Table No. AC-1 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time)
| No. | Nature of Construction and Materials | Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (min) of | ||||||||||
| Load Bearing | Non-load bearing | |||||||||||
| 60 | 90 | 120 | 180 | 240 | 60 | 90 | 120 | 180 | 240 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | |
| i) | Reinforced cement concrete1) | 120 | 140 | 160 | 200 | 240 | - | - | - | - | - | |
| (25) )2 | (25) )2 | (25)2) | (25) )2 | (25) )2 | ||||||||
| ii) | Unreinforced cement concrete | 150 | 175 | - | - | - | - | - | - | - | - | |
| iii) | No-fines concrete with: | |||||||||||
| a) | 13 mm cement/sand or gypsum/sand | - | - | - | - | - | 150 | 150 | 150 | 150 | 150 | |
| b) | 13 mm light weight aggregate gypsum plaster | - | - | - | - | - | 150 | 150 | 150 | 150 | 150 | |
| iv) | Bricks of clay: | |||||||||||
| a) | Without finish | 90 | 100 | 100 | 170 | 170 | 75 | 90 | 100 | 170 | 170 | |
| b) | With 13 mm lightweight aggregate plaster | 90 | 90 | 90 | 100 | 100 | 75 | 90 | 90 | 90 | 100 | |
| v) | Bricks of sand lime: | |||||||||||
| a) | Without finish | 90 | 100 | 100 | 190 | 190 | 75 | 90 | 100 | 170 | 170 | |
| b) | With 13 mm lightweight aggregate plaster | 90 | 90 | 90 | 100 | 100 | 75 | 90 | 90 | 90 | 100 | |
| vi) | Blocks of concrete: | |||||||||||
| a) | Without finish | 90 | 100 | 100 | - | 75 | 90 | 100 | 140 | 150 | ||
| b) | With 13 mm lightweight aggregate gypsum plaster | 90 | 90 | 90 | 100 | 100 | 75 | 75 | 75 | 90 | 100 | |
| c) | With 13 mm cement/sand or gypsum/sand | - | - | - | - | 75 | 90 | 90 | 100 | 140 | ||
| vii) | Blocks of lightweight concrete: | |||||||||||
| a) | Without finish | 90 | 100 | 100 | 140 | 150 | 75 | 75 | 75 | 125 | 140 | |
| b) | With 13 mm lightweight aggregate plaster | 90 | 90 | 90 | 100 | 100 | 50 | 63 | 75 | 75 | 75 | |
| c) | With 13 mm cement/sand or gypsum/sand | - | - | - | - | - | 75 | 75 | 75 | 90 | 100 | |
| viii) | Blocks of aerated concrete: | |||||||||||
| a) | Without finish | 90 | 100 | 100 | 140 | 180 | 50 | 63 | 63 | 75 | 100 | |
| b) | With 13 mm lightweight aggregate plaster | 90 | 90 | 100 | 100 | 150 | - | - | - | - | - | |
| Note: 1) Walls containing at least 1 percent of vertical reinforcement 2) Minimum thickness of actual cover to reinforcement | ||||||||||||
Page No 94
Table No. AC-2 : Masonry Walls: Hollow (Required to Resist Fire from One Side at a Time)
| No | Nature of Construction and Materials | Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (min) of | |||||||||||
| Load Bearing | Non-load bearing | ||||||||||||
| 60 | 90 | 120 | 180 | 240 | 30 | 60 | 90 | 120 | 180 | 240 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | |
| i) | Bricks of clay: | ||||||||||||
| a) | Without finish | 170 | 170 | 170 | 200 | 200 | 75 | 75 | 90 | 100 | 170 | 170 | |
| b) | With 13 mm lightweight aggregate plaster | 100 | 100 | 170 | 170 | 170 | 75 | 75 | 90 | 90 | 90 | 100 | |
| ii) | Blocks of concrete: | ||||||||||||
| a) | Without finish | - | - | - | - | - | 90 | 125 | 125 | 140 | 140 | 150 | |
| b) | With 13 mm cement/sand or gypsum/sand | - | - | - | - | - | 90 | 125 | 125 | 140 | 140 | 140 | |
| c) | With 13 mm lightweight aggregate gypsum plaster | 190 | 200 | 200 | - | - | 75 | 90 | 90 | 100 | 125 | 125 | |
| iii) | Blocks of lightweight concrete: | ||||||||||||
| a) | Without finish | 100 | 100 | 100 | - | - | 75 | 90 | 90 | 100 | 140 | 150 | |
