4.2.1 Fenestration
4.2.1.1 U-Factor
U-factors shall be determined for the overall fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. U-factors for sloped glazing and skylights shall be determined at a slope of 20 degrees above the horizontal. For unrated products, use the default table in Appendix A.
4.2.1.2 Solar Heat Gain Coefficient
SHGC shall be determined for the overall single or multi glazed fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer.
Exceptions to §4.2.1.2:
a) Shading coefficient (SC) of the center of glass alone multiplied by 0.86 is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration area.
b) Solar heat gain coefficient (SHGC) of the glass alone is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration product.
4.2.1.3 Visual Light Transmittance
Visual light transmittance (VLT) shall be determined for the fenestration product in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default table in Appendix A.
4.2.2 Opaque Construction
U-factors shall be calculated for the opaque construction in accordance with ISO-6946. Testing shall be done in accordance with approved ISO Standard for respective insulation type by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default tables in Appendix A.
4.2.3 Daylighting
Above grade floor areas shall meet or exceed the useful daylight illuminance (UDI) area requirements listed in Table 4-1 for 90% of the potential daylight time in a year. Mixed-use buildings shall show compliance as per the criteria prescribed in §2.5. Compliance shall be demonstrated either through daylighting simulation method in §4.2.3.1 or the manual method in §4.2.3.2. Assembly buildings and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area, are exempted from meeting the requirements listed in Table 4-1.
| Building Category | Percentage of above grade floor area meeting the UDI requirement | ||
| ECBC | ECBC+ | SuperECBC | |
| Business, Educational | 40% | 50% | 60% |
| No Star Hotel Star Hotel Healthcare | 30% | 40% | 50% |
| Resort | 45% | 55% | 65% |
| Shopping Complex | 10% | 15% | 20% |
| Assembly* | Exempted | ||
| *and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area | |||
4.2.3.1 Daylighting Simulation Method
Only BEE approved software shall be used to demonstrate compliance through the daylighting simulation method. Buildings shall achieve illuminance level between 100 lux and 2,000 lux for the minimum percentage of floor area prescribed in Table 4-1 for at least 90% of the potential daylit time. Illuminance levels for all spaces enclosed by permanent internal partitions (opaque, translucent, or transparent) with height greater or equal to 2 m from the finished floor, shall be measured as follows:
a) Measurements shall be taken at a work plane height of 0.8 m above the finished floor.
b) The period of analysis shall be fixed for 8 hours per day, anytime between 8:00 AM IST to 5:00 PM IST, resulting in 2,920 hours in total for all building types except for Schools. Schools shall be analyzed for 7 hours per day, anytime between 7:00 AM IST to 3:00 PM IST.
c) Available useful daylight across a space shall be measured based on point-by-point grid values. UDI shall be calculated for at least one point for each square meter of floor area.
d) Fenestration shall be modeled with actual visible light transmission (VLT) as per the details provided in the material specification sheet.
e) All surrounding natural or man-made daylight obstructions shall be modeled if the distance between the façade of the building (for which compliance is shown) and surrounding natural or man-made daylight obstructions is less than or equal to twice the height of the man-made or natural sunlight obstructers. If the reflectance of the surfaces is not known, default reflectance of 30% and 0% shall be used for all vertical surfaces of man-made and natural obstructers respectively.
f) Interior surface reflectance shall be modeled based on the actual material specification. If material specification is not available, following default values shall be used:
| Surface Type | Reflectance |
|---|---|
| Wall or Vertical Internal Surfaces | 50% |
| Ceiling | 70% |
| Floor | 20% |
| Furniture (permanent) | 50% |
4.2.3.2 Manual Daylighting Compliance Method
This method can be used for demonstrating compliance with daylighting requirements without simulation. Daylight extent factors (DEF) mentioned in Table 4-3 shall be used for manually
calculating percentage of above grade floor area meeting the UDI requirement for 90% of the potential daylit time in a year.
