4.1 General
The building envelope shall comply with the mandatory provisions of §4.2, and the prescriptive criteria of §4.3.
Roofs shall comply with the maximum assembly U-factors in Table 4-4 through Table 4-6. The roof insulation shall be applied externally as part of structural slab and not as a part of false ceiling.
| Composite | |
|---|---|
| All building types, except below | 0.33 |
| School <10,000 m2 AGA | 0.47 |
| Hospitality > 10,000 m2 AGA | 0.20 |
| Composite | |
|---|---|
| Hospitality Healthcare Assembly | 0.20 |
| Business Educational Shopping Complex | 0.26 |
| Composite | |
|---|---|
| All building types | 0.20 |
All roofs that are not covered by solar photovoltaic, or solar hot water, or any other renewable energy system, or utilities and services that render it unsuitable for the purpose, shall be either cool roofs or vegetated roofs.
a) For qualifying as a cool roof, roofs with slopes less than 20° shall have an initial solar reflectance of no less than 0.60 and an initial emittance no less than 0.90. Solar reflectance shall be determined in accordance with ASTM E903-96 and emittance shall be determined in accordance with ASTM E408-71 (RA 1996).
b) For qualifying as a vegetated roof, roof areas shall be covered by living vegetation
U-factors shall be determined for the overall fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. U-factors for sloped glazing and skylights shall be determined at a slope of 20 degrees above the horizontal. For unrated products, use the default table in Appendix A.
SHGC shall be determined for the overall single or multi glazed fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer.
Exceptions to §4.2.1.2:
a) Shading coefficient (SC) of the center of glass alone multiplied by 0.86 is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration area.
b) Solar heat gain coefficient (SHGC) of the glass alone is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration product.
Visual light transmittance (VLT) shall be determined for the fenestration product in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default table in Appendix A.
U-factors shall be calculated for the opaque construction in accordance with ISO-6946. Testing shall be done in accordance with approved ISO Standard for respective insulation type by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default tables in Appendix A.
Above grade floor areas shall meet or exceed the useful daylight illuminance (UDI) area requirements listed in Table 4-1 for 90% of the potential daylight time in a year. Mixed-use buildings shall show compliance as per the criteria prescribed in §2.5. Compliance shall be demonstrated either through daylighting simulation method in §4.2.3.1 or the manual method in §4.2.3.2. Assembly buildings and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area, are exempted from meeting the requirements listed in Table 4-1.
| Building Category | Percentage of above grade floor area meeting the UDI requirement | ||
| ECBC | ECBC+ | SuperECBC | |
| Business, Educational | 40% | 50% | 60% |
| No Star Hotel Star Hotel Healthcare | 30% | 40% | 50% |
| Resort | 45% | 55% | 65% |
| Shopping Complex | 10% | 15% | 20% |
| Assembly* | Exempted | ||
| *and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area | |||
Only BEE approved software shall be used to demonstrate compliance through the daylighting simulation method. Buildings shall achieve illuminance level between 100 lux and 2,000 lux for the minimum percentage of floor area prescribed in Table 4-1 for at least 90% of the potential daylit time. Illuminance levels for all spaces enclosed by permanent internal partitions (opaque, translucent, or transparent) with height greater or equal to 2 m from the finished floor, shall be measured as follows:
a) Measurements shall be taken at a work plane height of 0.8 m above the finished floor.
b) The period of analysis shall be fixed for 8 hours per day, anytime between 8:00 AM IST to 5:00 PM IST, resulting in 2,920 hours in total for all building types except for Schools. Schools shall be analyzed for 7 hours per day, anytime between 7:00 AM IST to 3:00 PM IST.
c) Available useful daylight across a space shall be measured based on point-by-point grid values. UDI shall be calculated for at least one point for each square meter of floor area.
d) Fenestration shall be modeled with actual visible light transmission (VLT) as per the details provided in the material specification sheet.