| b) | With 13 mm cement/sand or gypsum/sand | - | - | - | - | - | 75 | ||||||
Table No. AC-3: Framed Construction, Load Bearing (Required to Resist Fire from One Side at a Time)
| No. | Nature of Construction and Materials/Timber Studs at Centres not Exceeding 600 mm, Faced on Each Side With | Minimum Thickness (mm) of Protection for a fire Resistance of 60 min | |
| (1) | (2) | (3) | |
| i) | Plasterboard layers with joints staggered, joints in outer layer taped and filled -Total thickness for each face | 25 | |
| ii) | One layer of 12.7 mm plasterboard with a finish of lightweight aggregate | 13 | |
| iii) | Metal lath and plaster, thickness of plaster: | ||
| a) | Sanded gypsum plaster (metal lathing grade) | 22 | |
| b) | Lightweight aggregate gypsum plaster | 13 | |
Page No 95
Table No. AC-4: Framed Construction, Non-Load Bearing (Required to Resist Fire from One Side at a Time)
| No | Stud Construction | Nature of Construction and Materials/Steel or Timber Frame at Centres not Exceeding 600 mm, Facing on Both Sides of | Minimum Thickness (mm) of Protection for a fire Resistance of | |||||
| 30min | 60min | 90min | 120min | |||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | ||
| i) | Dry lining with materials fixed direct to studs, without plaster finish: | |||||||
| a) | One layer of plasterboard with taped and filled joints | Timber or steel | 12.7 | - | - | - | ||
| b) | Two layers of plasterboard with joints staggered, joints in outer layer taped and filled - Total thickness for each face | Timber or steel | 19 | 25 | - | - | ||
| c) | One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber | Timber or steel | 9 | 12 | - | - | ||
| d) | One layer of wood wool slabs Timber 25 | Timber | 25 | - | - | - | ||
| e) | One layer of chipboard or of plywood | Timber or steel | 18 | - | - | - | ||
| ii) | Lining with materials fixed direct to suds, with plaster finish: | |||||||
| a) | Plasterboard of thickness: | |||||||
| 1) | With not less than 5 mm gypsum plaster finish | Timber or steel | 9.5 | - | - | - | ||
| 2) | With not less than 13 mm gypsum plaster finish | Timber or steel | - | 12.7 | - | - | ||
| iii) | Wet finish: | |||||||
| a) | Metal lath and plaster, thickness of plaster: | |||||||
| 1) | Sanded gypsum plaster | Timber or steel | 13 | 13 | 19 | 25 | ||
| 2) | Lightweight aggregate gypsum plaster | Timber or steel | - | 13 | - | - | ||
Table No. AC-5: Framed External Walls Load Bearing (Required to Resist Fire from One Side at a Time)
| No | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a fire Resistance of 60 min |
|---|---|---|
| (1) | (2) | (3) |
| i) | Timber studs at centres not exceeding 600 mm with internal linings of: Plasterboard layers with joints in outer layer taped and filled, total thickness of plasterboard | 31 |
Page No 96
Table No. AC-6: Framed External Walls Non-Load Bearing [Required to Resist Fire from Inside the Building (A)]
| No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a fire Resistance of | |||||||
| 30min | 60min | 90min | 120min | 180min | 240min | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | ||
| i) | Steel frame with an external cladding of non-combustible sheets (excluding sheet steel), with a steel supporting framework and internal lining of: | ||||||||
| a) | Metal lath and plaster, thickness of plaster: | ||||||||
| 1) | Sanded gypsum plaster (metal lathing grade) | 13 | 13 | - | - | - | - | ||
