15.8.1 The following projections shall be permissible in marginal distances:
(a) Projections into marginal distances:- Every marginal distances provided either interior or exterior shall be kept free from any erection thereon and shall be open to the sky and no cornice, chajja, roof or weather shade more than 0.75 m. wide shall overhang or project over the said marginal distances so as to reduce the width to less than the minimum required.
However, sloping/horizontal chajja provided over balcony/ gallery etc. may be permitted upto <s>to project 0.3 m. beyond</s> balcony projections at <s>an angle of 30 degree from</s> horizontal level.
(b) A canopy not exceeding 5m. in length and 2.5 m. in width in the form of cantilever and unenclosed over the main entrance providing a minimum clear height of 2.40 m. below the beam bottom of canopy. The canopy shall not have access from upper floors (above floors), for using as sitting out place. There shall be a minimum clearance of 1.5 m. between the plot boundaries and canopy.
Provided that more than one canopy may be allowed in case of special buildings, as per requirement.
(c) Balcony :- Balcony or balconies of a minimum width of 1.00 m. subject to maximum of 2.00 m. may be permitted free of F.S.I. at any upper floor, not more than 15% of the built up area of the same floor and such balcony projection shall be subject to the following conditions.
(i) In non-core area, balcony may only be permitted on upper floors (except ground floor) and no balcony shall reduce the marginal distance to less than 2 m. In core area, balcony may only be permitted on upper floors projecting in front setbacks except over lanes having width 4.50 m. or less and subject to 1.00 m. clear marginal distance from plot boundary to the external face of the balcony.
(ii) The width of the balcony will be measured perpendicular to the building upto the outermost edge of balcony.
(iii) Balconies may be allowed to be enclosed on payment of premium at the rate of 10% of market value for land as per Annual Statement of Rates. The area taken for computing premium shall be equal to the built up area of enclosed balcony. This may be allowed at the time of approval of plans.
(iv) Balconies in excess of 15% of built up area shall be calculated in FSI.
(v) Nothing shall be allowed beyond the outer edge of balcony.
(vi) The constructed area which is not cantilever and form the part of built-up area shall not be treated as enclosed balcony in any case.
(d) A projection of maximum 30 cm. on roof top terrace level may be allowed throughout the periphery of the building. In case of pitched roof projection of maximum 45 cm. at roof top terrace level throughout periphery of the building shall be allowed.
(e) Accessory buildings:- The following accessory buildings may be permitted in the marginal distances -
(i) In an existing building where toilet is not provided, a single storeyed toilet subject to a maximum area of 4.0 sq. m. in the rear or side marginal distance and at a distance of 7.5 m. from the road line or the front boundary and 1.5 m. from other boundaries may be permissible. The Municipal Commissioner may reduce 1.5 m. margin in exceptional cases to avoid hardship.
(ii) Parking lock up garage not exceeding 2.4 m. in height shall be permissible in the rear corner of the plot with independent bungalow. Parking lock up garage when attached to main building shall be 7.5 m. away from the road line and shall be of such constructions giving fire resistance of 2 hours. The area of parking lock up garage shall be taken into account for the calculation of FSI.
(iii) Suction tanks, soak pits, pump room, electric cabin of substation or gen-set area, electric meter room as per requirement, garbage shaft for wet and dry garbage separately with collection chamber, space required for fire hydrants, electrical and water-fittings, water
tanks, dustbins, etc.
(iv) One watchman's cabin / booth not more than 5 sq. m. in built up area having min. 1.80 m. width or diameter of cabin / booth for each entrance to the campus.
Note :- When a building abuts on three or more roads then above mentioned user, except (iv), shall be permissible in front setback facing the smaller road or less important from traffic point of view.
(f) "Ramp" for basement, in side and rear marginal distances. In case of special buildings, ramps may be allowed, subject to 6.0 m. clear marginal distance for movement of fire fighting vehicle
(g) Staircase mid-landing of 1.2 m. width with clear minimum headway of 2.1 m. below the midlanding. However, clear distance from edge of landing to the plot boundary shall not be less than 1.8 m. In case of special buildings, this shall be subject to 6.0 m. clear marginal distance.
(h) Cupboard/Shelves of size stipulated in these regulations.
(i) Architectural projections upto 1.00 m. which will not reduce the marginal space more than 2.00 m.
15.8.2 Exclusion of structures / projections for FSI calculation
All structures, excluding following, shall be counted in FSI.
(a) Structures/ Projections mentioned in Regulation 15.8.1 (a), (b), (c), (d), (e)(i), (e)(iii), (f), (g), (i)
(b) Stilt / Multi-storeyed floor space used as parking.
(c) A basement/s under a building and used for meter room, air-conditioning plant, electric substation and parking spaces (use accessory to the principal use).
(d) Areas covered by (i) Lofts (ii) Service floor of height not exceeding 1.8 m. for hotels rating with three stars and above and hospitals .
(e) Area of structure for an effluent treatment plant as required as per the requirements of the Maharashtra Pollution Control Board or other relevant authorities.
(f) Areas covered by service ducts, stilt. Area of lifts on all floors excluding any one floor.
(g) Rockery, well and well structures, plant, nursery, water pool, swimming pool (if uncovered), platform around a tree, fountain bench, chabutara with top and unenclosed sides, ramps, compound wall, gate slide / swing, steps outside the buildings, domestic working place (open to sky), overhead water tank on top of the building and refuge area for high rise buildings.
(h) Area covered by new lift and passage thereto in an existing building with height upto15m., in core area.
(i) Telecommunication tower, antenna and construction of a room having upto 20 sq.m. area for allied activities.
(j) Structure permissible in recreational open space in layout or group housing scheme.
(j) Atrium in any building. Atrium may be allowed to be covered on top with transparent sheets.
(k) Escalators as provided in Regulation no.17.4.9.2.
15.8.3 Exclusion of structures / projections for FSI calculation subject to payment of premium:
(a) Supported double height terraces (open terraces with railing having minimum height equal to two floors) within the building line, not exceeding 20 % of the built up area of the same floor.
(b) Such terraces in excess of 20 % area shall be calculated in FSI.
(c) Nothing shall be allowed to be projected beyond and attached to the outer edge of the double height terrace.
(d) Premium shall be charged at the rate of 10% of market value for land as per Annual Statement of Rates.