e) All surrounding natural or man-made daylight obstructions shall be modeled if the distance between the façade of the building (for which compliance is shown) and surrounding natural or man-made daylight obstructions is less than or equal to twice the height of the man-made or natural sunlight obstructers. If the reflectance of the surfaces is not known, default reflectance of 30% and 0% shall be used for all vertical surfaces of man-made and natural obstructers respectively.
f) Interior surface reflectance shall be modeled based on the actual material specification. If material specification is not available, following default values shall be used:
| Surface Type | Reflectance |
|---|---|
| Wall or Vertical Internal Surfaces | 50% |
| Ceiling | 70% |
| Floor | 20% |
| Furniture (permanent) | 50% |
This method can be used for demonstrating compliance with daylighting requirements without simulation. Daylight extent factors (DEF) mentioned in Table 4-3 shall be used for manually
calculating percentage of above grade floor area meeting the UDI requirement for 90% of the potential daylit time in a year.
| Shading | Latitude | Window Type | VLT < 0.3 | VLT ≥0.3 | ||||||
| North | South | East | West | North | South | East | West | |||
| No shading or PF < 0.4 | ≥15°N | All window types | 2.5 | 2.0 | 0.7 | 0.5 | 2.8 | 2.2 | 1.1 | 0.7 |
| < 15°N | 2.4 | 2.0 | 1.3 | 0.6 | 1.7 | 2.2 | 1.5 | 0.8 | ||
| Shading with PF≥ 0.4 | All latitudes | All window types without light shelf | 2.8 | 2.3 | 1.5 | 1.1 | 3.0 | 2.5 | 1.8 | 1.5 |
| Window with Light shelf | 3.0 | 2.5 | 1.8 | 1.6 | 3.5 | 3.0 | 2.1 | 1.8 | ||
a) To calculate the daylit area:
i. In a direction perpendicular to the fenestration, multiply daylight extent factor (DEF) by the head height of the fenestration or till an opaque partition higher than head height of the fenestration, whichever is less.
ii. In the direction parallel to the fenestration, daylit area extends a horizontal dimension equal to the width of the fenestration plus either 1 meter on each side of the aperture, or the distance to an opaque partition, or one-half the distance to an adjacent fenestration, whichever is least.
iii. For skylights, calculate the horizontal dimension in each direction equal to the top aperture dimension in that direction plus either the floor-to-ceiling height (H) for skylights, or 1.5 H for monitors, or H or 2H for the sawtooth configuration, or the distance to the nearest 1 meter or higher opaque partition, or one-half the distance to an adjacent skylight or vertical glazing, whichever is least.
b) A separate architectural plan shall be prepared with all daylit areas marked on the floor plans. A summary shall be provided showing compliance as per Table 4-1.
Following areas of the building envelope, of all except naturally ventilated buildings or spaces, shall be sealed, caulked, gasketed, or weather-stripped:
a) Joints around fenestration, skylights, and door frames
b) Openings between walls and foundations, and between walls and roof, and wall panels
c) Openings at penetrations of utility services through roofs, walls, and floors
d) Site-built fenestration and doors
e) Building assemblies used as ducts or plenums
f) All other openings in the building envelope
g) Exhaust fans shall be fitted with a sealing device such as a self-closing damper
h) Operable fenestration should be constructed to eliminate air leakages from fenestration frame and shutter frame

Useful Daylight Illuminance (UDI) is defined as the annual occurrence of daylight between 100 lux to 2,000 lux on a work plane. This daylight is most useful to occupants, glare free and when available, eliminates the need for artificial lighting.
A 7,200 m2four story office building in Delhi is trying to achieve ECBC level compliance. Building is oriented along east west axis. It has a rectangular layout (60 m x 30 m). Total built up area is distributed evenly across all floors above grade. VLT of glazing in all orientations is 0.39. Windows have light shelves and external shading devices with P F ≥ 0 . 4 . . Head height of fenestrations is 3.0 m. Length of glazing on the north and south facing façade is 45 meter and on the east façade, 25 meter.
Table 4-1 lists the minimum daylight area requirements for ECBC Buildings. Row 2 of the table specifies that all ECBC Buildings other than resorts and shopping malls and, more than 3 stories above the ground shall have a minimum of 40% of its floor area exposed to daylight in range of 100 – 2,000 lux for at least 90% of the year.