| 2) | Lightweight aggregate gypsum plaster | 10 | 13 | 15 | 15 | 15 | 19 | ||
| b) | Two layer of plasterboard with joints staggered joints in outer layer taped and filled - Total thickness | 21 | 32 | - | - | - | - | ||
| c) | Plasterboard of thickness: | ||||||||
| ii) | 1) | With not less than 5 mm gypsum plaster finish | 12.7 | - | - | - | - | - | |
| 2) | With not less than 13 mm gypsum plaster finish | 9.5 | - | - | - | - | - | ||
| 3) | With not less than 10 mm lightweight aggregate gypsum plaster | 9.5 | - | - | - | - | - | ||
| d) | One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 min thick, or by timber | 9 | 9 | 12 | 12 | 12 | 12 | ||
| iii) | e) | One layer of wood/wool slabs without finish | - | 50 | - | - | - | - | |
| f) | One layer of compressed straw building slabs: | ||||||||
| 1) | Without finish | 50 | - | - | - | - | - | ||
| 2) | With not less than 5 mm gypsum plaster finish | - | |||||||
Page No 97
Table No. AC-7: Framed External Walls Non-Load Bearing [Required to Resist Fire from Inside the Building (B)]
| No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection to provide Sufficient Insulation to achieve a Modified Fire Resistance of Upto 240 min | ||
| (1) | (2) | (3) | ||
| i) | Steel frame with an external cladding of sheet steel fully lapped, steel bolted and fixed to steel sheeting rails, with timber or steel supporting framework and internal lining of: | |||
| a) | Metal lath and plaster, thickness of plaster: | |||
| 1) | Sanded gypsum plaster (metal lathing grade) | 13 | ||
| 2) | Lightweight aggregate gypsum plaster | 10 | ||
| b) | One layer of plasterboard with joints taped and filled | 12.7 | ||
| c) | Plasterboard of thickness with not less than 5 mm gypsum plaster finish | 9.5 | ||
| d) | One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber | 9 | ||
| e) | One layer of wood/wool slabs | 25 | ||
| f) | One layer of compressed straw building slabs | 50 | ||
| g) | One layer of chipboard or of plywood | 18 | ||
| h) | Aerated concrete blocks | 50 | ||
| j) | Bricks of clay | 75 | ||
| k) | Any internal decorative lining with a cavity fill independently supported and retained in position of mineral fibre insulating material (excluding glass) at a density of 48 kg/m3 | 50 | ||
Table No. AC-8: Framed External Walls Non-Load Bearing [Required to Resist Fire from Inside the Building (C)]
| No | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance of 90 min | ||
| (1) | (2) | (3) | ||
| i) | Timber frame with external cladding of weather boarding or external plywood, 9.5 mm with an internal lining of: | |||
| a) | Plasterboard not less than 9.5 mm thick, finished with: | |||
| 1) | Gypsum plaster | 13 | ||
| 2) | Lightweight aggregate gypsum plaster | 10 | ||
| b) | Plasterboard not less than 12.7 mm thick, finished with: | |||
| 1) | Gypsum plaster | 10 | ||
| 2) | Lightweight aggregate gypsum plaster | 10 | ||
| c) | One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick. | 9 | ||
| or by timber | 12 | |||
PageNo 98
Table No. AC-9: Reinforced Concrete Columns
| No. | Nature of Construction and Materials | Minimum Dimensions (mm) of Protection for a fire Resistance of | |||||||
| 30 min | 60 min | 90 min | 120 min | 180 min | 240 min | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | ||
| i) | Fully exposed | a) | Width | 150 | 200 | 250 | 300 | 400 | 450 |
| b) | Cover | 40 | 40 | 40 | 40 | 40 | 40 | ||
