A cool roof is one that reflects most of the incident solar radiation and efficiently emits some of the absorbed radiation back into the atmosphere, instead of conducting it to the building below.30 The term specifically refers to the outer layer or exterior surface of the roof, which acts as the key reflective surface.31 A cool roof minimizes the solar heat gain of a building by first reflecting a considerable amount of incoming radiation and then by quickly re-emitting the absorbed portion. Cool roof encompasses an extensive array of applications including roof coatings, colours, textures, finishes such as broken china mosaic, tiles, and even metals.
However, cool roofs are not to be seen as an alternative to the thermal transmittance requirement of the roof ( U r o o f ) as given in this code. It is encouraged to have any cool roof application over a roof assembly complying with the maximum thermal transmittance value given in the code.
Defining a cool roof
The ‘coolness’ of a roof is influenced by its solar reflectance and thermal emittance.
Solar reflectance: Solar reflectance is the ratio of solar radiation reflected by a surface to the solar radiation incident upon it. Solar reflectance is measured on a scale of 0 to 1. A reflectance value of 0 indicates that the surface absorbs all incident solar radiation, and a value of 1 denotes a surface that reflects all incident solar radiation. The term ‘albedo’ is often used inter-changeably with solar reflectance.
Thermal emittance: Thermal emittance is the relative ability of a material to reradiate absorbed heat as invisible infrared radiation. Emittance, measured from 0 to 1, is defined as the ratio of the radiant flux emitted by a body to that emitted by a black body at the same temperature and under the same conditions.
According to ECBC 2017 cool roof requirement, roofs with slopes less than 20 degrees shall have an initial solar reflectance of at least 0.6 and an initial emittance of 0.9.
The Solar Reflectance Index (SRI) is a term that incorporates both solar reflectance and emittance in a single value and quantifies how hot a surface would get relative to standard black and standard white surfaces. It is the ability of a material to reject solar radiation, as shown by a small temperature rise.32 The SRIs of a standard black surface (having
30 Shakti Foundation. 2017. Cool Roofs for Cool Delhi: Design Manual. Available at http://shaktifoundation.in/wp-content/uploads/2017/06/cool-roofs-manual.pdf (accessed on 1 May 2018)
31 ibid
32 Bureau of India Standards (BIS). 2016. National Building Code 2016. Part 11. New Delhi: BIS
56
ANNEXURE 10
reflectance of 0.05 and emittance of 0.9) and a standard white surface (of reflectance 0.8 and emittance 0.9) are taken as 0 and 100, respectively.
IGBC Green Homes requires a minimum SRI value of 78 for roof slopes with gradient ≤1:6 and 29 for steeper roof.
For more detailed information on cool roof, please refer Cool Roofs for Cool Delhi: Design Manual.33
Roof Gardens
In the case of roofs with roof gardens on earth fill for plantation or lawn, the thermal resistance of the earth fill can be taken into the calculation of the thermal transmittance (U value) of the roof. Some of the heat absorbed by the earth fill is also released into the atmosphere due to evapotranspiration of irrigation water from the roof garden, thus giving additional benefit.
3 Shakti Foundation. 2017. Cool Roofs for Cool Delhi: Design Manual. Available at http://shaktifoundation.in/wp-content/uploads/2017/06/cool-roofs-manual.pdf (accessed on 01 May 2018)
Bureau of Energy Efficiency (BEE)