Special regulations for schools
Buildings of schools shall conform to the following special regulations:
1.Site
Site of the school building
[a] shall not have opening direct to the National / State Highways with heavy vehicular traffic.
[b] shall not be close to water bodies and forests.
[c] shall not be in the close proximity of garbage dumps, dusty and noisy roads or factories.
2.No. of floors
The provisions in the National Building Code 2016 in all aspects apart from adherence to these rules.
3.Stair case and exits shall conform to the following minimum standards.
[a] Minimum width 1.6m
[b] One stair case for every 6 class rooms
[c] Mid landing not less than 1.6m in width
[d] Continuous stairs from ground level to the terrace level.
[e] Travel distance to the stair case from any part of upper floors shall not be more than 22.6m.
[f] Exit door if any from the stair case at the ground level shall open directly to the open space and it shall not be less than 2m in width and 2.1m in height.
4.Class rooms shall confirm to the following:
[a] Minimum size shall be 6m x 6m for student strength of not exceeding 40 Nos.
[b] Thickness of wall shall not be less than 23 cms.
[c] Head room height of the class rooms shall be minimum 3metres.
[d] Each class room shall have at least 2 doors and 2 windows
[e] Doors and windows should be made of materials with high fire resistance rating.
5.Fire safety measures
[a] Adequate no. of fire extinguishers shall be provided
[b] Provision of separate water tank / sump to meet the requirement of fire fighting during emergency shall be provided.
[c] Buildings shall be constructed using non-combustible materials.
6.Electrical wiring, equipments and installations shall confirm to the safety standards prescribed in the NBC and also confirm to the requirements of the Chief Electrical Inspectorate.
7.Others
[a] Kitchen if any located within the school premises shall not be closer to the class rooms or student toilets.
[b] Where covered verandah / corridor is provided, it shall be minimum 1.8m. in width in front of class rooms.
[c] The parapet wall in the open terrace shall be minimum 23cm in thickness and 100cm in height.
[d] Toilets enough in number and with adequate water supply shall be provided.