| ii) | 50 percent exposed | a) | Width | 125 | 160 | 200 | 200 | 300 | 350 |
| b) | Cover | 40 | 40 | 40 | 40 | 40 | 40 | ||
| iii) | One face exposed | a) | Thickness | 100 | 120 | 140 | 160 | 200 | 240 |
| b) | Cover | 40 | 40 | 40 | 40 | 40 | 40 | ||
Table No. AC-10: Concrete Beams
| No | Nature of Construction and Materials | Minimum Dimensions (mm) of Protection for a fire Resistance of | |||||||
| 30min | 60min | 90min | 120min | 180min | 240min | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | ||
| i) | Reinforced concrete (simply supported) | a) | Width | 200 | 200 | 200 | 200 | 240 | 280 |
| b) | Cover | 20 | 20 | 20 | 40 | 601) | 701) | ||
| ii) | Reinforced concrete (continuous) | a) | Width | 200 | 200 | 200 | 200 | 240 | 280 |
| b) | Cover | 20 | 20 | 20 | 30 | 40 | 501) | ||
| iii) | Prestressed concrete (simply supported | a) | Width | 100 | 120 | 150 | 200 | 240 | 280 |
| b) | Cover | 25 | 40 | 551) | 70 | 801) | 901) | ||
| iv) | Prestressed concrete (continuous) | a) | Width | 80 | 100 | 120 | 150 | 200 | 240 |
| b) | Cover | 20 | 30 | 40 | 551) | 701) | 801) | ||
| 1) Require attention to the additional measures necessary to reduce the risk of spilling. | |||||||||
Table No. AC-11: Concrete Floors
| No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of | |||||||
| 30min | 60min | 90min | 120min | 180min | 240min | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | ||
| i) | Reinforced concrete (simply supported) | a) | Thickness | 75 | 95 | 110 | 125 | 150 | 170 |
| b) | Cover | 20 | 20 | 25 | 35 | 451) | 551) | ||
| ii) | Reinforced concrete (continuous) | a) | Thickness | 75 | 95 | 110 | 125 | 150 | 170 |
| b) | Cover | 20 | 20 | 20 | 25 | 35 | 451) | ||
| 1) Require attention to the additional measures necessary to reduce the risk of spilling | |||||||||
Page No 99
Table No. AC-12: Concrete Floors: Ribbed Open Soffit
| No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of | |||||||
| 30min | 60min | 90min | 120min | 180min | 240min | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | ||
| i) | Reinforced concrete (simply supported) | a) | Thickness of floor | 75 | 95 | 110 | 125 | 150 | 170 |
| b) | Rib width | 125 | 125 | 125 | 125 | 150 | 175 | ||
| c) | Cover | 20 | 20 | 35 | 451) | 551) | 651) | ||
| ii) | Reinforced concrete (continuous) | a) | Thickness of floor | 75 | 95 | 110 | 125 | 150 | 170 |
| b) | Rib width | 125 | 125 | 125 | 125 | 150 | 175 | ||
| c) | Cover | 20 | 20 | 20 | 35 | 451) | 551) | ||
| 1) | |||||||||
- Require attention to the additional measures necessary to reduce the risk of spilling
Table No. AC-13: Encased Steel Columns, 203 mm x 203 mm
| No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish for a Fire Resistance of | ||||||
| 60 min | 90 min | 120 min | 180 min | 240 min | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | ||
| i) | Hollow protection (without an air cavity over the flanges): | |||||||
| a) | Metal lathing with trowelled lightweight aggregate gypsum plaster1) | 13 | 15 | 20 | 32 | - | ||
| b) | Plasterboard with 1.6 mm wire binding at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified: | |||||||
| 1) | 9.5 mm plaster board | 10 | 15 | - | - | - | ||
| 2) | 19 mm plaster board | 10 | 13 | 20 | - | - | ||
| c) | Asbestos insulating boards, thickness of board: | |||||||
| 1) | Single thickness of board, with 6 mm cover fillets at transverse joints | - | 19 | 3. | - | - | ||
