16.11.1 Basement shall generally be constructed within the prescribed setbacks and prescribed building line in one or two level and may be put to only following uses: Following user shall be permissible free of FSI. (i) Air conditioning equipment and other machines used for services and utilities of the building; (ii) Parking spaces and (iii) Strong room, bank cellars, radio/laser therapy unit etc. Following user shall be permissible and counted in FSI. (i) Storage incidental to principle use (ii) Commercial uses. Provided that if the basement is constructed below ground level and only for parking, then such basement can be extended in side and rear margins upto 3 m. form the plot boundary.
16.11.2 The basement shall not be used for any other user than mentioned above.
16.11.3 Multilevel basements may be permitted if the basement is used for parking. The ramps of minimum 3.0 m. width for entry and exit of vehicle separately shall be provided. In case of bona-fide hardship, the Municipal Commissioner may allow only one ramp with not less than 6.0 m. in width.
16.11.4 If the basement is proposed to be constructed below podium then marginal distances shall be as that of podium.
16.11.5 The basement shall have the following requirements -
(a) Every basement shall be in every part at least 2.4 m. in height from the floor to the soffit of beam.
(b) Adequate ventilation shall be provided for the basement with a ventilation area not less than 2.5% of the area of the basement. Any deficiency may be met by providing additional adequate mechanical ventilation in the form of blowers, exhaust fans, air conditioning systems etc.
(c) The minimum height of the ceiling of any basement shall ordinarily be 0.9 m. and maximum of 1.2 m. above the average surrounding ground level. However it does not apply to the mechanically ventilated basements. In such cases, basement may also be allowed flushing to the average ground level
(d) Adequate arrangement shall be made such that surface drainage does not enter the basement.
(e) The walls and floor of the basement shall be water-tight and be so designed that the effect of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
(f) The access to the basement shall be separate from the main and alternate staircase providing access and exit from higher floors. Where the staircase is continuous in case of building served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors [see Regulation no. 17.4.3 (m)] Open ramps shall be permitted if they are constructed within the building line subject to the provision of (d).