m | 3.5x3 = 10.5 m | (45+2) = 47 m | 47 x 10.5 = 493.5 m² |
| South | 3.0 | 45 m | 3.0x3=9.0m | (45+2) = 47 m | 47 x 9 = 423 m² |
| East | 2.1 | 25 m | 2.1x3=6.3m | (25+2)=27 m | 27 x 6.3 = 170 m² |
| West | 1.8 | 0 m (service zone) | 0 | 0 | 0 |
| Total daylight area per floor meeting UDI requirement during 90% of the year | 1086.5 m² | ||||
| Total daylight area in the building meeting UDI requirement during 90% of the year | 1086.5 x 4 = 4346 m² | ||||