| 2) | Two layers, of total thickness | - | - | - | 38 | - | ||
| d) | Solid bricks of clay, composition or sand lime, reinforced in every horizontal joint, unplastered | 50 | 50 | 50 | 75 | 100 | ||
| e) | Aerated concrete blocks | 60 | 60 | 60 | - | - | ||
| f) | Solid blocks of lightweight concrete hollow protection (with an air cavity over the flanges) | 50 | 50 | 50 | 60 | 75 | ||
| ii) | Asbestos insulating board screwed to 25 mm asbestos battens | 12 | 19 | - | - | - | ||
| iii) | Solid protections: | |||||||
| a) | Concrete, not leaner than 1:2:4 mix (unplastered): | |||||||
| 1) | Concrete not assumed to be load bearing, reinforced) | |||||||
Page No 100
| No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish for a Fire Resistance of | |||||
| 60 min | 90 min | 120 min | 180 min | 240 min | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | |
| b) | Lightweight concrete, not leaner than 1:2:4 mix (unplastered): concrete not assumed to be load bearing, reinforced2) | 25 | 25 | 25 | 40 | 60 | |
| 1) So rued or designed, as to allow full penetration fin mechanical bond, 2) Reinforcement shall consist of steel binding wire not less than 2.3 mm in thickness, or a steel mesh weighing not less than 0.5 kg/d. in concrete protection, the spacing of that reinforcement snail not exceed 200 mm in any direction. | |||||||
Page No 101
Table No. AC-14: Encased Steel Beams, 406 mm X 176 mm (Protection Applied on Three Sides)
| No | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for fire Resistance of | |||||||
| 30min | 60min | 90min | 120min | 180min | 240min | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | ||
| i) | Hollow protection (without an air cavity beneath the lower flange): | ||||||||
| a) | Metal lathing with trowelled lightweight aggregate gypsum plaster1) | 13 | 13 | 15 | 20 | 25 | - | ||
| b) | Plasterboard with 1.6 mm wire binding2) at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified: | ||||||||
| 1) | 9.5 mm plaster board | 10 | 10 | 15 | - | - | - | ||
| 2) | 19 mm plaster board | 10 | 10 | 13 | 20 | - | - | ||
| c) | Asbestos insulating boards, thickness of board: | ||||||||
| 1) | Single thickness of board, with 6 mm cover fillets at transverse joints | - | - | 19 | 25 | - | - | ||
| 2) | Two layers of total thickness | 38 | 50 | ||||||
| ii) | Hollow protection (with an air cavity below the lower flange): | ||||||||
| a) | Asbestos insulating board screwed to 25 mm asbestos battens | 9 | 12 | - | - | - | - | ||
| iii) | Solid protection: | ||||||||
| a) | Concrete, not leaner than 1:2:4 mix (unplastered): | ||||||||
| 1) | Concrete not assumed to be load bearing, reinforced3) | 25 | 25 | 25 | 25 | 50 | 75 | ||
| 2) | Concrete assumed to be load bearing | 50 | 50 | 50 | 50 | 75 | 75 | ||
| b) | Lightweight concrete4), not leaner than 1:2:4 (mix) unplastered | ||||||||
Page No 102
Table No. AC-15: Timber Floors – Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 21 mm Finished Thickness
| No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for fire Resistance of | ||||
| 30 min | 60min | 120min | ||||
| (1) | (2) | (3) | (4) | (5) | ||
| i) | 37 mm (minimum) timber joists with a ceiling of: | |||||
| a) | Timber lathing and plaster, plaster of thickness | 15 | - | - | ||
| b) | Metal lathing and plaster, thickness of plaster: | |||||
| 1) | Sanded gypsum plaster (metal lathing grade) | 15 | - | - | ||
| 2) | Lightweight aggregate gypsum plaster | 13 | 13 | 25 | ||