| Shading | Latitude | Window Type | VLT < 0.3 | VLT ≥0.3 | ||||||
| North | South | East | West | North | South | East | West | |||
| No shading or PF < 0.4 | ≥15°N | All window types | 2.5 | 2.0 | 0.7 | 0.5 | 2.8 | 2.2 | 1.1 | 0.7 |
| < 15°N | 2.4 | 2.0 | 1.3 | 0.6 | 1.7 | 2.2 | 1.5 | 0.8 | ||
| Shading with PF≥ 0.4 | All latitudes | All window types without light shelf | 2.8 | 2.3 | 1.5 | 1.1 | 3.0 | 2.5 | 1.8 | 1.5 |
| Window with Light shelf | 3.0 | 2.5 | 1.8 | 1.6 | 3.5 | 3.0 | 2.1 | 1.8 | ||
a) To calculate the daylit area:
i. In a direction perpendicular to the fenestration, multiply daylight extent factor (DEF) by the head height of the fenestration or till an opaque partition higher than head height of the fenestration, whichever is less.
ii. In the direction parallel to the fenestration, daylit area extends a horizontal dimension equal to the width of the fenestration plus either 1 meter on each side of the aperture, or the distance to an opaque partition, or one-half the distance to an adjacent fenestration, whichever is least.
iii. For skylights, calculate the horizontal dimension in each direction equal to the top aperture dimension in that direction plus either the floor-to-ceiling height (H) for skylights, or 1.5 H for monitors, or H or 2H for the sawtooth configuration, or the distance to the nearest 1 meter or higher opaque partition, or one-half the distance to an adjacent skylight or vertical glazing, whichever is least.
b) A separate architectural plan shall be prepared with all daylit areas marked on the floor plans. A summary shall be provided showing compliance as per Table 4-1.
4.2.4 Building Envelope Sealing
Following areas of the building envelope, of all except naturally ventilated buildings or spaces, shall be sealed, caulked, gasketed, or weather-stripped:
a) Joints around fenestration, skylights, and door frames
b) Openings between walls and foundations, and between walls and roof, and wall panels
c) Openings at penetrations of utility services through roofs, walls, and floors
d) Site-built fenestration and doors
e) Building assemblies used as ducts or plenums
f) All other openings in the building envelope
g) Exhaust fans shall be fitted with a sealing device such as a self-closing damper
h) Operable fenestration should be constructed to eliminate air leakages from fenestration frame and shutter frame
Note 4-1 Daylight Extent Factor and Useful Daylight Illuminance

Useful Daylight Illuminance (UDI) is defined as the annual occurrence of daylight between 100 lux to 2,000 lux on a work plane. This daylight is most useful to occupants, glare free and when available, eliminates the need for artificial lighting.
Application of UDI and Daylight Extent Factor
A 7,200 m2four story office building in Delhi is trying to achieve ECBC level compliance. Building is oriented along east west axis. It has a rectangular layout (60 m x 30 m). Total built up area is distributed evenly across all floors above grade. VLT of glazing in all orientations is 0.39. Windows have light shelves and external shading devices with P F ≥ 0 . 4 . . Head height of fenestrations is 3.0 m. Length of glazing on the north and south facing façade is 45 meter and on the east façade, 25 meter.
Table 4-1 lists the minimum daylight area requirements for ECBC Buildings. Row 2 of the table specifies that all ECBC Buildings other than resorts and shopping malls and, more than 3 stories above the ground shall have a minimum of 40% of its floor area exposed to daylight in range of 100 – 2,000 lux for at least 90% of the year.
This office building must then have at least 2,880 m2(40% of 7,200 m2) of floor area fulfilling the UDI requirements. Across each floor plate, this area should be then 2.880 / 4 = 720 m ²
Compliance with § 4.2.3 Daylight Requirements can be checked for through two approaches.
(a) Analysis Through Software
If the whole building performance approach is used, compliance for daylighting requirements can be checked by analysing the façade and floor plate design in an analytical software approved by BEE (§ 3.4). The image below, developed through an approved software, specifies the lux levels and time period of a year during which lighting levels would be available. With this information, designers can check if the required minimum area as per § 4.2.3 has the required daylight levels.
