a) Interior stair shall be constructed of non-combustible materials throughout;
b) Interior staircase shall be constructed as a self-contained unit with at least one side adjacent to an external wall and shall be completely enclosed;
c) A staircase shall not be arranged around a lift shaft unless the latter is entirely enclosed by a material of required fire- resistance rating. For buildings more than 15m. in height, the staircase location shall be to the satisfaction of Fire Officer, Fire Brigade Authority, wherever necessary.
d) Hollow combustible construction shall not be permitted.
e) The minimum width of an internal staircase shall be as per the provisions of Regulation no. 17.3.5.
f) The minimum width of treads without nosing shall be 25 cm. for an internal staircase for residential buildings. In the case of other buildings, the minimum treads shall be 30 cm. The treads shall be constructed and maintained in a manner to prevent slipping.
g) The maximum height of riser shall be 20 cm. in the case of residential buildings and 15 cm. in the case of other buildings. They shall be limited to 12 per flight. For low income housing scheme in narrow plots, the riser may be provided in one flight.
h) Handrails shall be provided with a minimum height of 90 cm. from the tread,
i) The minimum unobstructed headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
j) No living space, store or other fire risk spaces shall open directly into the external staircase or staircases.
k) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through a large lobby.
l) In the case of assembly, institutional, residential hotels, industrial and hazardous occupancies,
the exit sign with arrow indicating the way to the escape route shall be provided on the wall / floor and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further all landings of floor shall have floor indication boards indicating the floor number. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of appropriate size.
m) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. Wherever the building is served by more than one staircase, one of the staircases may lead to basement levels, provided the same is separated at ground level by either a ventilated lobby or cut-off screen wall without opening, having a fire resistance of not less than 2 hours with discharge point at two different ends or through enclosures. It shall also be cut off from the basement areas at various basement levels by a protected and ventilated lobby / lobbies. The staircase shall be lighted and ventilated and the minimum size of openings on walls abutting to open spaces shall be 0.3 sq. m. per landing.