| c) | One layer of plasterboard with taped and filled joints | 12.7 | - | - | ||
| d) | Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness | 19 | 31 | - | ||
| e) | One layer of plasterboard not less than 9.5 mm thick, finished with: | |||||
| 1) | Gypsum plaster | 5 | - | - | ||
| 2) | Sanded gypsum plaster | 13 | - | - | ||
| 3) | Lightweight aggregate gypsum plaster | 13 | - | - | ||
| f) | One layer of plasterboard not less than 12.7 mm thick, finished with: | |||||
| 1) | Gypsum plaster | 5 | - | - | ||
| 2) | Lightweight aggregate gypsum plaster | 10 | - | - | ||
| g) | One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber | 9 | 12 | - | ||
Page No 103
Table No. AC-16: Timber Floors – Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 15 mm Finished Thickness
| No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for fire Resistance of | ||||
| 30 min | 60 min | 120 min | ||||
| (1) | (2) | (3) | (4) | (5) | ||
| i) | 37 mm (minimum) timber joists with a ceiling of: | |||||
| a) | Timber lathing and plaster, plaster of thickness | 15 | - | - | ||
| b) | Metal lathing and plaster, thickness of plaster: | |||||
| 1) | Sanded gypsum plaster (metal lathing grade) | 15 | - | - | ||
| 2) | Lightweight aggregate gypsum plaster | 13 | 13 | 25 | ||
| c) | One layer of plasterboard with taped and filled joints | 12.7 | - | - | ||
| d) | Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness | 22 | 31 | - | ||
| e) | One layer of plasterboard not less than 9.5 mm thick, finished with: | |||||
| 1) | Gypsum plaster | 5 | - | - | ||
| 2) | Sanded gypsum plaster | 15 | - | - | ||
| 3) | Lightweight aggregate gypsum plaster | 13 | - | - | ||
| f) | One layer of plasterboard not less than 12.7 mm thick, finished with: | |||||
| 1) | Gypsum plaster | 5 | - | |||
| 2) | Lightweight aggregate gypsum plaster | 10 | - | - | ||
| g) | One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber | 9 | 121) | - | ||
| 1)Finished on top with 25 mm minimum thick glass fibre or mineral wool laid between joints. | ||||||
Page No 104
Table No. AC-17: Timber Floors – Any Structurally suitable flooring of Timber or Lignocellulose Boards
| No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for fire Resistance of | |||
| 30 min | 60 min | ||||
| (1) | (2) | (3) | (4) | ||
| i) | 37 mm (minimum) timber joists with a ceiling of: | ||||
| a) | Timber lathing and plaster, plaster of thickness | 15 | - | ||
| b) | Metal lathing and plaster, thickness of plaster for: | ||||
| 1) | Sanded gypsum plaster (metal lathing grade) | 15 | - | ||
| 2) | Lightweight aggregate gypsum plaster | 13 | 19 | ||
| c) | One layer of plasterboard with joints taped and filled and backed by timber | 12.7 | - | ||
| d) | Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness | 25 | - | ||
| e) | Two layers of plasterboard, each not less than 9.5 mm thick, joints between boards staggered, and outer layer finished with gypsum plaster | 5 | |||
| f) | One layer of plasterboard not less than 9.5 mm thick, finish with: | ||||
| 1) | Sanded gypsum plaster | 13 | - | ||
| 2) | Lightweight aggregate gypsum plaster | 15 | - | ||
| g) | One layer of plasterboard not less than 12.7 mm thick, finished with: | ||||
| 1) | Sanded gypsum plaster | 15 | - | ||
| 2) | Lightweight aggregate gypsum plaster | 13 | - | ||
| h) | One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber | 12 | - | ||
Page No 105