This office building must then have at least 2,880 m2(40% of 7,200 m2) of floor area fulfilling the UDI requirements. Across each floor plate, this area should be then 2.880 / 4 = 720 m ²
Compliance with § 4.2.3 Daylight Requirements can be checked for through two approaches.
If the whole building performance approach is used, compliance for daylighting requirements can be checked by analysing the façade and floor plate design in an analytical software approved by BEE (§ 3.4). The image below, developed through an approved software, specifies the lux levels and time period of a year during which lighting levels would be available. With this information, designers can check if the required minimum area as per § 4.2.3 has the required daylight levels.
Opaque above grade external walls shall comply with the maximum assembly U-factors in Table 4-7 through Table 4-9.
| Composite | |
|---|---|
| All building types, except below | 0.40 |
| No Star Hotel < 10,000 m<sup>2</sup> AGA | 0.63 |
| Business < 10,000 m<sup>2</sup> AGA | 0.63 |
| School <10,000 m<sup>2</sup> AGA | 0.85 |
| Composite | |
|---|---|
| All building types, except below | 0.34 |
| No Star Hotel < 10,000 m<sup>2</sup> AGA | 0.44 |
| Business < 10,000 m<sup>2</sup> AGA | 0.44 |
| School < 10,000 m<sup>2</sup> AGA | 0.63 |
| Composite | |
|---|---|
| All building types | 0.22 |
Exceptions to §4.3.1.1: Opaque external walls of an unconditioned building of No Star Hotel, Healthcare, and School categories in all climatic zones, except for cold climatic zone, shall have a maximum assembly U-factor of 0 . 8 W / m 2 . K.
c) Glazed façades, with non-cardinal orientation, shall be categorized under a particular cardinal direction if its orientation is within ± 45 degrees of that cardinal direction.
d) Any surrounding natural or man-made daylight obstructions shall not be considered in this method.

UDI Analysis with a Daylighting Analysis Software
This approach will be suitable for projects adopting the prescriptive compliance approach. From Table 4-3 determine the daylight extent factor (DEF) for the building. For a building located in Delhi (latitude > 15 degrees), with glazing of V L T ≥ 0 . 3 , shading PF ≥0.4 shading and light shelves in windows, DEFs for windows in North = 3.5, in South = 3.0, in East = 2.1, and in West = 1.8. Head height is 3.0 m. There are no opaque partitions adjacent to the external walls and windows are arranged in a continuous strip.
Area complying with requirements of should be calculated as follows:
In a direction perpendicular to the fenestration, multiply daylight extent factor (DEF) by the head height of the fenestration or till an opaque partition higher than head height of the fenestration, whichever is less. Head height will be considered because there are no opaque partitions near the external walls.
In the direction parallel to the fenestration, daylit area extends a horizontal dimension equal to the width of the fenestration plus either 1 meter on each side of the aperture, or the distance to an opaque partition, or one-half the distance to an adjacent fenestration, whichever is least. In this case, 1 meter on each side of the windows at extreme ends of the window strip in each façade will be considered since there are no opaque partitions adjacent to wall and no opaque area between the windows.
