1 Life Safety
a) Subdivision B-1 / B-2
i Panic bars shall be provided in the fire exits. Panic bars shall be located at a height between 865 mm and 1220 mm from the floor level.
ii All guest rooms and suites shall be protected by extended throw, quick response type sprinklers only. Also, these areas shall be provided with audio-based detectors, having a sound level of at least 75 dB.
iii Horizontal-sliding doors shall not be used for door openings across corridors.
b) Subdivision B-3
Page No 73
All locking devices, which would impede or prohibit exit, such as chain type bolts, limited opening sliding type locks and burglar locks, which are not disengaged easily by quick releasing catches, shall be prohibited.
ii All bathroom door locks or fasteners shall be designed to permit the opening of the locked or closed door from the outside in an emergency without the use of a special key.
iii No lodging or rooming house shall have its sole means of egress pass through any non-residential occupancy in the same building.
iv Rooming and lodging houses having floor area of 500 m2 on any one or more floors shall have access to minimum two separate means of exits, at least one of which shall be so arranged as to have direct exit discharge.
2 Additional Precautions
It shall be in accordance with the additional precautions for Residential buildings Group A.