The exit, exit access and exit discharge systems shall be illuminated continuously. The floors of the means of egress shall be illuminated at all points, including angles and intersections, in corridors and passageways, stairwells, landings of stairwells and exit.
Page No 33
ii) Emergency lighting shall be powered from a source independent of that supplying the normal lighting.
iii) Escape lighting shall be capable of,
• indicating clearly and unambiguously the escape routes.
providing adequate illumination along such routes to allow safe movement of persons towards and through the exits; and
ensuring that fire alarm call points and firefighting equipment provided along the escape routes can be readily located.
iv) The horizontal luminance at floor level on the centreline of an escape route shall not be less than 10 lumen/m2. In addition, for escape routes up to 2 m wide, 50 percent of the route width shall be lit to a minimum of 5 lumen/m2. In auditoriums, theatres, concert halls and such other places of assembly, the illumination of floor exit/access may be reduced during period of performances to values not less than 2 lux.
v) Required illumination shall be arranged such that the failure of any single lighting unit, such as the burning out of one luminaire, will not leave any area in darkness and does not impede the functioning of the system further.
vi) The emergency lighting shall be provided to be put on within 5s of the failure of the normal lighting supply. Also, emergency lighting shall be able to maintain the required illumination level for a period of not less than 90 min in the event of failure of the normal lighting even for smaller premises.
vii) Battery pack emergency lighting, because of its limited duration and reliability, shall not be allowed to be used in lieu of a diesel engine driven emergency power supply.
viii) Escape lighting luminaires should be sited to cover the following locations:
Near each intersection of corridors,
At exits and at each exit door,
Near each change of direction in the escape route,
Near each staircase so that each flight of stairs receives direct light,
Near any other change of floor level,
Outside each final exit and close to it,
Near each fire alarm call point,
Near firefighting equipment, and
To illuminate exit and safety signs as required by the enforcing authority.
ix) The luminaires shall be mounted as low as possible, but at least 2 m above the floor level.
x) Signs are required at all exits, emergency exits and escape routes, which should comply with the graphic requirements of the relevant Indian Standards.
b) Exit passageway (at ground) and staircase lighting shall also be connected to alternative supply. The alternative source of supply may be provided by battery continuously trickle charged from the electric mains.
c) Suitable arrangements shall be made by installing double throw switches to ensure that the lighting installed in the staircase and the corridor does not get connected to two sources of supply simultaneously. Double throw switch shall be installed in the service room for terminating the stand-by supply.
The emergency lighting system shall be well maintained by periodical inspections and tests so as to ensure their perfect serviceability at all times.