| Orientation | DEF | Window/ Fenestration Width | X m (distance perpendicular to fenestration) | Y m (distance parallel to fenestration) | (X x Y m² ) Above ground area meeting the UDI requirement for 90% of the time in a year) |
| North | 3.5 | 45 m | 3.5x3 = 10.5 m | (45+2) = 47 m | 47 x 10.5 = 493.5 m² |
| South | 3.0 | 45 m | 3.0x3=9.0m | (45+2) = 47 m | 47 x 9 = 423 m² |
| East | 2.1 | 25 m | 2.1x3=6.3m | (25+2)=27 m | 27 x 6.3 = 170 m² |
| West | 1.8 | 0 m (service zone) | 0 | 0 | 0 |
| Total daylight area per floor meeting UDI requirement during 90% of the year | 1086.5 m² | ||||
| Total daylight area in the building meeting UDI requirement during 90% of the year | 1086.5 x 4 = 4346 m² | ||||
For all climatic zones, vertical fenestration compliance requirements for all three incremental energy efficiency levels, i.e. ECBC, ECBC+, and SuperECBC, shall comply with the following:
a) Maximum allowable Window Wall Ratio (WWR) is 40% (applicable to buildings showing compliance using the Prescriptive Method, including Building Envelope Trade-off Method)
b) Minimum allowable Visual Light Transmittance (VLT) is 0.27
c) Assembly U-factor includes both frame and glass area weighted U-factors
d) Assembly SHGC includes both frame and glass area weighted SHGC
Vertical fenestration shall comply with the maximum Solar Heat Gain Coefficient (SHGC) and Ufactor requirements of Table 4-10. Vertical fenestration on non-cardinal direction, shall be
categorized under a particular cardinal direction if its orientation is within ± 2 2 . 5 ° of that cardinal direction.
| Composite | |
| Maximum U-factor (W/m².K) | 3.00 |
| Maximum SHGC Non-North | 0.27 |
| Maximum SHGC North for latitude ≥ 15°N | 0.50 |
| Maximum SHGC North for latitude < 15°N | 0.27 |
| See Appendix A for default values of unrated fenestration. | |
| Composite | |
|---|---|
| Maximum U-factor (W/m².K) | 2.20 |
| Maximum SHGC Non-North | 0.25 |
| Maximum SHGC North for latitude ≥ 15°N | 0.50 |
| Maximum SHGC North for latitude < 15°N | 0.25 |
Exceptions to SHGC requirements in Table 4-10 above:
For fenestration with a permanent external projection, including but not limited to overhangs, side fins, box frame, verandah, balcony, and fixed canopies that provide permanent shading to the fenestration, the equivalent SHGC for the proposed shaded fenestration may be determined as less than or equal to the SHGC requirements of Table 4-10. Equivalent SHGC shall be calculated by following the steps listed below:
a) Projection factor (PF) for the external permanent projection, shall be calculated as per the applicable shading type listed in §8.2. The range of projection factor for using the SEF is 0.25 ≤ PF ≥ 1.0 . Other shading devices shall be modeled through the Whole Building Performance Method in §9.
b) A shaded vertical fenestration on a non-cardinal direction, shall be categorized either under a particular cardinal direction or a primary inter-cardinal direction if its orientation is within the range of ±22.5 degrees of the cardinal or primary inter-cardinal direction.
c) An equivalent SHGC is calculated by dividing the SHGC of the unshaded fenestration product with a Shading Equivalent Factor (SEF). SEF shall be determined for each orientation and shading device type as per Equation 4.1.
d) The maximum allowable SHGC is calculated by multiplying the prescriptive SHGC requirement from Table 4-10 with the SEF.
E q u a t i o n 4. 1 : S E F = (C ₃ × P F ³) + (C ₂ × P F ²) + (C ₁ × P F) + C ₀
Where,
0 . 2 5 ≤ P F ≥ 1 . 0 , and,
C 3 , C 2 , C 1 and C 0 are the coefficient of shading equivalent factor (SEF), listed in Table 4-12 and Table 4-13.
