The design of any building and the type of materials used in its construction are important factors in making the building resistant to a complete burn-out and in preventing the rapid spread of fire, smoke or fumes, which may otherwise contribute to the loss of lives and property.
The fire resistance of a building or its structural and non-structural elements is expressed in minutes against a specified fire load which is expressed in kcal/m2, and against a certain intensity of fire. The fire-resistance test for structural element shall be done in accordance with accepted standards.
Types of construction according to fire resistance shall be classified into four categories:
a) Type 1 Construction,
b) Type 2 Construction,
c) Type 3 Construction
d) Type 4 Construction.
The minimum fire resistance ratings of structural and non-structural members for various types of construction shall be as given in Table No. 14.3. Non-combustible materials should be used for construction of buildings, and the internal walls of staircase enclosures should be of brick work or reinforced concrete or any other material of construction with minimum of 120 min rating. The walls for the chimney shall be of Type 1 or Type 2 Construction depending on whether the flue gas temperature is above 200°C or less, respectively. Load bearing steel beams and columns of buildings having total covered area of 500 m2and above shall be protected against failure/collapse of structure in case of fire.
It is required that a structural and/or non-structural element/component shall have the requisite fire resistance rating (Refer Table No. 14.3). The fire resistance rating for the structural and non-structural elements shall be based on guidelines as per approved and accepted standards. The fire rating shall be validated and certified with a view to meeting the requirements of Table No. 14.3. In the absence of any validated/certified rating, guidance may be obtained from the information available in Annexure C.
Load bearing steel beams and columns of buildings having total covered area of 5 0 0 ~ m 2 and above shall be protected against failure/collapse of structure in case of fire. This could be achieved by use of appropriate methodology using suitable fire resistance rated materials along with suppression system (Refer Annexure C, Table 25 and Table 26 Timber Floors).
The false ceiling, including all fixtures used for its suspension, shall be of non-combustible material and shall provide adequate fire resistance to the ceiling in order to prevent spread of fire across ceiling.
Page No 28
Table No.14.3: Fire Resistance Ratings of Structural and Non-Structural Elements (minutes)
| No. | Structural Element | Fire Resistance Ratings (min) for Type of Construction | |||||
| Type1 | Type2 | Type3 | Type4 | ||||
| (1) | (2) | (3) | (4) | (5) | (6) | ||
| i) | Exterior walls: | ||||||
| a) | Fire less than 3.7 m: | ||||||
| 1) | Bearing | 240 | 120 | 120 | 60 | ||
| 2) | Non-bearing | 120 | 90 | 60 | 60 | ||
| b) | Fire separation of 3.7 m or more but less than 9 m | ||||||
| 1) | Bearing | 240 | 120 | 120 | 60 | ||
| 2) | Non-bearing separation | 90 | 60 | 60 | 60 | ||
| c) | Fire separation of 9 m or more: | ||||||
| 1) | Bearing | 240 | 120 | 120 | 60 | ||
| 2) | Non-bearing | 60 | 60 | 60 | 60 | ||
| ii) | Fire separation assemblies (like fire check doors) | 120 | 120 | 120 | 120 | ||
| iii) | Fire enclosures of exits | 120 | 120 | 120 | 120 | ||
| iv) | Shafts for services, lift hoist way and refuse chutes | 120 | 120 | 120 | 120 | ||
| v) | Vertical separation between adjacent tenant spaces | 60 | 60 | 60 | 60 | ||
| vi) | Dwelling unit separation: | ||||||
| a) | Load bearing | 120 | 120 | 60 | 60 | ||
| b) | Non-load bearing | 60 | 60 | 30 | 30 | ||
| vii) | Interior bearing walls, bearing partitions, columns, beams, girders, trusses (other than roof trusses) and framing: | ||||||
| a) | Supporting more than one floor | 240 | 120 | 120 | 120 | ||
| b) | Supporting one floor only | ||||||