| Overhang + Fin | Overhang | Fin* | ||||||||||
| Coeffi cients | C3 | C2 | C1 | C0 | C3 | C2 | C1 | C0 | C3 | C2 | C1 | C0 |
| North | -0.03 | -0.23 | 1.09 | 0.99 | -0.02 | -0.10 | 0.43 | 0.99 | 0.14 | -0.39 | 0.62 | 0.99 |
| East | 4.49 | -6.35 | 4.70 | 0.52 | -0.05 | 0.42 | 0.66 | 1.02 | 0.12 | -0.35 | 0.57 | 0.99 |
| South | -4.09 | 8.14 | -0.73 | 1.32 | -1.01 | 1.91 | 0.24 | 1.12 | 0.53 | -1.35 | 1.48 | 0.88 |
| West | -1.21 | 3.92 | -0.56 | 1.28 | 1.52 | -2.51 | 2.30 | 0.76 | 0.02 | -0.15 | 0.46 | 1.01 |
| N-E | -0.95 | 1.50 | 0.84 | 1.18 | 2.19 | -3.78 | 2.62 | 0.72 | -1.64 | 3.07 | -1.05 | 1.30 |
| S-E | 2.67 | -4.99 | 5.68 | 0.32 | -0.93 | 1.37 | 0.76 | 0.99 | 0.68 | -1.47 | 1.35 | 0.88 |
| S-W | -0.50 | 1.36 | 2.45 | 0.73 | -3.23 | 5.61 | -1.56 | 1.32 | 1.86 | -3.81 | 2.71 | 0.69 |
| N-W | -6.85 | 11.7 | -3.92 | 1.89 | -0.22 | 0.19 | 0.74 | 1.01 | -2.02 | 2.63 | -0.18 | 1.14 |
* Coefficients are for side fins on both sides of fenestration. For side fins on only one side, divide the coefficients mentioned in this table by 2.
| Overhang + Fin | Overhang | Fin* | ||||||||||
| Coeffi cients | C3 | C2 | C1 | C0 | C3 | C2 | C1 | C0 | C3 | C2 | C1 | C0 |
| North | -0.09 | -0.29 | 1.41 | 1.05 | -0.05 | -0.10 | 0.54 | 1.02 | 0.10 | -0.40 | 0.77 | 1.01 |
| East | -0.55 | 0.89 | 1.28 | 0.97 | -0.62 | 0.88 | 0.51 | 1.02 | 0.15 | -0.41 | 0.56 | 0.98 |
| South | -4.09 | 6.98 | -1.92 | 1.41 | -2.49 | 4.89 | -2.45 | 1.43 | 1.57 | -3.35 | 2.62 | 0.59 |
| West | -1.99 | 3.82 | -0.19 | 1.18 | -0.16 | 0.10 | 0.89 | 0.97 | 0.06 | -0.22 | 0.48 | 0.99 |
| N-E | -1.73 | 3.45 | -0.02 | 1.23 | 0.10 | -0.55 | 1.15 | 0.92 | -0.26 | 0.30 | 0.48 | 1.02 |
| S-E | -2.06 | 4.32 | -0.96 | 1.41 | -0.60 | 0.90 | 0.37 | 0.94 | 0.83 | -1.42 | 1.22 | 0.92 |
| S-W | -2.06 | 4.48 | -1.13 | 1.40 | -0.39 | 0.50 | 0.60 | 0.87 | 1.56 | -3.17 | 2.41 | 0.73 |
| N-W | -0.53 | 0.72 | 1.79 | 0.93 | 0.10 | -0.38 | 0.96 | 0.96 | 0.24 | -0.57 | 0.90 | 0.97 |
* Coefficients are for side fins on both sides of fenestration. For side fins on only one side, divide the coefficients mentioned in this table by 2.
e) The maximum allowable SHGC of glazing shall be 0.9.
f) Any surrounding man-made or natural sunlight obstructers shall be considered as a permanent shading of PF equal to 0.4 if
i. the distance between the vertical fenestration of the building, for which compliance is shown, and surrounding man-made or natural sunlight obstructers is less than or equal to twice the height of the surrounding man-made or natural sunlight obstructers; and
ii. the surrounding man-made or natural sunlight obstructers shade the façade for at least 80% of the total time that the façade is exposed to direct sun light on a summer solstice. Compliance shall be shown using a sun path diagram for summer solstice super-imposed on the building plan.
g) Vertical fenestration, located such that its bottom is more than 2.2 m above the level of the floor, is exempt from the SHGC requirements in Table 4-10, if the following conditions are complied with:
i. The Total Effective Aperture for the elevation is less than 0.25, including all fenestration areas more than 1.0 meter above the floor level; and,
ii. An interior light shelf is provided at the bottom of this fenestration area, with a projection factor on interior side not less than:
a. for E-W, SE, SW, NE, and NW orientations
b. 0.5 for S orientation, and
c. 0.35 for N orientation when latitude is less than 15°N.

Note 4-2 Equivalent SHGC and Projection Factor
A 5,400 m² two story office building in Delhi is trying to achieve ECBC level compliance. It has a rectangular layout (90 m x 30 m) with floor to floor height of 4.0 m and floor area is evenly distributed over the two floors. Windows are either east or west facing and equally distributed on the two floors. The windows are all 1.85 m in length and 2.165 m in height with an overhang of 0.85 m. Cill level is 1.385 m above floor level. The overall glazing area is 384 m². SHGC of the glazing in the East/ West Fenestration is 0.30; area wighted U-Factor is 3.0 W/m².K. VLT of the glazing in all orientation is 0.5. Will the vertical fenestration comply with the ECBC from the prescriptive approach?
Solution:
Table 4-10 and §4.3.3 lists the U-factor, SHGC and VLT requirements for vertical fenestration for ECBC compliant buildings. The building is located in Delhi (Latitude: 28070' N, Longitude: 77010'E), which falls under the composite climate, as per Appendix B, Table 12.1. To fulfil prescriptive requirements, Window to Wall ratio ≤ 40%, SHGC ≤ 0.27, U-factor ≤ 3.0 W/m².K, and VLT ≥ 0.27.
Total Floor area = 5400 m²
Total wall area = 2 x (2x ((90m x 4m) + (30m x 4m))) = 1,920 m²
Total Fenestration area = 384 m²
Window to Wall Ratio (WWR) = 384/1,920 = 20%
As per the calculations, the building has a WWR of 20%, thus complying with the requirement for WWR. The U-factor is also less than 3.0 W/m².K. Similarly the VLT is 0.45, which is greater than the minimum specified value of 0.27, thus complying with the u-factor and VLT requirement.
Equivalent SHGC Calculation
As the windows have an overhang, this case will fall under the exception, and the equivalent SHGC value will be calculated as per Equation 4.1, i.e.
SEF = (C₃ x PF³) + (C₂ x PF²) + (C₁ x PF) + C₀
Where,
PF = Projection Factor, and,
C 0 , C 1 , C 2 , C 3 are coefficients of Shading Equivalent Factors (SEF), listed in Table 4-12 and Table 4-13.
First, calculate Projection Factor (PF) for each orientation. Shading Equivalent Factor coefficients should be from Table 4-12, as the latitude is greater than 1 5 ° N .
SEF East = (C ₃ × PF ³) + (C ₂ × PF ²) + (C ₁ × PF) + C ₀
SEFEast = (-0.05 × (0.345)³) + (0.42 × (0.345)²) + (0.66 × 0.345) + 1.02
SEF East = 1. 2 9 6
Therefore, equivalent SHGCtest=0.3 ÷ 1.296=0.23 Hence the vertical fenestration on the east façade will comply as per prescriptive approach, as the equivalent SHGC is less than maximum allowed.
Similarly, for the west facade:
SEF West = (C ₃ × PF 3) + (C ₂ × PF 2) + (C ₁ × PF) + C ₀
SEFWest = (1.52 × 0.3453) + (-2.51 × 0.3452) + (2.30 × 0.345) + 0.76
SEF West = 1. 3 1 7
Therefore equivalent SHGCWest = 0.3 ÷ 1.317 = 0.23, hence the vertical fenestration on the west façade will comply using the prescriptive approach, as the equivalent SHGC is less than maximum allowed.

Vertical fenestration on all unconditioned buildings or unconditioned spaces may have a maximum U-factor of 5 W / m 2 . .K provided they comply with all conditions mentioned in Table 4-14.
| Building Type | Climate zone | Orientation | Maximum Effective SHGC | Minimum VLT | PF |
| Unconditioned buildings or unconditioned spaces | All except cold | Non-North for all latitudes and North for latitude <15°N | 0.27 | 0.27 | ≥ 0.40 |
| North for latitude >15°N | 0.27 | 0.27 | 0.0 |